28
3
System Description
3.4
Functional Description of the Modules
MCC
Burner module: This module is equipped with the burner control with flame monitoring system,
valve leakage test as well as the complete communication interfaces.
The following variants of the inputs and outputs are available:
AEC-TPS
Module for controlling and monitoring 2 three-point step servomotors with potentiometer for
position acknowledgement.
The module is available in the following voltage variants:
AEC-VS
Module for controlling and monitoring frequency inverters or actuators with 4 ... 20 mA input
and 4 ... 20 mA acknowledgement. For the control of frequency inverters, the speed is record-
ed with pulse, Namur or three wire sensors. In addition, the module provides a non-failsafe
output for activating the frequency inverter and a non-failsafe input for importing the frequency
inverter’s fault status signals
.
The module is available in the following voltage variants:
SDI
Module with 8 safe digital inputs.
The module is available in the following voltage variants:
SDO
Module with 8 safe digital inputs.
The module is available in the following voltage variants:
Inputs
24 VDC
Outputs
24 VDC
Type 668R0100 -05
Inputs
24 VDC
Outputs
120 VAC
Type 668R0100 -04
Inputs
24 VDC
Outputs
230 VAC
Type 668R0100 -03
Inputs
120 VAC
Outputs
120 VAC
Type 668R0100 -02
Inputs
230 VAC
Outputs
230 VAC
Type 668R0100 -01
120 VAC
Type 668R0200-120VAC
230 VAC
Type 668R0200-230VAC
24 VDC
Type 668R0230-24VDC
120 VAC
Type 668R0230-120VAC
230 VAC
Type 668R0230-230VAC
24 VDC
Type 668R0400-24VDC
120 VAC
Type 668R0400-120VAC
230 VAC
Type 668R0400-230VAC
24 VDC
Type 668R0500-24VDC
120 VAC
Type 668R0500-120VAC
230 VAC
Type 668R0500-230VAC
Summary of Contents for AEC-TPS
Page 2: ......
Page 131: ...130 7 Operating Control and Displays 7 1 5 5 Deleting Curves Delete firing rate curve...
Page 148: ...147 7 Operating Control and Displays Channel configuration AL1 Fig 7 18 Channel configuration...
Page 157: ...156 7 Operating Control and Displays Fig 7 27 System CRCs menu...
Page 162: ...161 7 Operating Control and Displays Fig 7 32 IP setting menu...
Page 166: ...165 7 Operating Control and Displays Fig 7 35 Installation...
Page 167: ...166 7 Operating Control and Displays Fig 7 36 Installation...
Page 176: ...175 7 Operating Control and Displays Fig 7 49 Loading a protected dataset into the device...
Page 202: ...201 7 Operating Control and Displays Replacing a Module Fig 7 81 Module replacement menu...
Page 276: ...275 10 Maintenance 3 Restart CMS to complete the update...
Page 282: ...281 12 Appendix 12 5 EU Declaration of Conformity...
Page 283: ...282 12 Appendix...