The meter must not be exposed tensions or forces caused 
by by pipes or fittings. If this cannot be permanently guar-
anteed, it is necessary to improve the point of installation or 
fix the lines in position, by means of suitable connecting 
brackets for example. 

 

Fit the temperature sensors in the same circuit as the me-
ter. Observe the admixtures. 

 

Seal the temperature sensor and the fittings to protect 
against manipulation. 

 

If you install the meter for cooling metering, follow the ap-
propriate notes. 

Recommendation:

  If  you  are  installing  several  meters,  the 

same installation conditions must be consistent for all meters. 

Installation notes 

 

Note:

  When  installing  the  meter  the  locally  applicable 

installation regulations for meters must be observed. 

Inlet  or  outlet  sections  are  not  necessary.  If  you  install  the 
meter in the common return of two circuits, determine a place 
of installation with a minimum distance of 10 × DN from the T-
piece.  This  distance  ensures  a  good  thorough  mixing  of  the 
different  water  temperatures.  You  can  install  the  temperature 
sensors in T-pieces, ball valves, directly immersed or in pock-
ets  depending  on  the  version.  The  temperature  sensor  ends 
must reach to at least the middle of the pipe cross section. 

 

Note:

  Protect  the  meter  against  damage  through  im-

pacts or vibrations at the place of installation. 

 

On activation, open the slide valves slowly. 

The meter is made of a robust and very stable material. 

 

Only use open ended spanners to fit the meter. Only insert 
the open ended spanner on the holding surfaces provided. 

 

The maximum range of the tightening torque from 15 Nm 
for ¾" meter thread or 25 for 1" meter thread must be ad-
hered to during installation. For aligned pipe joints an angle 
of rotation of the cupling nut from 120 … 180° (¾") or 
90 … 120° (1") from contact of the seal with cupling nut is 
sufficient. 

Recommendation:

  Do  not  install  the  meter  on  the  pressure 

side  of  a  pump.  Maintain  a  minimum  distance  of  10  x  DN  on 
the pressure side. 

 

Note:

  During  installation  it  must  be  ensured  that  no 

water can enter the electronic unit during operation. 

Examples of installation (directly immersed sensor) 

You can install the meter in any position e.g. vertically or hori-
zontally. In order to avoid accumulation of air and disruption in 
operation, fit the meter in a vertical installation position and not 
in the uppermost area of a pipeline. 

 

 

*

 This position is not permitted for 

cold meters and in cases where 
moisture can enter the electronic 

unit due to condensation (e.g. 
during an interruption in the 

summer). 

Fig.1 

 

Fig. 2 

 

Fig. 3: Installation for circulation with admixing; placement of temperature sensors  

 

Fig. 4: Installation for circulation with throttling configuration for example (flow sensor 
in flow direction before control valve / differential pressure regulating valve) 

Installation notes for sensor adapter set 

A  mounting  set  is  included  for  meters  with  5.2 × 45 mm  tem-
perature  sensor. With  this  you  can  fit  the  temperature  sensor 
directly immersed into an insert or a ball valve for example. 

1. 

Install with O-ring at the point of installation with the fit-up 
aid/pen provided.  

2. 

Place both halves of the plastic bolting round the 3 notches 
of the temperature sensor. 

3. 

Press the bolting together and screw the bolting hand tight 
into the point of installation until it comes to a stop (tighten-
ing torque 3 ... 5 Nm). 

 

Fig. 5: Mounting adapter set 

3.1 

Installation for cooling metering 

Fit  the  electronic  unit  separate  to  the  volume  measurement 
unit, e.g. on the wall for water temperatures below 10° C. Make 
a  loop  downwards  in  order  to  prevent  condensation  running 
along  the  connected  lines  into  the  electronic  unit.  Install  the 
temperature sensors into the pipe from below. 

 

Note:

 Wall adapter plates are available as an accesso-

ry. 

3.2 

Electronic unit 

The  ambient  temperature  of  the  electronic  unit  must  not  ex-
ceed 55 °C. Avoid direct sunlight. 

Summary of Contents for ULTRAHEAT T230

Page 1: ...systems The meter is not suitable for drinking water Adhere to the AGFW requirements regarding circulat ing water FW510 Only personnel trained in the installation and opera tion of meters in heating and cooling systems may install and remove the meter Only install or remove the meter when the pipes are pressure less After installing the meter check the leak tightness of the system Guarantee and ca...

Page 2: ...the seal with cupling nut is sufficient Recommendation Do not install the meter on the pressure side of a pump Maintain a minimum distance of 10 x DN on the pressure side Note During installation it must be ensured that no water can enter the electronic unit during operation Examples of installation directly immersed sensor You can install the meter in any position e g vertically or hori zontally ...

Page 3: ...git LCD displaying various values Fig 6 LCD Number Description 1 Identification previous year value 2 Previous year value 3 Maxima 4 Previous month value 5 Identification previous month value 6 Activity display at flow 7 Calibrated value Switching the display Proceed as follows to switch between the display values Press the button briefly for less than 2 sec to show the next line of the current lo...

Page 4: ...ation thresholds are exceeded and flow and temperature difference are positive the meter summates the energy and the volume If the operate margin is gone below a u is displayed at a leading point for the flow power and temperature display For a positive flow the activity display appears in the user loop in the LCD All segments of the display are switched on for control purpos es during the segment...

Page 5: ...5 mm Temperature range 0 95 C Volume measurement unit Protection class IP 65 according to EN 60529 Mounting place Hot side cold side Installation position Any Flow straightening None Measuring range 1 100 Temperature range 5 90 C National type approvals may be different Maximum overload qs 2 x qp permanent Nominal pressure PN16 1 6 MPa PS16 qp m h Overall length and connection 0 6 110 mm 3 4 1 5 1...

Page 6: ...Landis Gyr GmbH Subject to change without prior notice 13 06 2017 6 10 Declaration of conformity Landis Gyr GmbH Humboldtstrasse 64 90459 Nuremberg Germany ...

Reviews: