28
3
Product Description
3.5.7
Technical Data external power unit Ex-Zone I
Fig. 3-30 External power unit Ex-Zone I
Fig. 3-31 Dimensions external power unit for Ex-Zone I
Technical Data
Explosion protection
II 2 G Ex db IIB + H2 T6/T5 GbII 2 D Ex tb IIIC T80 °C ... T95 °C Db
Material
copper-free aluminium, stainless steel 1.4404/316
Certificates/Test certificates
Certificate holder Rose Systemtechnik
ITS 15 ATEX 18302X, IECEx ITS 15.0041X
Electrical safety
IP66 according to EN 60529
Impact resistance
7 Joule according to EN 60079-0
Temperature range
-20 ... +60 °C / -4 ... +140 °F