Lambrecht meteo WS6 Manual Download Page 9

Manual
Weather Sensor u[sonic]WS7 Modbus

(16480) u[sonic]WS7 Modbus

Manual

Example

: Retrieve wind speed (min. max. avr.) and erase the register content

01 04 75 34 00 01 6A 08 01 04 02

00 00

B9 30 01

04 75 33 00 01 DB C9 01 04 02

00 D6

38 AE 01 04

75 32 00 01 8A 09 01 04 02

00 14

B9 3F

LEN 

6

Transmission 

Query =>

Source 

Master

Dest 

Slave 1 

Function 

Read Input Register (4)

Func Desk 

Address=30004, Quantity of Register=1

Checksum 

OK:86A

LEN 

5

Transmission 

Response <=

Source 

Slave 1

Dest 

Master

Function 

Read Input Register (4)

Func Desk 

Byte count=2

Data

 

00 00

Checksum 

OK:30B9

LEN 

6

Transmission 

Query =>

Source 

Master

Dest 

Slave 1

Function 

Read Input Register (4)

Func Desk 

Address=30003, Quantity of Register=1

Checksum 

OK:C9DB

LEN 

5

Transmission 

Response <=

Source 

Slave 1

Dest 

Master

Function 

Read Input Register (4)

Func Desk 

Byte count=2

Data

 

00 D6

Checksum 

OK:AE38

LEN 

6

Transmission 

Query =>

Source 

Master

Dest 

Slave 1

Function 

Read Input Register (4)

Func Desk 

Address=30002, Quantity of Register=1

Checksum 

OK:98A

LEN 

5

Transmission 

Response <=

Source 

Slave 1

Dest 

Master

Function 

Read Input Register (4)

Func Desk 

Byte count=2

Data

 

00 14

Checksum 

OK:3FB9

6.7 

Descriptive sensor parameter registers (Holding Register)

Register

Parameter name 

Quantity of registers

Remark

Access type

40050 

Device identification number 

(15 characters)

8 (2 characters in each 

register)

The returned data are 

in form of a 16 byte null 

terminated string

Read only

40100

Serial number
(11 characters)

6 (2 characters in each 

register)

The returned data are 

in form of a 12 byte null 

terminated string

Read only

40150 

Firmware version 
(up to 25 characters)

13 (2 characters in each 

register)

The returned data are 

in form of a 26 byte null 

terminated string

Read only

Example

:

 Retrieve the device identification number

(The identification number shown in the example is sensor-dependent. It is only used here for demonstration purposes).

0D 03 9C 72 00 08 CA 8B 0D 03 10

30 30 2E 31 36

                

00.16480.000130



34 38 30 2E 30 30 31 31 33 30 00

E8 6B

LEN 

6

Transmission 

Query =>

Source 

Master

Dest 

Slave 13

Function 

Read Holding Register (3)

Func Desk 

Address=40050, Quantity of Register=8

Checksum 

OK:8BCA

LEN 

19

Transmission 

Response <=

Source 

Slave 13

Dest 

Master

Function 

Read Holding Register (3)

Func Desk 

Byte count=16

Data

 

30 30 2E 31 36 34 38 30 2E 30 30 31 31 33 30 00

Checksum 

OK:6BE8

9

Summary of Contents for meteo WS6

Page 1: ...n and display of the measured values using the MeteoWare CS evaluation software Easy space saving mounting on 50 mm standard pipe The Perfect Weather Sensor For industrial use as well as under extreme...

Page 2: ...the appropriate disposal of waste electronic equipment Content 1 Introduction 3 1 1 Warranty 3 2 Setting to work 3 2 1 Installation conditions 3 2 1 1 Generally 3 2 2 Tools and installation aids 4 2...

Page 3: ...ring elements This heating is particularly effective against ice and snow in all climatic zones The measuring principle allows very low starting values and high repeat accuracy The sensor rapidly can...

Page 4: ...he two grup screws Finally the earth screw has to be connected to the ship s ground Acid free contact grease is recommended to protect contact surfaces against corrosion Note Follow all safety instruc...

Page 5: ...t safety regulations for such works During the electrical installation and termination works the external circuit breaker must be switched off It is not permitted to open those housings by unauthorize...

Page 6: ...ilization and communication of it s contents prohibited unless definitely permitted Infringement is bound to compensation All rights reserved for patent or registered pattern Ma e ohne Toleranzangabe...

Page 7: ...r than a single byte that the most significant byte is sent first Example Big Endian Register size value 16 bits 0x1234 is transmitted in the sequence 0x12 0x34 To obtain the real measuring value divi...

Page 8: ...10 1 Read only 30003 Wind speed maximum m s 10 1 Read only 30004 Wind speed minimum m s 10 1 Read only 30202 Wind direction average 10 1 Read only 30203 Wind direction maximum 10 1 Read only 30204 Wi...

Page 9: ...n Read Input Register 4 Func Desk Byte count 2 Data 00 14 Checksum OK 3FB9 6 7 Descriptive sensor parameter registers Holding Register Register Parameter name Quantity of registers Remark Access type...

Page 10: ...2 00 01 61 88 0D 10 9C 41 00 01 7F 41 LEN 9 Transmission Query Source Master Dest Slave 13 Function Write Multiple Register 16 Func Desk Address 40001 Quantity 1 Byte count 2 Register values 00 01 Che...

Page 11: ...elter 0 1 r h at 10 40 C 3 Shelter inaccuracy 4 r h dependant on v 2 m s and solar radiation 7 Technical data 16480 Weather Sensor u sonic WS7 Modbus Id No 00 16480 001130 Range of application 40 70 C...