46
LOCK CODE
AL01
AL02
AL03
AL04
AL05
AL06
AL07
AL08
AL09
AL10
Burner lock-out alert
Total safety thermostat triggering
Boiler probe in short circuit (CC)
Interrupted boiler probe (CA)
Water heater probe in short circuit (CC)
Interrupted water heater probe (CA)
External probe in short circuit (> 50°C) (CC)
Interrupted external probe (< -25°C) (CA)
No communication with remote control or
multi-zone board
Fumes safety thermostat triggering
String
Effect
Problem
The failure led blinks. The hour counter stops.
The burner is still fed. The last circulator called
activates for the post-circulation time P14. After
resetting the burner control box, the failure led
still blinks for 10 seconds
The failure led blinks. The burner shuts off. The
hour counter stops. The last circulator called ac-
tivates
The failure led blinks. Burner and circulators shut
off
The failure led blinks. Burner and circulators shut
off
The failure led blinks. The hot water system is
excluded
The failure led blinks. The hot water system is
excluded
The heating external probe is excluded (manual
operation)
The failure led blinks. The heating external probe
is excluded (manual operation). The Ext symbol
on the LCD blinks
Active alarm if, once the remote control or the
multi-zone board is connected, the system de-
tects that there is no serial communication. The
alarm is reset the first time the connection is re-
stored. Exclusion of all commands handled by
the presence of the remote control and exclusion
of all functions related to the presence of the multi-
zone board
Not active
Summary of Contents for ERA 31 BS 130
Page 2: ...2...
Page 11: ...11 PROGRAMMAZIONE DEL CRONODATARIO...
Page 28: ...28...
Page 37: ...37 PROGRAMMING THE HOUR DATE COUNTER...
Page 54: ...54...
Page 63: ...63 PROGRAMACI N DEL RELOJ PROGRAMMADOR DIGITAL...
Page 80: ...80...
Page 89: ...89 ACERTARO REL GIO PROGRAMADOR...
Page 106: ...106...
Page 107: ...107...