I N S T A L L A T I O N
Version: 121212-001 E
Fig. Ventilation through facade
Fig. Ventilation via ventilation stack
Ventilation
• Make sure that the compressor always has a sufficient amount of fresh air available for cooling.
• To prevent serious damage, ensure that the cooling air flow can flow freely.
• The necessary cooling air flow can be calculated by using the following formula:
300 x drive power [kW] = required cooling air flow [m³/h]
Example 11kW motor: 300 x 11kW = 3300 m³/h = required cooling air flow.
• The fan capacity for fresh air and warm air must meet at least the required cooling air flow.
The fans must have the same capacity.
Summary of Contents for LW 230 ES
Page 12: ...A S A F E T Y P R E C A U T I O N S ...
Page 19: ...A I N S TA L L AT I O N ...
Page 26: ...A O P E R AT I O N ...
Page 34: ...A R E M E D Y I N G FA U LT S ...
Page 39: ...A M A I N T E N A N C E A N D S E R V I C E ...
Page 68: ...A M A I N T E N A N C E R E C O R D S ...
Page 76: ...B Operating Instructions ECC Electronic compressor control www uebler net Version 11 12 E ...
Page 96: ...C ERSATZTEILLISTEN SPARE PARTS LISTS DETAILANSICHTEN DETAILED VIEWS ...
Page 158: ...D O P T I O N S ...
Page 160: ...D A U T O S T A R T F U N C T I O N D 2 LW 230 280 320 ES ...
Page 165: ...D O I L P R E S S U R E G A U G E D 7 LW 230 280 320 ES ...
Page 168: ...D O I L P R E S S U R E M O N I T O R I N G D 10 LW 230 280 320 ES ...
Page 172: ...D O I L T E M P E R A T U R E M O N I T O R I N G D 14 LW 230 280 320 ES ...
Page 175: ...D I N T E R S TA G E P R E S S U R E G A U G E D 17 LW 230 280 320 ES ...
Page 179: ...D C Y L I N D E R H E A D T E M P E R AT U R E M O N I T O R I N G D 21 LW 230 280 320 ES ...
Page 186: ...D A I R C O O L E R C O N N E C T I O N K I T D 28 LW 230 280 320 ES ...
Page 189: ...D C O N D E N S A T E TA N K 6 0 LT R D 31 LW 230 280 320 ES ...