background image

VSWR and AGC circuits and additionally from U2A which is a ‘mute’ type signal.  R5 
controls the threshold of control of these signals.  The circuit configuration comprising 
CR1, CR2 and CR3 form a matched attenuator, biased by the output of U2B, R2, R3, R7 
and R8.  As the output of U2B rises, the attenuation of the circuit decreases, thus 
increasing the RF output as J2. 
 

METERING BOARD 
 
CIRCUIT DESCRIPTION 
 

 

The Metering board detects forward and reflected power levels and processes 

these signals to provide outputs for metering, telemetry, AGC and VSWR protection. 
 
 

The forward and reflected power detectors are ‘visual only’ detectors.  The 

description that fo llows is for the forward detector portion only; the ‘reflected’ detector is 
identical.  CR1 and Q1 form a basic detector circuit and C3, C4 and L1 trap out the 
4.5MHz aural components.  CR3 and C7 act as a peak detector providing the buffer 
circuit of U1 with a peak-level voltage. 
 
 

The outputs of the peak detectors are applied to operational amplifiers U1B and 

U2B which have a zeroing function and provide the drive for the metering circuit and 
telemetry.  These amplifiers also drive the AGC and VSWR circuits.  Operation 
amplifiers U1A and U2A compare the forward and reflected signals to preset levels and 
provide an error signal to the Pin Attenuator board.  An additional circuit consisting of 
U3 acts as a comparator to drive an LED on the indicator board as the VSWR signal rises 
about the preset level. 
 
 

Set up Procedure for Metering, VSWR and AGC Circuits 

 

 

Set the AGC/MAN Switch on the front panel to the MAN position. 

 

Terminate the output of the amplifier into a suitable 50ohm load through a 
thru- line wattmeter or equivalent. 

 

Turn the visual and aural carrier switches on the exciter to the OFF 
position. 

 

Apply DC power to the amplifier.  The blower should come on.  There 
should be no output power indication. 

 

Turn the metering switch to the 35V position.  Measure the voltage at E12 
on the Regulator board and adjust R34 for a corresponding front panel 
reading on the lower meter scale. 

 

Turn the metering switch to the 50V position.  Measure the voltage at E13 
on the Regulator board and adjust R37 for a corresponding front panel 
reading on the lower meter scale. 

 

Turn the metering switch to the FWD position and adjust R18 on the 
metering board for a zero reading on the front panel meter.  This should 
also correspond to a minimum voltage at TP1.  Repeat this procedure for 
the RFL position, R2 and TP2. 

Summary of Contents for TTS250M

Page 1: ......

Page 2: ...vely Cooling is provided by a squirrel cage type blower mounted on the rear of the slide out drawer Air is drawn through a filter in the rear door of the cabinet blown through the amplifier heatsink and exhausted through a grill at the front of the amplifier No provision is made for ducting exhaust air Metering is provided for voltage current and RF power The amplifier is VSWR protected with an au...

Page 3: ...oth stages are biased for Class A operation and each has its own set of three terminal regulators for voltage or current regulation The signal is first applied to a form of variable attenuator consisting of R2 R6 and R12 The first stage of amplification is a CA2842 hybrid IC this amplifier provides approximately 22dB of gain A coaxial cable jumper is provided between this stage and the next to all...

Page 4: ...divides the input into two equal and opposite signals Capacitors C3 C4 and the associated strip line circuitry form an impedance matching network to the gates of the FETs C1 and C2 are DC isolation blocking capacitors Capacitors C13 and C16 and associated strip line inductors form an output impedance matching network and T2 combines the out of phase signals at the output J2 C14 and C15 also act as...

Page 5: ...P transistor U2 through a Darlington transistor Q3 Short circuit protection is provided by Q1 and Q4 Q4 shunts the drive away from the base of U2 when the output current causes the voltage across R6 and R10 to rise high enough to open transistor Q1 Supply voltage for the IC is via R8 and CR3 from the 30V supply Metering outputs are provided for the supply as well as those for current drawn from ea...

Page 6: ...s Important Ensure that the primary taps on the power transformer are set as near as possible to the nominal on site line voltage Of course the system will operate with other tap settings but the range in which it will work will no longer be as wide Taps are provided for 200 208 220 230 and 242 VAC Once the nominal voltage has been established and appropriate primary tap selected the raw DC input ...

Page 7: ...ive the AGC and VSWR circuits Operation amplifiers U1A and U2A compare the forward and reflected signals to preset levels and provide an error signal to the Pin Attenuator board An additional circuit consisting of U3 acts as a comparator to drive an LED on the indicator board as the VSWR signal rises about the preset level Set up Procedure for Metering VSWR and AGC Circuits Set the AGC MAN Switch ...

Page 8: ...ontactor AC is fed to the transformer of the power supply as well as to 6F1 and 6F2 in line with the amplifier blower The contactor is energized by a solid state relay 6Z1 Interlocks are provided for the amplifier thermal cutout as well as an auxiliary interlock for customer interface The 12V from the exciter is applied through the REMOTE LOCAL Switch directly in the LOCAL position or when in the ...

Page 9: ...ons are listed in the table on the following page FUNCTION CONNECTION AUX INTERLOCK 6TB3 2 REMOTE CONTROL 6TB3 3 REMOTE TELEMETRY 65V SUPPLY 6Z2 TB1 6 REMOTE TELEMETRY 30V SUPPLY 6Z2 TB1 5 REMOTE TELEMETRY FWD POWER 6Z2 TB1 4 THERMAL CUTOUT STATUS 6Z2 TB1 1 6Z2 TB1 2 AC LINE INPUT POWER 6TB1 1 6TB1 2 NEUTRAL 6TB1 3 ...

Page 10: ......

Page 11: ......

Page 12: ......

Page 13: ......

Page 14: ......

Page 15: ......

Page 16: ......

Reviews: