43
UK
CALIBRATION OF AIR PRESSURE SWITCH
The air pressure switch places the burner in safety mode or shuts it down should there be a drop in combustion
air pressure. It will be calibrated at a pressure below 1st stage rated-flow on-burner air pressure, checking that
CO values do not exceed 10,000 p.p.m..
CALIBRATION OF MINIMUM GAS PRESSURE SWITCH
The minimum gas pressure switch serves to prevent the burner from being started up or to shut it down if the
gas pressure falls below the minimum required level. This setting should be 40% lower than the gas pressure
obtained with the burner operating at maximum delivery.
Pressure
outlet
PRESSURE
Type:
LGW 10 A2P
GW 150 A5
Remove the cover and adjust
dial A
GAS PRESSURE
AIR PRESSURE
Model
Air pressure
switch type
Setting range
mbars
Air pressure
switch type
Setting range
mbars
310 PM/M-E
LGW 10 A2P
1 - 10
GW 150 A5
5 - 120
430 PM/M-E
CHECKING IONIZATION CURRENT
Microamperemeter connection
The minimum value of 30 μA should be observed,
and large oscillations are to be avoided.