Lambrecht meteo WS6 Manual Download Page 8

Manual
Weather Sensor u[sonic]WS7 Modbus

(16480) u[sonic]WS7 Modbus

Manual

6.5 

Instantaneous values / realtime values (Input Register)

The following measured values are provided by LAMBRECHT meteo sensors.

Register address Parameter name

Unit

Divisor

Quantity of registers

Access type

30001

Wind speed

m/s

10

1

Read only

30201

Wind direction

°

10

1

Read only

30401

Air temperature

°C

10

1

Read only

30601

Relative humidity

%r.h.

10

1

Read only

30701

Dew point

°C

10

1

Read only

30801

Air pressure

hPa

10

1

Read only

31401

Global radiation

W/m²

10

1

Read only

Example:

 Retrieve wind speed

0D 04 75 31 00 01 7A C5 0D 04 02

00 1F

E8 F9

LEN 

6

Transmission 

Query =>

Source 

Master

Dest 

Slave 13

Function 

Read Input Register (4)

Func Desk 

Address=30001, Quantity of Register=1

Checksum 

OK:C57A

LEN 

5

Transmission 

Response <=

Source 

Slave 13

Dest 

Master

Function 

Read Input Register (4)

Func Desk 

Byte count=2

Data 

00 1F

Checksum 

OK:F9E8

6.6 

Period data - Average, maximum and minimum (Input Register)

Register

Parameter name 

Unit 

Divisor

Quantity of registers

Access type

30002 

Wind speed average

m/s 

10

1

Read only 

30003 

Wind speed maximum

m/s 

10

1

Read only 

30004 

Wind speed minimum

m/s 

10

1

Read only 

30202 

Wind direction average

° 

10

1

Read only 

30203 

Wind direction maximum

° 

10

1

Read only

30204 

Wind direction minimum

° 

10

1

Read only

30402 

Air temperature average

°C 

10

1

Read only

30403 

Air temperature maximum

°C 

10

1

Read only

30404 

Air temperature minimum

°C 

10

1

Read only

30602 

Relative humidity average

% r.h. 

10

1

Read only

30603 

Relative humidity maximum

% r.h. 

10

1

Read only

30604 

Relative humidity minimum

% r.h. 

10

1

Read only

30702 

Dew point average

°C 

10

1

Read only

30703 

Dew point maximum

°C 

10

1

Read only

30704 

Dew point minimum

°C 

10

1

Read only

30802 

Air pressure average

hPa 

10

1

Read only

30803 

Air pressure maximum

hPa 

10

1

Read only

30804 

Air pressure minimum

hPa 

10

1

Read only

31402 

Global radiation average

W/m² 

10

1

Read only

31403 

Global radiation maximum

W/m² 

10

1

Read only

31404 

Global radiation minimum

W/m² 

10

1

Read only

The data are valid for the period between the current request and the previous request. The maximum range of a period is 

1 hour. Recalling the average value of a minimum, maximum and average group will erase the appropriate registers. 
Retrieve the values of a group in the sequence minimum, maximum, average.
Use command: 0x03

8

Summary of Contents for meteo WS6

Page 1: ...n and display of the measured values using the MeteoWare CS evaluation software Easy space saving mounting on 50 mm standard pipe The Perfect Weather Sensor For industrial use as well as under extreme...

Page 2: ...the appropriate disposal of waste electronic equipment Content 1 Introduction 3 1 1 Warranty 3 2 Setting to work 3 2 1 Installation conditions 3 2 1 1 Generally 3 2 2 Tools and installation aids 4 2...

Page 3: ...ring elements This heating is particularly effective against ice and snow in all climatic zones The measuring principle allows very low starting values and high repeat accuracy The sensor rapidly can...

Page 4: ...he two grup screws Finally the earth screw has to be connected to the ship s ground Acid free contact grease is recommended to protect contact surfaces against corrosion Note Follow all safety instruc...

Page 5: ...t safety regulations for such works During the electrical installation and termination works the external circuit breaker must be switched off It is not permitted to open those housings by unauthorize...

Page 6: ...ilization and communication of it s contents prohibited unless definitely permitted Infringement is bound to compensation All rights reserved for patent or registered pattern Ma e ohne Toleranzangabe...

Page 7: ...r than a single byte that the most significant byte is sent first Example Big Endian Register size value 16 bits 0x1234 is transmitted in the sequence 0x12 0x34 To obtain the real measuring value divi...

Page 8: ...10 1 Read only 30003 Wind speed maximum m s 10 1 Read only 30004 Wind speed minimum m s 10 1 Read only 30202 Wind direction average 10 1 Read only 30203 Wind direction maximum 10 1 Read only 30204 Wi...

Page 9: ...n Read Input Register 4 Func Desk Byte count 2 Data 00 14 Checksum OK 3FB9 6 7 Descriptive sensor parameter registers Holding Register Register Parameter name Quantity of registers Remark Access type...

Page 10: ...2 00 01 61 88 0D 10 9C 41 00 01 7F 41 LEN 9 Transmission Query Source Master Dest Slave 13 Function Write Multiple Register 16 Func Desk Address 40001 Quantity 1 Byte count 2 Register values 00 01 Che...

Page 11: ...elter 0 1 r h at 10 40 C 3 Shelter inaccuracy 4 r h dependant on v 2 m s and solar radiation 7 Technical data 16480 Weather Sensor u sonic WS7 Modbus Id No 00 16480 001130 Range of application 40 70 C...

Reviews: