20/96
Device description
© Gyr
D000062026 en a
– E650 Series 4 – ZMD400AT/CT, ZFD400AT/CT – User Manual
U1
U2
U3
1 : T
U1-U2
2 : T
U1-U3
3 : T (fn)
1
2
3
Time measurement
for rotating field,
frequency, phase angle
U1-U1
Figure 8. Time measurement
The phase angle between voltage and current is determined by the times
between zero passage of the phase voltage U1 and those of the phase
currents I1, I2 and I3.
For further processing of the individual signal the signal processor
generates mean values over one second, which the following
microprocessor scans at intervals of one second.
2.6.3
Measured quantities
Measured quantity
ZMD400
ZFD400
Active energy in quadrant I
A (QI)
Sum / Phases
Sum
Active energy in quadrant II
A (QII)
Sum / Phases
Sum
Active energy in quadrant III
A (QIII)
Sum / Phases
Sum
Active energy in quadrant IV
A (QIV)
Sum / Phases
Sum
Active energy import
+A (QI+QIV)
Sum / Phases
Sum
Active energy export
–A (QII+QIII) Sum / Phases
Sum
Active energy, absolute value
+A
+
-A
Sum / Phases
Sum
Active energy, absolute value
+A
-
-A
Sum / Phases
Sum
Active energy import summation
Σ +A
Sum
Sum
Active energy export summation
Σ -A
Sum
Sum
Active energy by single quantity
Σ
ALx
Sum
Sum
Reactive energy in quadrant I
R (QI)
Sum / Phases
Sum
Reactive energy in quadrant II
R (QII)
Sum / Phases
Sum
Reactive energy in quadrant III
R (QIII)
Sum / Phases
Sum
Reactive energy in quadrant IV
R (QIV)
Sum / Phases
Sum
Reactive energy import
+R (QI+QII)
Sum / Phases
Sum
Reactive energy export
–R (QIII+QIV) Sum / Phases
Sum
Reactive energy import
+R (QI+QIV) Sum / Phases
Sum
Reactive energy export
–R (QII+QIII) Sum / Phases
Sum
Reactive energy, combined
R (QI+QIII)
Sum / Phases
Sum
Reactive energy, combined
R (QII+QIV)
Sum / Phases
Sum
Reactive energy, absolute value
+R
+
-R
Sum / Phases
Sum
Reactive energy, absolute value
+R
-
-R
Sum / Phases
Sum
Reactive energy import summation
Σ +R
Sum
Sum
Reactive energy export summation
Σ -R
Sum
Sum
Mean value formation