For Your Safety
3.6.3
Checking Burner Sequencer Part
Check the following:
•
Correct setting of time parameters (especially safety and pre-ventilation periods).
•
Whether an ionisation flame sensor or a corresponding flame scanner is used since only
these are capable of running in continuous operation.
•
Functioning of flame sensor in case of flame blow-off during operation, parasitic light being
present during pre-ventilation period and missing flame formation at the end of the safety-
period.
•
Check the performance of all available and/or essential incomming signals, such as for:
–
Air pressure
–
Gas pressure - min/oil pressure - min
–
Safety interlock chain (e.g. STB)
•
Activated Leakage control function for gas valves if required for application purposes.
–
If necessary, ensure a correct leakage quantification.