PAGE 25
Meter Assembly for 1.5” and 2” Valves
Note: Be sure the proper meter size is programmed in the software.
Standard meter cable used for spacing up to 3” between valve body and meter body, longer distance requires longer
cable # V3221.
Service or replace the turbine by:
1. Turn the bypass for the system on and relieve the pressure on the system before removing the meter.
2. Press downward on the remote meter assembly to relieve tension on the retaining clip V3632. Remove the clip and
take the meter assembly out of the housing.
3. Remove the bend from the two exposed tips of the retaining clip V3501 and remove clip.
4. Service or replace the V3118-03 Turbine Assembly and place it back on the turbine shaft.
5. Insert the V3501 Turbine Clip and re-bend the exposed ends of the clip. The V3118-03 turbine has a groove to line up
with the V3501 Turbine Clip.
6. Insert meter assembly back into the meter housing.
7. Re-install the meter retaining clip V3632 as shown below
8. Open the bypass for the system slowly to bring back into service and check to be sure you have no water leaks.
V3040
1.5” NPT Meter, 28” Cable
V3040-15
1.5” NPT Meter, 15’ Cable
V3094
2” NPT Meter, 28” Cable
V3094-15
2” NPT Meter, 15’ Cable
Drawing No.
Order No.
Description
Quantity
1
V3003-02
Commercial meter assembly, 28” Cable
1
V3221
Commercial meter assembly, 15’ Cable
2
V3118-03
Commercial meter turbine assembly
1
3
V3105
O-ring, -215
1
4
V3501
Turbine clip
1
5
V3632*
Meter Retaining Clip
1
6
V3754-01
2” Meter Housing NPT
1
7
V3401-04
1.5” Meter Housing NPT
1
Not
Shown
V3437
1.5” Flow Straightener
1
V3488
2” Flow Straightener
WHEN INSTALLING THE METER, MAKE SURE THE ARROW ON THE METER BODY IS GOING THE SAME DIRECTION AS THE WATER FLOW.
THIS WATER METER SHOULD NOT BE USED AS THE PRIMARY MONITORING DEVICE FOR CRITICAL OR HEALTH EFFECT APPLICATIONS.
OPERATING PRESSURES: 20 PSI MINIMUM / 125 PSI MAXIMUM • OPERATING TEMPERATURES: 40°F MINIMUM / 110°F MAXIMUM
*The meter can be installed in either horizontal or vertical applications.
A
Page 42
WS1.5", 2" and 2"QC Drawings and Service Manual
Meter Assembly for WS1.5 and WS2 Valves
Note: Be sure the paper meter size is programmed in the software.
Standard meter cable used for spacing up to 3” between valve body and meter body, longer distance requires longer cable #V3221.
Service or replace the turbine by:
1. Turn the bypass for the system on and relieve the pressure on the system before removing the meter.
2. Press downward on the remote meter assembly to relieve tension on the retaining clip V3632. Remove the clip and take the meter
assembly out of the housing.
3. Remove the bend from the two exposed tips of the retaining clip V3501 and remove clip.
4. Service or replace the V3118-03 WS15/2 Turbine Assembly and place it back on the turbine shaft.
5. Insert the V3501 WS15/2 Turbine Clip and re-bend the exposed ends of the clip. The V3118-03 turbine has a groove to line up
with the V3501 WS15/2 Turbine Clip.
6. Insert meter assembly back into the meter housing.
7. Re-install the meter retaining clip V3632 as shown below (or the U-shaped V3223 WS2 Meter Clip).
8. Open the bypass for the system slowly to bring back into service and check to be sure you have no water leaks.
The V3118-03 has a groove to line up with the V3501 WS1.5/2 Turbine Clip.
Installation of the WS2 Meter NPT Assembly can be accomplished with 2” NPT pipe. For WS2 Meter BSPT Assembly use 63mm pipe.
WHEN INSTALLING THE METER, MAKE SURE THE ARROW ON THE METER BODY IS GOING THE SAME DIRECTION AS THE WATER FLOW.
THIS WATER METER SHOULD NOT BE USED AS THE PRIMARY MONITORING DEVICE FOR CRITICAL OR HEALTH EFFECT APPLICATIONS.
OPERATING PRESSURES: 20 PSI MINIMUM / 125 PSI MAXIMUM • OPERATING TEMPERATURES: 40°F MINIMUM / 110°F MAXIMUM
*The meter can be installed in either horizontal or vertical applications.
V3040
1.5” NPT Meter, 28” Cable
V3040BSPT
1.5” BSPT Meter, 28” Cable
V3040-15
1.5” NPT Meter, 15’ Cable
V3040BSPT-15
1.5” BSPT Meter, 15’ Cable
V3094
2” NPT Meter, 28” Cable
V3094BSPT
2” BSPT Meter, 28” Cable
V3094-15
2” NPT Meter, 15’ Cable
V3094BSPT-15
2” BSPT Meter, 15’ Cable
Drawing No.
Order No.
Description
Quantity
1
V3003-02
Commercial meter assembly, 28” Cable
1
V3221
Commercial meter assembly, 15’ Cable
2
V3118-03
Commercial meter turbine assembly
1
3
V3105
O-ring, -215
1
4
V3501
Turbine clip
1
5
V3632 *
Meter Retaining Clip
1
6
V3754-01
WS2 Meter Housing NPT
1
V3754BSPT-01
WS2 Meter Housing BSPT
7
V3401-04
WS1.5 Meter Housing NPT
1
V3401BSPT-04
WS1.5 Meter Housing BSPT
Not
Shown
V3437
WS1.5 Flow Straightener
1
V3488
WS2 Flow Straightener
Typical meter retaining clip installation.
Ensure clip is fully engaged in groove
and tabs positioned in slot as shown.
B indicates BSPT
N indicates NPT
6
1
2
3
4
5
Bend clip
after install
Area of
detail
7
A
A
B indicates BSPT
N indicates NPT
Area of
detail
Bend clip
after install
7
3
2
4
5
1
6
Summary of Contents for LX15 Series
Page 34: ...PAGE 34 NOTES ...
Page 35: ...PAGE 35 ...