Input voltage
20 .. 72 V DC
Current consumption
< 60 mA typ.
Operating temperature
0 .. 50 °C
Storing temperature
-20 .. 70 °C
Admissible ambient humidity
0 .. 95 % rel. humidity, non-condensing
Admissible operating pressure
1 bar overpressure
(oil-free and solvent-free air, filtered by 5 µm)
Dimensions
(H x W x D)
160 x 150 x 90 mm
(without connectors)
Weight
approx. 1200 g
Measurement ranges / Output frequencies Tx-Bus
Integrated sensors
1.
Contact
dry contact
open
1024 Hz
closed
1792 Hz
Address on the Tx-bus
n (n = coded address)
2.
System voltage
115/230 V AC
voltage < 50 V AC
1024 Hz
voltage > 90 V AC
1792 Hz
Address on the Tx-bus
n + 1 (n = coded address)
3.
Compressor runtime
0 .. 10,000 s
(most recent cycle)
0 .. 10,000 s
1000 .. 2000 Hz
Resolution
10 s (1 Hz)
Address on the Tx-bus
n + 2 (n = coded address)
4.
Compressor operating hours
0 .. 10,000 h
0 .. 10,000 h
1000 .. 2000 Hz
Resolution
10 h (1 Hz)
Address on the Tx-bus
n + 3 (n = coded address)
5.
Relative humidity of output air
0 .. 100 % RH
0 .. 100 % RH
1000 .. 2000 Hz
Resolution
0.1 % RH (1 Hz)
Max. measuring error
± 3.5 % FS (Full scale)
Address on the Tx-bus
n + 4 (n = coded address)
6.
Temperature of output air
0 .. 50 °C
0 .. 50 °C
1000 .. 1500 Hz
Resolution
0.1 °C (1 Hz)
Max. measuring error
± 2 °C
Address on the Tx-bus
n + 5 (n = coded address)
Technical Data