16
4
Technical Data
NOTICE
If the connection cable is subjected to particular stress caused by UV radiation, the connection
cable protective tubes provided for this purpose must be used.
Order no. 659N990/0/1/2 available in 3/5 and 10 m lengths
Climatical conditions
Operating class temperature
F200K
Sensor
IR-1
IR-2
UV1, UV-6
UV-2, UV-3
- 40 °C/-40 °F*/**
X
X
X
- 20 °C/-4 °F
X
X
X
+ 60 °C/+140 °F
X
X
X
+ 75 °C*/+167 °F*
X
X
* - in preparation for F200K…Ex… (See Ex approval)
** - not valid for FFDT 4s
Operating class temperature
LiYCY
moving
- 5 °C/+23 °F ...
+ 70 °C/+158 °F
Cable
fixed
- 20 °C/-4 °F ...
+ 80 °C/+176 °F
LiYCY A
moving
- 5 °C/23 °F ...
+ 70 °C/+158 °F
fixed
- 40 °C/-40 °F ...
+ 80°C/+176 °F
Silikon
moving
- 25 °C/-13 °F ...
+ 150°C/+302 °F
fixed
- 40 °C/-40 °F ...
+ 150°C/+302 °F
protected
- 60 °C/-76 °F ...
+ 150 °C/+302 °F
Relative humidity
0 ... 95% non-condensing
Vibration fatigue limit
according to GL2003-12/VI-7-2
4 g/0.14 oz
Protection type
IP67; in closed state
IP66 (only F200K Ex), in closed state
NEMA 4X
Mass
0.6 kg/1.322 lb (F200K, F200K Ex-II)
Storage conditions
(in original packing)
Storage location
enclosed premises
Air temperature
- 40 ... +75 °C/-40 ... +167 °F
Type IR-1 +65 °C/ +149 °F
Air humidity
0 ... 95 % not condensing
Transport conditions (in original packing)
Type of transport
enclosed holds
Air temperature
- 40 ... + 75 °C/-40 ... +167 °F