INSTALLATION CONT’D 

 

GAS CONNECTION 

This appliance must be installed under a ventilation hood.  The installation of any 
components such as vent hoods, grease extractors, fire and smoke detection 
devices, or fire extinguisher systems, must conform to N.F.P.A Standard #96, latest 
edition. 
This appliance is manufactured for use with the type of gas indicated on the data 
plate.  Contact the factory if the gas type does not match that which is on the data 
plate. 
All gas connections must be in accordance with local codes and comply with the 
National Fuel Gas Code ANSI Z223.1 latest edition. 
Gas must be delivered to the appliance regulator at less than 1/2 pound of pressure 
and less than 1/2 inch water column pressure drop. 
The regulator on this appliance is set to 6 inches water column for natural gas and 
10 inches water column for propane.  A 1/8 inch NPT tap is provided on the main 
manifold for checking regulator pressure. 
When replacing the 1/8 inch plug in the main manifold a joint sealant that is 
resistant to the action of liquid petroleum gas must be used. 
The supply piping must be of sufficient size to provide 10,000 BTU/hr per foot of 
Cheesemelter.  A 1/2 inch NPT connection is provided at the lower right rear 
corner. 
A gas shut off valve must be installed to the appliance and located in an accessible 
area.  In the event of a significant drop in gas pressure, turn the shut off valve off 
and contact your gas supplier. 
This appliance and its individual shutoff valve must be disconnected from the gas 
supply piping system during any pressure testing of that system at test pressures in 
excess of 1/2 PSGI (3.45 kPA) and the appliance must be isolated from the gas 
supply piping system by closing its individual manual shutoff valve during any 
pressure testing of the gas supply system at test pressures equal to or less than 1/2 
PSIG (3.45 kPA). 
Test for gas leaks.  Use a commercial leak detector or a soap and water solution. 

 

 

NOTICE 

Do not install the Cheesemelter over a Charbroiler or any other open 
flame appliance. 

 

VENTILATION AND CLEARANCES 

Standard minimum clearance from combustible construction is as follows: 

To prevent the function of this appliance from being affected by a reduced 
atmospheric pressure, adequate make-up air in the kitchen should be provided to 
replace the air taken out by the ventilating system. 

6” from side 
0” from back 
4” from floor or 12” from high heat source 
 

When mounting over a range top griddle or any other high heat source a bottom 
clearance of 12” must be maintained and the heat shield (provided with all wall 
mount units) must be installed.  Failure to maintain this clearance and / or to install 
the heat shield will the equipment warranty 

 

 

 

Summary of Contents for 236CM

Page 1: ...cturing 10 Sunnen Drive St Louis MO 63143 Part 2M 60803 02 Phone 314 678 6315 Fax 314 781 2714 Rev C www langworld com July 22 2008 Installation Operation Maintenance Model 236CM 248CM Gas Infrared Ch...

Page 2: ...D MAY RESULT IN MINOR OR MODERATE INJURY NOTICE Helpful operation and installation instructions and tips are present FOR YOUR SAFETY DO NOT STORE OR USE GASOLINE OR OTHER FLAMMABLE VAPORS AND LIQUIDS...

Page 3: ...FOLLOW THE INSTRUCTIONS AND WARNINGS CONTAINED IN THIS MANUAL TABLE OF CONTENTS CHAPTER PAGE TABLE OF CONTENTS 3 READ FIRST 4 SAFETY PROCEDURES 6 EQUIPMENT DESCRIPTION 7 UNPACKING 8 INSTALLATION 9 INI...

Page 4: ...fications are on the data plate This information should be carefully read and understood before proceeding with the installation NOTICE The installation of any components such as a vent hood grease ex...

Page 5: ...G service agent nearest you WARNING BOTH HIGH AND LOW VOLTAGES ARE PRESENT INSIDE THIS APPLIANCE WHEN THE UNIT IS PLUGGED WIRED INTO A LIVE RECEPTACLE BEFORE CLEANING SERVICING OR REPLACING ANY PARTS...

Page 6: ...ntrol and interlocks on an appliance and attendant components of installation cannot in and of themselves assure absolute safety of operation Diligent capable well trained operators and maintenance pe...

Page 7: ...ation for efficiency and reduced heat loss Interior The interior dimensions are 10 25 4cm High 14 36 8cm deep and 33 45 83 8cm 114 3cm Wide The melter comes standard with one rack which can be placed...

Page 8: ...the carrier s agent Concealed loss or damage means loss or damage which does not become apparent until the merchandise has been unpacked If concealed loss or damage is discovered upon unpacking make a...

Page 9: ...e legs so that burners are level Leg adjustment is made by turning the adjustable foot at the bottom of each leg Ensure that the leg does not turn while adjusting the foot WALL HUNG INSTALLATIONS The...

Page 10: ...off valve must be installed to the appliance and located in an accessible area In the event of a significant drop in gas pressure turn the shut off valve off and contact your gas supplier This applian...

Page 11: ...at the pilot burner as air must first be purged from the gas line The pilot burner will remain lit even if the Cheese Melter is switched to Off Once the pilot burner is lit allow one minute for pilot...

Page 12: ...e used for quick browning and toasting with the heat decreasing at each lower position In order to change positions simply slide the rack in and out of the slots provided Make sure that the end of the...

Page 13: ...ssible use Constant during peak periods DON TS Do not use the melter as a cooking or baking device it is best suited for finishing dishes immediately prior to serving Do not use the unit to heat or th...

Page 14: ...t tint may be removed using a Carbon Release oven cleaner The oven interior should be cleaned using a mild soap and a non metal scouring pad DO NOT use caustic cleaners Always apply these cleaners whe...

Page 15: ...ise to lengthen the pilot flame The pilot must light the main burner within 5 seconds of gas being available at the burner tiles listen for the solenoid valve to open The pilot must light the main bur...

Page 16: ...ilot valve Burner will not light Auto Constant switch in incorrect position Defective regulator Plugged main orifice Incorrect water column Defective solenoid valve Low pilot No gas to unit Defective...

Page 17: ...ch Check switch for normal operation Defective Power Cord Check Power cord for continuity Defective Regulator Check unit for proper Water Column Plugged Orifice Clean orifice Faulty Solenoid Valve Che...

Page 18: ...ifold Gas Melter 3ft 4ft 5ft Units 2K 80100 10 Manifold Gas Melter 4ft 5ft Units 2K 80100 11 Pilot Burner Assembly 2J 80201 20 Orifice Pilot Burner 010 DRL LP 2A 80401 09 Orifice Pilot Burner 021 DRL...

Page 19: ......

Page 20: ...STAR INTERNATIONAL HOLDINGS INC COMPANY Star Holman Lang Wells Bloomfield Toastmaster 10 Sunnen Drive St Louis MO 63143 U S A 314 678 6303 www star mfg com...

Reviews: