FL 32 MCA
6
EN
Notes:
1.
Parameters with more than one description vary their function and/or range in relation to the setting of the parameter given in brackets.
2.
Parameters with more than one description are reset to the default value if the parameter given in brackets is modified.
3.
The Maximum Heating Power parameter can also be modified in Test Mode.
Press the Reset button to return to the Service Menu. Press the Reset button for 20 seconds to exit the card Service Menu, or exiting occurs automatically after 15 minutes.
"In” - Information Menu
7 pieces of information are available.
Press the Heating buttons to scroll the list of information in increasing or decreasing order. Press the DHW buttons to display the value.
Notes:
1.
In case of damaged sensor, the card displays hyphens.
Press the Reset button to return to the Service Menu. Press the Reset button for 20 seconds to exit the card Service Menu or exiting occurs automatically after 15 minutes.
"Hi" - History Menu
The card can store the last 11 faults: the History datum item H1: represents the most recent fault that occurred; the History datum item H10: represents the least recent fault that occurred.
The codes of the faults saved are also displayed in the corresponding menu of the Remote Timer Control.
Press the Heating buttons to scroll the list of faults in increasing or decreasing order. Press the DHW buttons to display the value.
Press the Reset button to return to the Service Menu. Press the Reset button for 20 seconds to exit the card Service Menu, or exiting occurs automatically after 15 minutes.
"rE" - History Reset
Press the Eco/Comfort button for 3 seconds to delete all the faults stored in the History Menu: the card will automatically exit the Service Menu, in order to confirm the operation.
Press the Reset button for 20 seconds to exit the card Service Menu, or exiting occurs automatically after 15 minutes.
P07
Burner shutdown in hot water production (b02=1)
0=Fixed
0=Fixed
0=Fixed
1=Linked to set point
2=Solar (5)
3=Solar (10)
4=Solar (20)
Burner shutdown in hot water production (b02=2)
0=Fixed
0=Fixed
1=Linked to set point
2=Solar (5)
3=Solar (10)
4=Solar (20)
Hot water tank hysteresis (b02=3)
0-4°C
2°C
Hot water tank hysteresis (b02=4)
0-4°C
2°C
P08
DHW standby time (b02=1)
0-60 seconds
30 seconds
60 seconds
DHW standby time (b02=2)
0-60 seconds
60 seconds
DHW standby time (b02=3)
0-60 seconds
30 seconds
DHW standby time (b02=4)
0-60 seconds
30 seconds
P09
DHW user max. set point (b02=1)
50-65°C
50°C
55°C
DHW user max. set point (b02=2)
50-65°C
55°C
DHW user max. set point (b02=3)
50-65°C
65°C
DHW user max. set point (b02=4)
50-65°C
65°C
P10
Anti-inertia function temperature (b02=1)
70-85°C
70°C
0
No effect on adjustment (b02=2)
--
0
Delivery temperature in hot water production (b02=3)
70-85°C
80°C
Delivery temperature in hot water production (b02=4)
70-85°C
80°C
P11
Anti-inertia function Post-Circulation (b02=1)
0-5 Seconds
0 seconds
30 seconds
DHW Post-Circulation (b02=2)
0-60 Seconds
30 seconds
DHW Post-Circulation (b02=3)
0-60 Seconds
30 seconds
DHW Post-Circulation (b02=4)
0-60 Seconds
30 seconds
P12
Max. output in DHW
0-100%
100%
100%
P13
Absolute min. power
0-100%
0%
0%
P14
Post-Ventilation
0=Default
0=Default
0=Default
1=50 seconds
P15
CO2 limit Offset (b03=0)
0 (Minimum)
30 (Maximum)
20
20
No effect on adjustment (b03=1)
--
20
No effect on adjustment (b03=2)
--
20
CO2 limit Offset (b03=3)
0 (Minimum)
30 (Maximum)
20
CO2 limit Offset (b03=4)
0 (Minimum)
30 (Maximum)
20
No effect on adjustment (b03=5)
--
20
P16
Exchanger protection activation
0=No F43
10°C/second
10°C/second
1-15=1-15°C/second
Contents
Description
Range
t01
NTC Heating sensor (°C)
between 05 and 125 °C
t02
NTC Safety sensor (°C)
between 05 and 125 °C
t03
NTC DHW sensor (°C)
between 05 and 125 °C
t04
NTC External sensor (°C)
between -30 and 70°C (negative values flash)
L05
Actual burner power (%)
00%=Min., 100%=Max.
F06
Actual Flame resistance (Ohm)
00-99 Ohm (-- = burner off)
St07
Fan step (Number)
0=Off, 1=Min, 2=Med, 3=Max
Contents
Description
Range
Default
FL 32 MCA
cod. 3541F151 - Rev. 01 - 03/2018