LA-ON31-RACK 

 

5. Storage and Maintenance 

5.1. Storage   

Before storing, charge the UPS at least 7 hours. Store the UPS covered and upright in a cool, dry location. 

During storage, recharge the battery in accordance with the following table: 

Storage Temperature 

Recharge Frequency 

Charging Duration 

-25°C - 40°C 

Every 3 months 

1-2 hours 

40°C - 45°C 

Every 2 months 

1-2 hours 

5.2. Maintenance   

  The UPS system operates with hazardous voltages. Repairs may be carried out only by qualified 

maintenance personnel.   

 Even after the unit is disconnected from the mains, components inside the UPS system are still 

connected to the battery packs which are potentially dangerous.   

  Before carrying out any kind of service and/or maintenance, disconnect the batteries and verify that no 

current is present and no hazardous voltage exists in the terminals of high capability capacitor such as 
BUS-capacitors.  

  Only persons are adequately familiar with batteries and with the required precautionary measures may 

replace batteries and supervise operations. Unauthorized persons must be kept well away from the 
batteries.  

  Verify that no voltage between the battery terminals and the ground is present before maintenance or 

repair. In this product, the battery circuit is not isolated from the input voltage. Hazardous voltages may 
occur between the battery terminals and the ground.   

 Batteries may cause electric shock and have a high short-circuit current. Please remove all 

wristwatches, rings and other metal personal objects before maintenance or repair, and only use tools 
with insulated grips and handles for maintaining or repairing. 

  When replace the batteries, install the same number and same type of batteries.   

 Do not attempt to dispose of batteries by burning them. This could cause battery explosion. The 

batteries must be rightly deposed according to local regulation. 

  Do not open or destroy batteries. Escaping electrolyte can cause injury to the skin and eyes. It may be 

toxic.  

  Please replace the fuse only with the same type and amperage in order to avoid fire hazards.   

  Do not disassemble the UPS system. 

 

Summary of Contents for 10KR

Page 1: ...EN USER MANUAL 3Ph 1Ph 10K 20K RACK Online UPS Uninterruptible Power Supply System...

Page 2: ...operating instructions in this manual strictly Save this manual properly and read carefully the following instructions before installing the unit Do not operate this unit before reading through all sa...

Page 3: ...LLATION FOR PARALLEL SYSTEM 9 2 5 SOFTWARE INSTALLATION 11 3 OPERATIONS 12 3 1 BUTTON OPERATION ERROR MARCADOR NO DEFINIDO 3 2 LED INDICATORS AND LCD PANEL 12 3 3 AUDIBLE ALARM 14 3 4 SINGLE UPS OPERA...

Page 4: ...onnect appliances or devices that would overload the UPS e g big motor type equipment to the UPS output sockets or terminal Place cables in such a way that no one can step on or trip over them Do not...

Page 5: ...hat no liquid or other foreign objects can enter into the UPS system otherwise guarantee would not be accepted The UPS can be operated by any individuals with no previous experience 1 5 Standards Safe...

Page 6: ...Unpack the package and check the package contents The shipping package contains One UPS One user manual One monitoring software CD One RS 232 cable option One USB cable One parallel cable only availab...

Page 7: ...6 6 LA ON31 RACK Diagram 2 15KR L 20KR L Rear Panel Diagram 3 10KR 10KR L Input Output Terminal Diagram 4 15KR L 20KR L Input Output Terminal...

Page 8: ...ctions must be executed by professional personnel 1 Make sure that the mains wire and breake avoid the hazards of electric shock or fire NOTE Do not use the wall receptacle as the input power source f...

Page 9: ...leakage current protective function if necessary 6 Put the terminal block cover back to the rear panel of the UPS Warning Only for standard model Make sure that the UPS is not turned on before instal...

Page 10: ...onnection and conductance reliability should be checked carefully Make sure the utility input output wiring is correct The wire current spec color position connection and conductance reliability shoul...

Page 11: ...m for 15KR L 20KR L 2 5 Software Installation For optimal computer system protection install UPS monitoring software to fully configure UPS shutdown Install CD or visit the website http www laparaups...

Page 12: ...button to display next selection in setting menu Mute Down Button Mute the alarm Press and hold the button more than 0 5s to mute the buzzer Please refer to section 3 4 9 for details Down key Press th...

Page 13: ...cy Load information Indicates the load level by 0 25 26 50 51 75 and 76 100 Indicates overload Indicates the load or the output is short Mode operation information Indicates the UPS connects to the ma...

Page 14: ...Over temperature Overload UPS Model abnormal Continuously beeping Yes 3 4 Single UPS Operation 1 Turn on the UPS with utility power supply in AC mode 1 After power supply is connected correctly set th...

Page 15: ...disabled or the input power is not within bypass acceptable range it will cut off output directly 4 Charge the batteries 1 After the UPS is connected to the utility power the charger will charge the...

Page 16: ...se refer to section 3 3 for the details 10 Operation in warning status 1 When Fault LED flashes and the buzzer beeps once every second it means that there are some problems for UPS operation Users can...

Page 17: ...utility power supply in AC mode a Turn on the input breaker of each UPS After all UPSs enter to bypass mode measure the voltage difference between the output of each UPS with a multimeter If the volt...

Page 18: ...h UPS and then turn off the running system All UPSs will transfer to bypass mode Remove all the maintenance bypass covers and set the maintenance switches from UPS to BPS Turn off all the input breake...

Page 19: ...the UPS Refer to following diagram Parameter 1 It is for program alternatives There are 14 programs to set up Refer to below table Parameter 2 and parameter 3 are the setting options or values for eac...

Page 20: ...Y Y Yes means that this program can be set in this mode It is only available to operate when a loss of neutral line is detected Otherwise it will display in program setting menu This function can get...

Page 21: ...will transfer to battery mode when input frequency is not within 56 64 Hz If Parameter 2 is ATO the Parameter 3 will show the current frequency Note For single unit it will have bypass output for a c...

Page 22: ...g Parameter 2 OPN Bypass allowed When selected UPS will run at Bypass mode depending on bypass enabled disabled setting FBD Bypass not allowed When selected it s not allowed for running in Bypass mode...

Page 23: ...3 when entering the setting menu next time z 13 Battery voltage adjustment Interface Setting Parameter 2 Select Add or Sub function to adjust battery voltage to real figure Parameter 3 the voltage ran...

Page 24: ...which L2 delay L1 120 L3 delay L2 120 or L2 delay L1 240 L3 delay L2 240 3 8 Operating Mode Status Description The following table shows LCD display for operating modes and status 1 If the UPS is in...

Page 25: ...r into no output mode if powering on or turning off the UPS It means that the UPS has no output Alarm beeps every two minutes No output mode LCD Display Description When the input voltage is within ac...

Page 26: ...g ECO mode LCD display Description When input frequency is within 46 64Hz the UPS can be set at a constant output frequency 50Hz or 60Hz The UPS will still charge battery in this mode CVCF mode LCD di...

Page 27: ...ss mode LCD display Description When UPS is in AC mode or CVCF mode press Test key for more than 0 5s Then the UPS will beep once and start Battery Test The line between I P and inverter icons will bl...

Page 28: ...cond Battery unconnected Beeping every second Over charge Beeping every second EPO enable Beeping every second Fan failure Over temperature Beeping every second Charger failure Beeping every second I...

Page 29: ...excess loads from UPS output first Then shut down the UPS and restart it Fault code is shown as 43 The icon lights on LCD display and alarm beeps continuously UPS is overload too long and becomes faul...

Page 30: ...with the required precautionary measures may replace batteries and supervise operations Unauthorized persons must be kept well away from the batteries Verify that no voltage between the battery termin...

Page 31: ...urrent 1 A 10 max 2 A 10 max Standard Model Charging Voltage 14 4 V 1 Type Depending on applications Numbers 18 20 Charging Current 4 A 10 max Long run Model Charging Voltage 14 4 V 1 PHYSICAL Dimensi...