Error messages 

The heat meter constantly performs self-diagnostics 
and can display various error messages. 

Error  

Error / action to be taken: 

 

code:

 

F0 

No flow; 
Air in measuring unit / pipe, vent pipe 

F1 

Interruption of flow sensor  

F2 

Interruption of return sensor 

F3 

Electronic for temperature evaluation defective 

F4 

Battery empty; replace! 

F5 

Short-circuit flow sensor 

F6 

Short-circuit return sensor 

F7 

Fault in the internal memory 

F8 

F1, F2, F3, F5 or F6 pending for longer than 8 hours. 
No more measurements are performed. 

F9 

Error in the electronics 

Message F8 has to be reset in parameter setting 
mode (manually, PappaWin). All other error 
messages are cleared automatically once the error 
has been corrected. 

Functional details 

If the response thresholds are exceeded and the 
flowrate and temperature difference are positive, the 

quantity of thermal energy 

and the 

volume 

are 

summated. In the 

segment test, 

all segments of the 

display are switched on for test purposes. 

On the 

yearly set day, 

the meter readings for 

quantity of heat and volume, the values for the 
service life maxima and the flowrate and missing 
times are placed in the 

previous year memory

.  

The 

flowrate, heat power, 

and 

temperature 

difference

 are acquired with the correct sign. If the 

response threshold is not reached, the value is 
preceded by a 

u

. The current 

temperatures 

are 

shown together on one line of the display as 
integers in 

°C

To calculate the maximum, the heat power and 
flowrate are averaged over a 

measuring period 

of, 

for example, 60 min. The 

maximum values

 from the 

average calculation are preceded by 

Ma 

on the LC 

display. 

The 8-digit 

property number

 (also the secondary 

address in M-bus operation), can be set in 
parameter setting mode. The 

unit number 

is 

assigned by the manufacturer. 
The 

operating time 

is counted from the first time 

the power supply is connected. 

Missing times 

are 

summated, if an error is pending that prevents the 
heat meter from measuring. The 

date

 is 

incremented daily. 
The type of installed 

modules

 is displayed. If an M-

but module is installed, the primary and secondary 
address will be displayed on the following lines. 

The number for the 

firmware version

 is assigned 

by the manufacturer. 

 

Notes 

 Regulations on the use of heat meters must be 

observed, see EN 1434, Part 6! 

  

In particular, cavitation in the system must be 
avoided. 

 Heat meters up to DN25 may only be installed 

with directly immersed sensors according to 
German calibration law! 

 Install the unit in such a way that no water can 

enter the electronic unit during operation. 

  All information given on the data sheet of the heat 

meter must be observed.  

 User seals may only be removed by authorized 

persons for service purposes and must be 
replaced afterwards.  

 No later than 30 seconds after installation, the 

heat meter detects the plugged modules 
automatically and is ready for communication or 
pulse output.  

  The type of modules plugged can be displayed in 

the service loop depending on how the display is 
parameterized. 

 For fast pulses, the parameters must be set 

accordingly with the PappaWin software. 

 Up-to-date versions of all instructions can be 

found in the Internet at 

www.landisgyr.com

 

 

 

 

Gyr GmbH 

Humboldtstr. 64 

D-90459 Nuremberg 

Germany 

Summary of Contents for Heat Meter Ultrasonic UH50

Page 1: ... cavitation must be avoided in the entire measuring range i e at least 1 bar at qp and approx 3 bar at qs applies to approx 80 C The heat meter left the factory in perfect safe condition Calibration maintenance component replacement and repairs must only be performed by trained personnel who are familiar with the hazards involved The manufacturer will provide further technical support on request H...

Page 2: ...300 56 200 160 18 8 138 24 UH50x 82 60 16 100 360 68 235 180 18 8 158 24 UH50x 83 60 25 100 360 68 235 190 22 8 158 24 Examples of installation Ball valve Example of mounting with a ball valve recommended up to DN25 Welded sleeve with pocket Example of mounting with pockets recommended for DN25 Hint for mounting adapter set sensor direct immersed For heat meters with temperature sensor 5 2x45 mm a...

Page 3: ...n again A heat meter with a removable control cable may be separated during the installation When installation is done be sure that only paired parts volume part calculator are connected together The control cable must not be extended Power supply The heat meter can be powered either with a battery or via power supply modules The 110 V 230 V power supply modules are encapsulated and comply with sa...

Page 4: ...r quantity of heat volume unit status tariff register 1 tariff register 2 isolated bounce free CL module passive 20 mA current loop per EN 62056 21 2002 M bus module per EN 1434 3 fixed and extended variable protocol also for coupling with a suitagle heating controller Analog module Radio module Multi module external These modules are have no effect on consumption metering and can therefore also b...

Page 5: ...sible combinations Factory installed sensors Do not disconnect shorten or extend the cables of factory installed sensors Sensors installed by the customer In the case of sensors provided by the customer max cable length 5 m an extension is impermissible the 2nd and 3rd sleeve from the left must be cut to ensure the correct cable cross sections Unlatch the housing cover by pressing in the side tabs...

Page 6: ...tton 1 applies the value set in the blinking digit The next digit to the right of this then blinks can be set again with the LCD button 2 and can be applied with LCD button 1 As the final acknowledgment of a display line a star symbol is briefly displayed If incorrect entries are made parameter setting be performed again Completing parameter setting Parameter setting mode is exited by pressing LCD...

Page 7: ...ls with date stamp Max heat power on the set day at 2s intervals with date stamp Max temperatures on the set day at 2s intervals with date stamp for flow and return maximum Missing time count on the set day After the last display the previously selected set day is displayed again Pressing LCD button 1 selects the next set day Note If you want to drop out and go directly to the next loop choose a m...

Page 8: ...veraged over a measuring period of for example 60 min The maximum values from the average calculation are preceded by Ma on the LC display The 8 digit property number also the secondary address in M bus operation can be set in parameter setting mode The unit number is assigned by the manufacturer The operating time is counted from the first time the power supply is connected Missing times are summ...

Reviews: