INSTALLATION
DANGER
THIS APPLIANCE MUST BE GROUNDED AT THE TERMINAL PROVIDED.
FAILURE TO GROUND THE APPLIANCE COULD RESULT IN
ELECTROCUTION AND DEATH.
WARNING
INSTALLATION OF THE UNIT MUST BE DONE BY PERSONNEL
QUALIFIED TO WORK WITH ELECTRICITY AND PLUMBING. IMPROPER
INSTALLATION CAN CAUSE INJURY TO PERSONNEL AND/OR DAMAGE
TO EQUIPMENT. UNIT MUST BE INSTALLED IN ACCORDANCE WITH ALL
APPLICABLE CODES.
NOTICE
The data plate is located on the right hand side of the oven. Voltage,
wattage, serial number, wire size, and clearance specifications are on the
data plate. This information should be carefully read and understood
before proceeding with the installation.
NOTICE
The installation of any components such as a vent hood, grease
extractors and fire extinguisher systems must conform to their applicable
National, State and locally recognized installation standards.
Range Installation
The Range will come pre-assembled with the casters already installed.
Electrical Connection
The electrical connection must be made in accordance with local codes or, in the
absence of local codes, with
NFPA No. 70,
latest edition (in Canada use
CSA
STD. C22.1
).
The electrical service entrance is provided by a 1-1/4-inch knockout at the range
back directly behind the control compartment. A grounding lug is provided at the
rear service entrance.
The CR30 (PT) may have been purchased with a cord & plug kit. This kit includes
a 48” cord with a
NEMA L15-30P
plug.
Range Voltage
The Lang Model CR30 range operates as shipped on either 208V or 240V (single
or three phase) and 480V (three phase). Amperages, KW rating and phasing can be
found in the wiring diagram section of this manual.