52
6
Maintenance
6.3
Perform Maintenance
Procedure:
CAUTION!
Residual heat on all parts of the system and the pilot burner.
Risk of contact burns.
Allow the system and pilot burner to cool down before removal.
1
Shut down the system and secure it from being switched on again.
2
Allow the pilot burner to cool down completely.
3
Shut off the gas and air supply.
4
Depressurise the gas and air supply systems and disconnect them.
5
Have the closures for the combustion chamber opening ready.
6
Disconnect the electrical connections and ensure that there is no voltage present.
7
Loosen the grub screws.
8
Pull the pilot burner out of the flange.
Remove the device
NOTICE
If the location conditions permit, it makes sense to remove the device together with the feed-
through flange.
Advantage: The position of the outer tube in the feed-through flange is maintained without any
changes.
Alternatively, the outer tube with feed-through flange and air enclosure can remain on the
combustion chamber so that only the electrodes need to be pulled out of the outer tube.
Requirement for this: The outer tube is short enough that the electrode rods can be removed
from the outer tube without twisting.
Fig. 6-2 Leave outer tube and feed-through flange on the combustion chamber
1
Mark the position in which the outer tube is
inserted in the feed-through flange.
2
Loosen the grub screws of the feed-through
flange.
3
Pull the pilot burner out of the feed-through flange.