7
6. Using a wrench, loosen lock nut on the regulator adjustment
screw of the high pressure CO
2
regulator connected to the
source, then using a screwdriver back out lock nut screw all
the way.
A. CO
2
Regulator
B. Screwdriver
C. Loosened Lock Nut
D. Regulator Adjustment Screw
A
B
C
D
7. Repeat Step 6 on the previous page for both low pressure
CO
2
regulators on the regulator manifold routed to the unit
and the syrup pumps.
DO NOT TURN ON CO
2
SUPPLY AT THIS TIME
!
WARNING
Dispenser Setup
1. Turn on water source.
2. Open the pressure relief valve located on the front of the
unit, by flipping up on the valve cap lever. Hold open until
water flows from the relief valve then close (flip down) the
relief valve.
3. Verify all Bag-In-Box contains syrup and check all
connections for leaks.
4. Place enough ice in the ice bin to fill approximately 1/2 of the
bin before plugging in the unit.
5. Connect unit power cord to grounded electical outlet.
A. Pressure
Relief Valve
B. Valve Lever
A
B
The dispenser must be properly electrically grounded
to avoid serious injury or fatal electrical shock. The
power cord has a three-prong grounded plug. If a
three-hole grounded electrical outlet is not available,
use an approved method to ground the unit. Follow all
local electrical codes when making connections. Each
dispenser must have a separate electrical circuit. Do
not use extension cords. Do not connect multiple
electrical devices on the same outlet.
!
WARNING
A. Regulator Adjustment Screw
B. Adjust to 110 PSI (0.758 MPA)
C. Wrench
A
B
C
6. Test the motor operation by pushing the ice chute lever until
agitator motor begins to turn.
7. Activate each valve to ensure a good flow of water is
achieved.
8. Ensure pump deck is turned OFF before turning on CO
2
.
9. Turn on CO
2
at the source then, using a screwdriver, adjust
the high pressure regulator at the source to 110 PSI (0.758
MPA) then tighten locknut with wrench.
10. Adjust both of the low pressure regulators on the regulator
manifold to 75 PSI (0.517 MPA) then tighten locknut with
wrench.
11. Activate each valve until gas-out.
12. Plug in the remote carbonator pump deck, if not already
done so, and turn the switch to the ON position.
13. Activate each valve until the carbonator pump comes on.
Release the button, allow carbonator to fill and stop. Repeat
this process until a steady flow of carbonated water is
achieved.
14. Activate each valve to purge air from the syrup lines.
The pump deck has a 3 minute timeout feature. If the
timeout occurs, turn the deck OFF then ON by flipping
the switch on the control box.
NOTE
To check for CO
2
leaks, close the valve on the CO
2
cylinder and observe if the pressure to the system
drops with the cylinder valve closed for five minutes.
Open the cylinder valve after check.
NOTE
Summary of Contents for Bevariety ACIB 22
Page 14: ...14 WIRING DIAGRAMS ACIB 22 30...