Available Meter Forms
The
FOCUS
is available in the following meter forms:
4.1.1.
S-Base
•
Transformer rated: Class 10 & 20: 3S, 4S
•
Self-contained: class 100: 1S
•
Self-contained: class 200: 2S, 12S and 25S (Network)
•
Self-contained: class 320: 2SE
4.1.2.
K-Base
•
Self-contained: class 480: 2K
Meter Form Schematic Diagrams
Self-contained meter forms
Figure 11 – Form 1S
Table 1 - Form 1S Specification
Form
Class
Test Amps
Volts
Wire
Kh
1S 100 15 120 2 1.8