58
10
Accessories
10.3.2
FH40-10 (for IR and UV, with Ball-and-socket-joint and Purge Air Connection)
Fig. 10-7 Dimensional drawing FH30-10 type 659S1500 with flame scanner F200K
1
Purging air
2
Insulating part
A Clamping screw tightened by
hand
Fig. 10-8 Drawing dimension FH40-10 Type 659S1600 with flame scanner F200K
Instructions for purge/sealing air
•
Free of dirt and oil
(may be with oil separators, particulate filters)
•
> 20 mbar above the current pressure prevailing
•
≥
5 m³/h/22.01 gpm for cooling
•
< 50 °C/+122 °F at the purge air inlet
1
Purging air
2
Insulation part
A Clamping screw tightened by
hand
B Ball-and-socket-joint, locked by
SW10
Fig. 10-9 View A