6
4
Technical Data
4
Technical Data
4.1
Characteristics
The compact flame scanner is available in 2 basic versions, as well as an ex-proof enclosure
type with several spectral varieties (IR / UV).
* Special versions with regard to the lower limit frequencies are available on request
NOTICE
Signals lying in the mains frequency range or its multiples are suppressed for 50 Hz mains
generally. For 60 Hz application, please indicate separately in your order form. The related
stop ranges are changed in factory.
LAMTEC offers a version without mains frequency suppression for special applications.
This design requires additional measures during installation.
Please contact LAMTEC Support for further information
The compact flame scanner is accordingly marked by a rating plate.
Design type
F200K1
F200K2
Sensitivity range
1 sensitivity range
6 levels
2 sensitivity range
increased sensitivity in
range II, can externally be
switched over, 6 levels
each
Frequency range
10 ...190 Hz*
*10/20/30 ... 190 Hz
can be adjusted on the
device