227
8
CO/O
2
Control
Setting the Correction Range and the Spread Factor
NOTICE
The spread factor can only be set or changed when the burner is switched off.
Access level 1 is required.
1. Open the correction window
2. Select the channel to be corrected. Enter the correction shift and the correction range into
the text boxes.
Deleting the O
2
and CO Optimisation Curve
NOTICE
To delete O
2
and CO optimisation curve access level 1 is required.
NOTICE
Recommendation:
Delete optimisation curves if:
– The optimisation curve of the O
2
trim is no longer valid (e.g. after a longer burner standstill).
– The burner starts to run into a air deficiency when the firing rate changes.
Summary of Contents for AEC-TPS
Page 2: ......
Page 131: ...130 7 Operating Control and Displays 7 1 5 5 Deleting Curves Delete firing rate curve...
Page 148: ...147 7 Operating Control and Displays Channel configuration AL1 Fig 7 18 Channel configuration...
Page 157: ...156 7 Operating Control and Displays Fig 7 27 System CRCs menu...
Page 162: ...161 7 Operating Control and Displays Fig 7 32 IP setting menu...
Page 166: ...165 7 Operating Control and Displays Fig 7 35 Installation...
Page 167: ...166 7 Operating Control and Displays Fig 7 36 Installation...
Page 176: ...175 7 Operating Control and Displays Fig 7 49 Loading a protected dataset into the device...
Page 202: ...201 7 Operating Control and Displays Replacing a Module Fig 7 81 Module replacement menu...
Page 276: ...275 10 Maintenance 3 Restart CMS to complete the update...
Page 282: ...281 12 Appendix 12 5 EU Declaration of Conformity...
Page 283: ...282 12 Appendix...