1.6 OVERALL DIMENSIONS

fig. 1 - 

MOD.

9

12

18

24

UM

W

720

805

890

mm

W1

70

69

65

mm

H

495

554

673

mm

D

270

330

342

mm

1.7 APPLICATION FIELD

We recommend to use of the unit under the conditions described below.

Operating mode Parameter

Inner side

Outer side

U.M

B.S

B.U

B.S

B.U

Cooling

Maximum inlet air temperature 

32

23

50

\

(°C)

Minimum inlet air temperature 

17

16

-15

\

(°C)

Heating

Maximum inlet air temperature 

30

\

24

20

(°C)

Minimum inlet air temperature 

0

\

-15

-13

(°C)

All

Supply Voltage 

230±10%

(V)

Supply Frequency 

50±2

(Hz)

Summary of Contents for RUBINO S 9

Page 1: ...EN R E F R I G E R A N T G A S R32 D L Y E C IT MANUALE INSTALLAZIONE E MANUTENZIONE EN USE AND MAINTENANCE MANUAL NL INSTALLATIE EN ONDERHOUDSHANDLEIDING Monosplit DC inverter in pompa di calore Mono...

Page 2: ...10 2 5 INSTALLAZIONE DELL UNIT ESTERNA 11 2 6 KIT SCARICO CONDENSA PER UNIT ESTERNA 12 2 7 TUBAZIONI DI COLLEGAMENTO 13 2 8 COLLEGAMENTI FRIGORIFERI 15 2 9 ISOLAMENTO TUBAZIONI 15 2 10 SERRAGGIO TUBAZ...

Page 3: ...ue che il nostro servizio d assistenza organizzato in collaborazione con i nostri concessionari sempre a disposizione per eventuali consigli e interventi diretti 1 3 PRESENTAZIONE DELLE UNIT I condizi...

Page 4: ...nto attuativo 626 2011 relativo alla Direttiva 2009 125 CE a Freddo A A A A a Caldo A A A A Consumo in stand by 0 5 0 5 0 5 0 5 W Portata aria unit interna Max med min 460 330 260 530 400 350 800 600...

Page 5: ...nit all interno delle condizioni descritte sotto Modalit di funzionamento Parametro Lato interno Lato esterno U M B S B U B S B U Raffreddamento Temperatura massima aria ingresso 32 23 50 C Temperatur...

Page 6: ...ituato nell unit esterna di tipo ROTATIVO con protezione contro i sovraccarichi termici ed elettrici E montato su supporti di gomma per eliminare i fenomeni dovuti a vibrazioni 3 GRUPPO VENTILANTE L u...

Page 7: ...di appoggiare qualsiasi oggetto sulla parte superiore delle unit Non inserire o far cadere oggetti attraverso le griglie di protezione dei ventilatori La superficie della batteria tagliente Non toccar...

Page 8: ...tra 25 C e 55 C N B Non disperdere gli imballi nell ambiente Una volta deciso il luogo d installazione vedi in seguito i paragrafi relativi per sballare le due unit procedere come segue Unit esterna 1...

Page 9: ...diametro maggiore 4 Tubazione lato liquido 5 Tubo scarico condensa 6 Sifone fig 4 Unit esterna posta in alto e unit interna in basso fig 5 In questo caso sulla tubazione d aspirazione 3 devono essere...

Page 10: ...e le perdite di carico aumentando di conseguenza il rendimento complessivo della macchina Rispettare i limiti riportati nelle seguenti Tabella Modello UM 9 12 18 24 Attacchi linea liquido 1 4 1 4 1 4...

Page 11: ...to in cemento di 20 30 cm cos da impedire la formazione di neve attorno alla macchina Le pompe di calore durante il periodo invernale producono della condensa che cade sul piano d appoggio formando de...

Page 12: ...dell unit esterna Il fissag gio avviene inserendo la parte sagomata del raccordo nel foro 2 Collegare al raccordo fig 10 un tubo di gomma sufficientemente resistente in modo che non si deformi determi...

Page 13: ...uperiori a quelle del refrigerante R32 necessario scegliere i materiali adeguati Nella tabella sottostante vengono riportati gli spessori dei tubi di rame consigliati in relazione ai diametri nominali...

Page 14: ...0 80 16 6 16 0 12 9 23 26 5 8 15 88 1 00 19 7 19 0 16 0 25 29 fig 17 N B Assicurarsi che l olio utilizzato per la lubrificazione della cartella sia del medesimo tipo o compatibile con l olio utilizzat...

Page 15: ...omanda inoltre di fare attenzione ai punti di collegamento se condo quanto descritto Usare del nastro isolante termico per fasciare i tubi dalla zona collegamento con i rubinetti dell unit esterna fin...

Page 16: ...po monometrico abbinato alla bombola di azoto N2 Pressurizzare il sistema ad una pressione massima di 30 bar con l azoto della bombola Verificare la tenuta delle giunzioni con sapone liquido Per evita...

Page 17: ...ndi l esecuzione del vuoto sulle tubazioni di collegamento e sull unit interna Per l esecuzione di tale fase si proceda come descritto Collegare il tubo di carica descritto in precedenza alla pompa de...

Page 18: ...i conduttori provenienti dalla sorgente di alimentazione direttamente ai morsetti di ingresso del disposi tivo di sezionamento dell alimentazione fare riferimento agli schemi elettrici a corredo macch...

Page 19: ...frigorifero 3 4 ACCENSIONE Una volta eseguiti i controlli preliminari per mettere in funzione la macchina necessario attivare l unit tramite il telecomando Premere il tasto d accensione e impostare la...

Page 20: ...DIFFERENCE OF REFRIGERANT PIPES 28 2 5 INSTALLING THE OUTDOOR UNIT 29 2 6 CONDENSATION DRAIN KIT FOR OUTDOOR UNIT 30 2 7 CONNECTION PIPES 31 2 8 COOLING CONNECTIONS 33 2 9 PIPE INSULATION 33 2 10 PIPE...

Page 21: ...ers is always at your disposal if advice or interventions are required 1 3 PRESENTATION OF THE UNIT Air conditioners split type air conditioners must be connected to an outdoor unit This model range c...

Page 22: ...09 125 CE Cooling A A A A Heating A A A A Stand by mode power consumption 0 5 0 5 0 5 0 5 W Air flow Max med min 460 330 260 530 400 350 800 600 500 1090 770 610 m3 h Sound pressure level Max med min...

Page 23: ...IELD We recommend to use of the unit under the conditions described below Operating mode Parameter Inner side Outer side U M B S B U B S B U Cooling Maximum inlet air temperature 32 23 50 C Minimum in...

Page 24: ...unit is the highly efficient and silent ROTARY type with protection against both thermal and electrical overloads It is fitted on rubber supports to eliminate faults due to vibrations 3 VENTILATING UN...

Page 25: ...ng with any work on the machine Do not place anything on the top part of the units Do not push items through the protective fan grilles or allow objects to drop through The bank surface is sharp Do no...

Page 26: ...ng away exteriors to avoid envi ronmental pollution Once the place in which the unit is to be installed has been cho sen see the relative sections proceed as follows to unpack the two units Outdoor un...

Page 27: ...4 Piping on liquid side 5 Condensation drain pipe 6 Trap fig 4 Outdoor unit positioned at the top and indoor unit at the bot tom fig 5 In this case traps 6 must be installed on the suction piping 3 e...

Page 28: ...ngths L will limit the load losses consequently increasing the overall efficiency of the machine Comply with the limits given in the following tables Model UM 9 12 18 24 Liquid connection 1 4 1 4 1 4...

Page 29: ...condensation that drips on the supporting surface forming annoying and or unple asant puddles To avoid this use the condensation drain fitting kit as indicated in the relative section 50cm 50cm 30cm 2...

Page 30: ...the base of the outdoor unit The fastening is carried out by inserting the shaped part of the fitting in the hole 2 Connect the fitting fig 10 to a sufficiently resistant rubber hose so that it is not...

Page 31: ...lected since the operating pres sure values are sensibly higher than those of the R32 refrigerant The following table gives the thickness values of the recommen ded copper pipes in relation to the nom...

Page 32: ...0 13 2 13 5 9 7 20 22 1 2 12 70 0 80 16 6 16 0 12 9 23 26 5 8 15 88 1 00 19 7 19 0 16 0 25 29 fig 17 Note Make sure that the oil used to lubricate the flare is the same type or compatible with the oil...

Page 33: ...available on the market Pay also attention to the connection points accor ding to what described Use thermal insulating tape to tie the hoses from the area con necting the outdoor unit cocks to the up...

Page 34: ...nitrogen bottle N2 Pressurize the system to a maximum 30 bar using the nitrogen in the bottle Use liquid soap to check that the joints are tight Keep the bottle vertical during the pressurizing operat...

Page 35: ...rosion in the circuit This is why a vacuum must be created in the connection pipes and indoor unit Proceed in the following way Connect the previously described charging pipe to the vacuum pump Turn o...

Page 36: ...terminals of the general switch must be connected consult the wiring diagrams supplied with the unit The electrical panels are fitted with a terminal for connecting the earth wire identified by the m...

Page 37: ...iminary controls start the machine with the remote control Press the ON button and select the required operating mode The remote control functions are illustrated in the user manual 4 SAFETY AND POLLU...

Page 38: ...LENGTE EN HOOGTEVERSCHIL VAN DE KOELLEIDINGEN 46 2 5 INSTALLATIE VAN DE BUITENUNIT 47 2 6 CONDENSAFVOERSET VOOR DE BUITENUNIT 48 2 7 VERBINDINGSLEIDINGEN 49 2 8 KOELAANSLUITINGEN 51 2 9 ISOLATIE VAN L...

Page 39: ...rvicedienst in samenwerking met onze dealers altijd tot uw beschikking voor eventuele adviezen en directe ingrepen 1 3 PRESENTATIE VAN DE UNIT Airconditioners zijn lucht lucht klimaatregelingstoestell...

Page 40: ...Effici ntieklasse Standaard 626 2011 Richtlijn 2009 125 CE Koeling A A A A Verwarming A A A A Stroomverbruik in stand bymodus 0 5 0 5 0 5 0 5 W Luchtstroom Max med min 460 330 260 530 400 350 800 600...

Page 41: ...wordt om de unit in de hieronder beschreven omstandigheden te gebruiken Bedrijfsmodus Parameter Binnenkant Buitenzijde UM B S B U B S B U Koeling Maximale inlaatluchttemperatuur 32 23 50 C Minimale in...

Page 42: ...RESSOR De compressor die zich in de buitenunit bevindt is van het RO TERENDE type met beveiliging tegen thermische en elektrische overbelastingen Hij is gemonteerd op rubberen steunen om tril lingsver...

Page 43: ...gewijzigd worden Sluit de stroomtoevoer af alvorens werkzaamheden aan de machine te verrichten Leg geen voorwerpen op de bovenkant van de unit Steek geen voorwerpen door de beschermroosters van de ven...

Page 44: ...teriaal niet in het milieu achter Ga als volgt te werk zodra de installatieplaats is gekozen zie de betreffende paragrafen verderop om de twee units uit te pakken 1 Snijd de twee nylon strips door 2 N...

Page 45: ...jde grootste diameter 4 Leiding vloeistofzijde 5 Condensafvoerslang 6 Sifon Fig 4 Buitenunit hoog en binnenunit laag geplaatst Fig 5 In dit geval moeten er elke drie meter hoogteverschil sifons 6 word...

Page 46: ...n L zijn de drukverliezen kleiner waardoor het totale rendement van het apparaat hoger wordt Neem de limieten in de volgende tabellen in acht Model UM 9 12 18 24 Vloeistoflijnverbindingen 1 4 1 4 1 4...

Page 47: ...ter condens die op de ondergrond valt en soms lastige en of onaangename wate rafzettingen vormt Gebruik de condensafvoerset volgens de aanwijzingen in de desbetreffende paragraaf om dit te voorkomen 5...

Page 48: ...gd door het geprofileerde deel in de opening te steken 2 Verbind met het verbindingsstuk 1 Fig 10 een voldoende stevige rubberslang stevig genoeg om vervorming en hieruit mogelijk voortvloeiende verna...

Page 49: ...r en de diameter van de buis moet in het gat passen Aangezien de bedrijfsdrukwaarden aanzienlijk hoger liggen dan bij R32 koelmiddel is het noodzakelijk om de juiste materialen te kiezen De onderstaan...

Page 50: ...0 12 9 23 26 5 8 15 88 1 00 19 7 19 0 16 0 25 29 Fig 17 NB controleer of de gebruikte smeerolie voor het wijder gemaakte uiteinde van hetzelfde type of compatibel is met de gebruikte olie in het koelc...

Page 51: ...de verbindingspunten volgens de beschrijvingen Gebruik warmte isolatietape om de leidingen te omwikkelen van de aansluitzone met de kranen van de buitenunit tot het bovenste uiteinde van de leiding o...

Page 52: ...Het systeem op een druk van maximum 30 bar brengen met de stikstof uit de fles De afdichting van de verbindingen controleren met vloeibare zeep Om te voorkomen dat er vloeibare stikstof in het systee...

Page 53: ...in het circuit De verbindingsleidingen en de binnenunit moeten dan vacu m worden getrokken Ga hiervoor als volgt te werk Sluit de eerder beschreven vulbuis op de vacu mpomp aan Open de knop op de man...

Page 54: ...s op de ingangsklemmen van de scheidingsinrichting van de voeding aan te sluiten raadpleeg de schakelschema s die bij de machine zijn geleverd De schakelkasten zijn voorzien van een aansluitklem van d...

Page 55: ...uk in het koelcircuit 3 4 INSCHAKELING Na de voorafgaande controles moet de unit met de afstandsbediening worden ingeschakeld om de machine in werking te stellen Druk op de startknop en stel de gewens...

Page 56: ...IT Cod 3QEXXXX Rev 00 56 Made in China LAMBORGHINI Caloreclima un marchio del gruppo FERROLI Spa 37047 San Bonifacio Verona Italy Via Ritonda 78 A tel 39 045 6139411 fax 39 045 6100933 www ferroli co...

Reviews: