Commissioning
6.3.1
Programming Curves
Programming RC curves (AL2)
The curve screen shows the setpoint curves for the channels (ratio controller) per curve set.
Two different views are available:
•
setpoint graphic
•
curve table
To change a curve in the CMS, the CMS must first be switched into the START CONFIGU-
RATION mode.
NOTICE
This function is relevant for safety.
The function must be confirmed a second time within 8 seconds.
In CONFIGURATION mode, two device functions are available in the curve view window:
•
Save point
•
Delete curve set
NOTICE
Individual curve points can only be modified and cannot be deleted.
In CONFIGURATION mode, the spanner symbol is shown and the screen is also
displayed with a red border.
The firing rate or the setpoints for the channels can be adjusted using the arrow keys
or the appropriate buttons.
Fig. 6-2 Programming RC curves
Summary of Contents for CMS
Page 2: ......
Page 131: ...130 7 Operating Control and Displays 7 1 5 5 Deleting Curves Delete firing rate curve...
Page 148: ...147 7 Operating Control and Displays Channel configuration AL1 Fig 7 18 Channel configuration...
Page 157: ...156 7 Operating Control and Displays Fig 7 27 System CRCs menu...
Page 162: ...161 7 Operating Control and Displays Fig 7 32 IP setting menu...
Page 166: ...165 7 Operating Control and Displays Fig 7 35 Installation...
Page 167: ...166 7 Operating Control and Displays Fig 7 36 Installation...
Page 176: ...175 7 Operating Control and Displays Fig 7 49 Loading a protected dataset into the device...
Page 202: ...201 7 Operating Control and Displays Replacing a Module Fig 7 81 Module replacement menu...
Page 276: ...275 10 Maintenance 3 Restart CMS to complete the update...
Page 282: ...281 12 Appendix 12 5 EU Declaration of Conformity...
Page 283: ...282 12 Appendix...