Start-up
Replace the housing cover and press it in gently until you hear all the tabs latch. Open the shut-
off valves. Check the heating system for tightness and vent it carefully.
No more than 100 s later, message F0 will disappear. After that, check that the displays for
flowrate and temperaures are plausible. Vent the system until the flowrate display is stable.
Adjust the system with the flowrate display (updated in the flowrate timebase).
Seal the sensors. Attach user seals to the electronic unit and the sensors.
Read and note down the meter readings for quantity of heat, volume, operating time, and
missing time.
We recommend resetting the maxima and the missing time (see Parameter setting).
In case of
incorrect installation
, the relevant error message will be displayed.
Note: During a system stoppage, such messages may appear although mounting was correct.
Start-up lock
see
Display lock
The following
safety notices
have been included in the instructions:
Text
CI
I / SI
OI
)
Do not pick up by the electronic unit
x
x
no
)
Be careful of sharp edges (thread, flange, measuring tube)
x
x
no
)
Installation and removal must be performed by qualified personnel
only
x x no
)
Mounting and unmounting are only permitted when the system is not
under pressure
x x no
)
After installation, a tightness test must be conducted with cold
pressure
x x no
)
Only ever use under service conditions, otherwise dangers can arise
and the warranty may be voided
x x no
)
Breaking the calibration seal voids the warranty
x
x
no
)
The 110 V / 230 V versions must only be connected by an electrician
werden
x x no
)
The lithium batteries must be properly returned
x
x
no
)
Lightning protection cannot be ensured; this must be provided by the
building wiring
x x no
)
Only one compartment for the power supply must be equipped – do
not remove the red locking hatch
x x no
Tariff control by means of threshold values
(tariffs “T2”, “T3”, “T4”, “T5”, and “T6”)
The threshold values can be derived from the
flowrate
, the
heat power
, the
return temperature
,
the
flow temperature
or
temperature difference
. Up to 3 tariff thresholds are possible; the
selected measured value aplies to all threshold values. Each tariff threshold is assigned its own
tariff register.
In the tariff registers, it is possible to acquire either the quantity of heat or the volume.
The total quantity of heat and the total volume are summated independently of the tariff
thresholds.
Heat quantity
Volume
TR1
TR2
TR3
Threshold 1
Threshold 2
Threshold 3
Measured quantities for threshold values:
Q / P / TV / TR / TDiff
Accumulated measured value:
W or V
W
V
Summation is performed, if:
Threshold 1 < Meas. value < threshold 2
Threshold 2 < Meas. value < threshold 3
Threshold 3 < Meas. value
Tariff registers:
Standard registers:
Tariff situations "T2", "T3", "T4", "T5", "T6"
T