Landis & Gyr Ultrasonic UH50 General Information Manual Download Page 8

UH50 Ultrasound Heatmeter 

 

Configuration Instructions 

UH 106-101c 

Page 8 / 13 

Radio module 

Radio module;
with internal or

external antenna

Pulse inputs:

Channel 1,
Channel 2 

 

With its integrated antenna, the radio module 
permits wireless read-out from a distance of up to 
100 meters. For special mounting situations, the 
radio module can be supplied as a version with an 
external antenna. 
The module is programmed via radio telegrams. 
With a button, the transmit parameters can be reset 
to default values. 
Two LEDs indicate the current operating state.  
The power supply of the module is drawn from the 
heat meter. If the heat meter is operated with a 
battery, a 6-year battery of type D (“for all 
applications”) is required. 
The module contains an additional two pulse 
counters to acquire external counting pulses. 
The following must be noted concerning the inputs 
for the pulse counters: 

 

  - Only connect isolated contacts (Reed contact, 
 

no open collector)   

  - No galvanic isolation of the electronics of the heat 
 meter 

 

 

 

- External power source or grounding not 

 

 permissible 

Display on LCD 

RM

 (radio module) 

Technical data radio 

Frequency 433 

MHz 

Range 

up to 100 meters 

 

(with integrated antenna) 

Read-out frequency  max. 1 read-out per day 

 

(average) 

Technical data pulse counters 

Pulse counters: 

2 inputs for external pulses 

Counter range: 

0..99,999,999 

Pulse significance: 

0.001...999.99 

Counter identifier: 

8-digit 

Min. pulse length: 

50 ms 

Max. pulse rate: 

5 pulse/s when using both   
channels 

Max. pulse rate: 

10 pulse/s when using only   
one channel 

The radio module reads the data either when data is 
requested or only once per day. 
The heat meter must be functioning in normal mode. 
The data are packed and output in various telegram 
types. 

Data content  

All telegrams are preceded by the time stamp (date 
and time) and the property number.

 

Telegram type: 

Content: 

“Basic” 

Cumulated values and error status 

“Previous year” 

Cumulated previous year’s values 

and error status 

“Previous month” 

Cumulated previous month’s values 

and error status 

“Extended” 

Current instantaneous values, stored 

maximum values and error status 

“Pulse and service”

Data of the pulse counter 

Multi module 

The external multi module extends the heat meter by 
another three module slots for 2WR5 modules. That 
enables operation with a UH50 module and three 
2WR5 modules. 

Block diagram multi module

Module #2

e.g. M-bus

Module

*)

Module #1

z.B. Funkmodul

*)

Module #3

e.g. analog

module

*)

Multi

module

Pulse output

Button

Coding switch

LEDs

M-bus

10V / 20 mA

M-bus

Power supply

Radio

*) The module combination is only

an example

Pulse energy
Pulse volume
Pulse operating status
Pulse tariff 1

Pulse  input #1
Pulse input #2

Adapter

plate

in meter

 
Display on LCD 

MM 

(multi module ) 

The following modules of type 2WR5 can be used 
without restriction: 

-

 

M-bus module 

-

 

Analog module 

-

 

Radio module 

If several M-bus modules are used, one module 
functions as the master. The addresses of the M-
bus modules can be changed independently via the 
M-bus system. If the master address is changed it is 
written back to the heat meter. 
The bus address of the master can also be changed 
via the heat meter. 
The multi module has one pulse output each as 
standard for energy, volume, operating status and 
tariff register 1. 
The multi module is configured using the 3 button 
and the 2 coding switch. 
The operating state is displayed on LEDs, further 
LEDs indicate the status of the output pulses. 
For further details and a separate description, see 
“WZX-MM Multimodule Installation and Service 
Instructions”. 

Summary of Contents for Ultrasonic UH50

Page 1: ...temperature 20 to 60 C Max height 2000 m above MSL Ambient temperature 5 to 55 C Ambient humidity 93 rel Housing degree of prot IP 54 per EN 60529 Safety class Line 110 230 V AC II per EN 61558 Line 24 V ACDC III per EN 61558 Response threshold f T0 2 K Temperat difference T 3 K to 120 K Temperat meas range 2 180 C Sensors Type Pt500 or Pt100 per EN 60751 Temperature range 0 150 C 45 mm overall le...

Page 2: ...r outlet sections are necessary However if the heat meter is installed in the shared return of two heating systems e g heating and hot water the mounting location must be a sufficient distance from the T element that forms the junction min 10 DN to allow the different water temperatures to mix well The sensor can be mounted in ball valves or in pockets The sensors must be inserted at least up to t...

Page 3: ...d of the loop Accumulated quantity of heat with tariff status Tariff register 1 optional Accumulated volume Segment test Error message with error code number LCD button 1 is used to switch the display from the user loop to the selection of service loops LOOP 1 n Service loop selection Service loop 1 Service loop 2 LOOP n Service loop n LCD button 1 advances the display to the next loop After the l...

Page 4: ...re difference flow temperature and return temperature with their date stamps on a yearly set day Monthly values The electronic unit stores the meter readings for quantity of heat volume the tariff register missing time and flowrate measuring time as well as the monthly maxima for flowrate power temperature difference flow temperature and return temperature with their date stamp for 18 months on th...

Page 5: ... end ferrules 0 25 1 5 mm conductor sizes 26 14 AWG Multiple conductor connection 2 conductors of same cross section rigid or flexible 0 2 0 75 mm flexible with end ferrules without plastic sleeve 0 25 0 34 mm flexible with TWIN ferrules with plastic sleeve 0 5 0 75 mm Recommended screwdriver 0 6 x 3 5 mm Tightening torque 0 4 Nm Permissible combinations of modules Slot for module 2 is equipped wi...

Page 6: ...conducting Pulses for operating states Ready pulsed conducting i e 100 200 µs pulse duration 500 ms period Fault constantly non conducting Fast pulses Note In battery operation a D cell is required For applications such actuating controllers or as flowrate transmitters higher pulse rates are required The parameters required for this pulse significance pulse duration can be configured with the Papp...

Page 7: ...and maximum power measuring period with maxima for power flowrate and temperatures actual values for power flowrate and temperatures F0 pre warning setting and resetting a user lock setting the date and time and the primary and secondary address Special version with minimum update rate of 30 s can be supplied WZU MB 30 but it has a shorter battery life Data scope for fast readout Update after a mi...

Page 8: ...l mode The data are packed and output in various telegram types Data content All telegrams are preceded by the time stamp date and time and the property number Telegram type Content Basic Cumulated values and error status Previous year Cumulated previous year s values and error status Previous month Cumulated previous month s values and error status Extended Current instantaneous values stored max...

Page 9: ...ated or all tariffs can be deactivated Surcharge quantity tariff by means of return temperature tariff T12 The quantity of heat is summated depending on the return temperature in tariff registers 1 or 2 The summated quantity of heat is calculated from the difference of the return temperature from the defined return temperature threshold instead of from the temperature difference Above return thres...

Page 10: ...thly set day parameterized 21 Master reset performed 22 All times deleted 23 Missing time deleted 24 Event occurs Maxima deleted Read out is performed via the optical interface with the PappaWin software Data logger optional The data logger permits the archiving of data that the user can select from a predefined set of values The data logger contains four archives whose 8 channels can be assigned ...

Page 11: ... length 190mm nominal pressure PN16 connection G 1 B 23 Nominal flowrate 1 5 m h length 190mm nominal pressure PN25 connection flanged DN 20 24 Nominal flowrate 1 5 m h length 190mm nominal pressure PN25 connection G 1 B 25 Nominal flowrate 2 5 m h length 130mm nominal pressure PN16 connection G 1 B 36 Nominal flowrate 2 5 m h length 130mm nominal pressure PN25 connection G 1 B 37 Nominal flowrate...

Page 12: ... mounted in the tube F Sensor Pt500 removable mounting in the tube as an option G Sensor Pt500 removable mounted in the tube within a pocket H Sensor Pt100 not removable not mounted in the tube N Sensor Pt100 not removable mounted in the tube P Sensor Pt100 not removable mounting in the tube as an option R Sensor Pt100 not removable mounted in the tube within a pocket S Hardware dependent features...

Page 13: ...supply 24V AC DC with plug WZU ACDC24 00 Communication modules Code Analog module WZU AM CL Module WZU CL M bus module WZU MB M bus module with 30s minimum reading cycle WZU MB 30 M bus module with guaranteed data set WZU MB GR Pulse module WZU P2 Pulse module with OptoMOS WZU P2L Radio module WZU RM Radio module with external antenna WZU RM EXT Notes Regulations on the use of heat meters must be ...