Lamborghini Caloreclima 0DAC4ZYD Instructions For Use, Installation And Maintenance Download Page 3

FL D C

3

EN

cod. 3541P520  -  Rev. 00  -  06/2018

DHW temperature adjustment

Use the DHW buttons (details 1 and 2 - fig. 1) to adjust the temperature from a min. of
40°C to a max. of 55°C.

fig. 5

Room temperature adjustment (with optional room thermostat)

Using the room thermostat, set the temperature required in the rooms. If the room ther-
mostat is not installed, the boiler will keep the system at the set system delivery setpoint
temperature.

Room temperature adjustment (with optional remote timer control)

Using the remote timer control, set the required temperature in the rooms. The boiler will
adjust the system water according to the required room temperature. For operation with
remote timer control, please refer to the relevant instruction manual.

ECO/COMFORT selection

The unit has a function that ensures a high domestic hot water delivery speed and max-
imum comfort for the user. When the device is activated (COMFORT mode), the water
contained in the boiler is kept hot, thereby ensuring immediate availability of hot water
on opening the tap, without waiting times.
The user can deactivate the device (ECO mode) by pressing the 

eco/comfort

 button

(detail 7 - fig. 1). In ECO mode the display activates the ECO symbol (detail 12 - fig. 1).
To activate the COMFORT mode, press the 

eco/comfort

 button (detail 7 - fig. 1) again.

Sliding Temperature

When the optional external probe is installed the boiler adjustment system works with
"Sliding Temperature". In this mode, the heating system temperature is regulated ac-
cording to weather conditions, to ensure the high comfort and energy efficiency through-
out the year. In particular, as the outside temperature increases the system delivery
temperature decreases according to a specific "compensation curve".
With the Sliding Temperature adjustment, the temperature set with the heating buttons
(detail 3 - fig. 1) becomes the maximum system delivery temperature. It is advisable to
set a maximum value to allow system adjustment throughout its useful operating range.
The boiler must be adjusted at the time of installation by qualified personnel. However,
the user can make any further adjustments necessary to optimise comfort levels.
Compensation curve and curve offset
Press the 

reset button

 (detail 6 - fig. 1) for 5 seconds to access the “Sliding temperature”

menu; the display shows “CU” flashing.
Use the DHW buttons (detail 1 - fig. 1) to adjust the desired curve from 1 to 10 according
to the characteristic (fig. 6). By setting the curve to 0, the sliding temperature adjustment
is disabled.
Press the heating buttons (detail 3 - fig. 1) to access parallel curve offset; the display
shows “OF” flashing. Use the DHW buttons (detail 1 - fig. 1) to adjust parallel curve offset
according to the characteristic (fig. 7).
Press the 

reset button

 (detail 6 - fig. 1) again for 5 seconds to exit the "Sliding Temper-

ature" menu.
If the room temperature is lower than the required value, it is advisable to set a higher
order curve and vice versa. Proceed by increasing or decreasing in steps of one and
check the result in the room.

fig. 6 - Compensation curves

fig. 7 - Example of compensation parallel curve offset

Adjustments from Remote Timer Control

A

If the Remote Timer Control (optional) is connected to the boiler, the above ad-
justments are managed according to that given in table 1.

Table. 1

System water pressure adjustment

The filling pressure read on the boiler water gauge (detail 2 - fig. 8) with system cold must
be approx 1.0 bar. If the system pressure falls below minimum values, the boiler stops
and fault 

F37

 is displayed. Pull out the filling knob (detail 1 - fig. 8) and turn it anticlock-

wise to return it to the initial value. Always close it afterwards.
Once the system pressure is restored, the boiler will activate the 300-second air venting
cycle indicated on the display by 

Fh

.

To prevent boiler shutdown, it is advisable to periodically check the pressure on the
gauge with system cold. In case of a pressure below 0.8 bar, it is advisable to restore it.

fig. 8- Filling knob

System draining

The drain faucet ring nut is located under the safety valve inside the boiler.
To drain the system, turn the ring (ref. 1 - fig. 9) counter-clockwise to open the faucet. Do
not use any tools; use hands only.
To drain only the water in the boiler, first close the shut-off valves between the system
and boiler before turning the ring.

fig. 9- Safety valve with drain faucet

I I I I

II

II

I

20

30

40

50

60

70

80

90
85

20

10

0

-10

-20

1

2

3

4

5

6

8

9

10

7

20

30

40

50

60

70

80

90

85

20

30

40

50

60

70

80

90

85

1

2

3

4

5

6

8

9

10

7

1

2

3

4

5

6

8

9

10

7

OFFSET = 20

OFFSET = 40

Heating temperature setting

Adjustment can be made from the Remote Timer Control menu 
and the boiler control panel.

DHW temperature adjustment

Adjustment can be made from the Remote Timer Control menu 
and the boiler control panel.

Summer/Winter Switchover

Summer mode has priority over a possible Remote Timer Control 
heating demand.

Eco/Comfort selection

On disabling DHW from the Remote Timer Control menu, the 
boiler selects the Economy mode. In this condition, the 

eco/com-

fort

 button (detail 7 - fig. 1) on the boiler panel is disabled.

On enabling DHW from the Remote Timer Control menu, the 
boiler selects the Comfort mode. In this condition it is possible 
select one of the two modes with the 

eco/comfort

 button (detail 7 

- fig. 1) on the boiler panel.

Sliding Temperature

Both the Remote Timer Control and the boiler card manage Slid-
ing Temperature adjustment: the boiler card Sliding Temperature 
has priority.

A

1

2

1

B

1

Summary of Contents for 0DAC4ZYD

Page 1: ...C24 32 c od 3541P520 Rev 00 06 2018 INSTRUCTIONS FOR USE INSTALLATION AND MAINTENANCE RU 1 3541P520...

Page 2: ...tion 17 Water gauge Indication during operation Heating A heating demand generated by the Room Thermostat or Remote Timer Control is in dicated by flashing of the hot air above the radiator on the dis...

Page 3: ...1 fig 1 to adjust parallel curve offset according to the characteristic fig 7 Press the reset button detail 6 fig 1 again for 5 seconds to exit the Sliding Temper ature menu If the room temperature i...

Page 4: ...lling a gas cock between the system and boiler Make sure all the gas con nections are tight 3 5 Electrical connections IMPORTANT B BEFORE CARRYING OUT ANY OPERATION THAT REQUIRES REMOVING THE CASING D...

Page 5: ...1 or 2 units of the parameter q01 by pressing the DHW button after each change wait 10 seconds for the pressure to stabilise 9 When the pressure read on the pressure gauge is equal to the minimum nom...

Page 6: ...b02 4 b06 Mains Voltage Frequency 0 50Hz 0 1 60Hz b07 Comfort burner on time b02 1 0 20 seconds 5 No effect on adjustment b02 2 No effect on adjustment b02 3 No effect on adjustment b02 4 b08 Gas valv...

Page 7: ...s of the fuel circuit and water systems Check the efficiency of the flue and air fume ducts while the boiler is working Make sure the water is circulating properly between the boiler and the systems M...

Page 8: ...if necessary A09 Gas valve fault Wiring disconnected Check the wiring Faulty gas valve Check the gas valve and replace it if necessary F10 Delivery sensor 1 fault Sensor damaged Check the wiring or re...

Page 9: ...et 1 2 9 Cold water inlet 1 2 10 System delivery 3 4 11 System return 3 4 fig 15 Front view fig 16 Side view fig 17 Top view FL D C24 fig 18 Bottom view FL D C24 and C32 fig 19 Top view FL D C32 700 4...

Page 10: ...0 12 0 Min gas pressure at burner G20 mbar 1 5 1 5 Max gas flow G20 m3 h 2 73 3 64 Min gas flow G20 m3 h 0 88 1 22 Burner nozzles G31 no x 11 x 0 79 15 x 0 79 Gas supply pressure G31 mbar 37 37 Max g...

Page 11: ...LPG B NATURAL GAS Circulating pump head pressure losses FL D C32 A Boiler pressure losses 1 2 and 3 Circulating pump speed A 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 35 30 25 20 15 10 5...

Page 12: ...ating pump 42 DHW temperature sensor 44 Gas valve 72 Room thermostat optional 81 Ignition detection electrode 95 Diverter valve 114 Water pressure switch 126 Fume thermostat 136 Flowmeter 138 External...

Page 13: ...7 18 20 G8 0037 B A B 0DQXIDFWXUHU 0DQXIDFWXUHU DGGUHVV Model RGH Qnw Hi PMS PMW Qn Hi tmax C D Pn 80 60 H2O Pn 50 30 12 Serial number DUFRGH 1 1 3URGXFWLRQ GDWH See the manual 80 IPX5D 23 5 7 0 8 3 2...

Page 14: ...1 1 2 3 4 5 6 7 8 9 10 11 12 Eco 13 14 15 16 17 11 1 d2 11 1 d1 Comfort 11 1 cap 4 4 11 1 d3 d4 d5 2 3 5 7 1 5 2 7 1 5 3 B sez 3 3 2 4 6 1 2 10 1 6 1 2 3 4 1 30 C 80 C 45 C 4 0 1 4 2 3 reset eco comf...

Page 15: ...3 1 6 1 5 CU 1 1 1 10 6 0 3 1 OF 1 1 7 6 1 5 6 7 A 1 1 2 8 1 0 F37 1 8 300 Fh 0 8 8 1 9 9 I I I I I I I I I 20 30 40 50 60 70 80 90 85 20 10 0 10 20 1 2 3 4 5 6 8 9 10 7 20 30 40 50 60 70 80 90 85 20...

Page 16: ...D C 16 RU cod 3541P520 Rev 00 06 2018 3 3 1 3 2 B 5 C 15 C A 3 3 B B 18 25 Fr 1 F 10 CaCO3 3 4 18 3 5 B B 3 3A B HAR H05 VV F 3x0 75 2 8 B 230 23 10 3 6 0 5 B 4 B LAMBORGHINI 1 2 3 4 5 6 72 139 138 3...

Page 17: ...0 15 Eco comfort 5 B TEST Eco Comfort 2 q02 q02 1 2 10 3 1 q01 q01 1 2 10 Eco Comfort 2 TEST TEST TEST 3 4 1 5 TEST 13 13 TEST 100 3 4 1 00 100 1 1 0 2 1 100 TEST TEST 3 TEST 3 4 1 5 TEST 15 TEST sez...

Page 18: ...10 b02 2 10 100 10 15 b02 3 b02 4 b12 0 1 0 FL D C P01 0 40 20 P02 1 20 C 5 P03 0 10 2 P04 0 20 6 P05 31 85 C 80 P06 0 100 100 P07 b02 1 0 1 2 3 4 b02 2 0 0 1 2 3 4 b02 3 0 1 2 3 4 C b02 4 0 1 2 3 4 C...

Page 19: ...set 20 20 rE History 3 Eco comfort History Service Service Re set 20 20 4 2 B cap 5 4 3 B 14 1 P19 b02 1 0 20 C 10 b02 2 0 20 C b02 3 b02 4 P20 b02 1 0 20 C 10 b02 2 0 20 C b02 3 b02 4 P21 b02 1 0 20...

Page 20: ...2 5 5 1 3 20 21 22 A01 A02 A03 F04 20 F05 A06 F07 A09 F10 1 F11 F14 2 A16 F20 A21 A23 A24 F34 170 F35 F37 F39 A41 o o a e o c o o e c a oc a e a o c c e e o e F42 F43 H 2O F50 8 1 2 56 9 1 2 74 10 3...

Page 21: ...cod 3541P520 Rev 00 06 2018 7 3 4 8 1 2 9 1 2 10 3 4 11 3 4 15 16 17 FL D C24 18 FL D C24 e C32 19 FL D C32 700 400 mm 131 C24 mm 143 C32 0 1 2 3 4 330 208 216 184 36 66 66 66 66 100 155 10 8 7 9 11...

Page 22: ...P 23 5 31 3 7 0 9 7 Pmax 80 60 C 91 0 91 0 30 89 6 89 8 NOx 3 150 mg kWh NOx G20 x 11 x 1 35 15 x 1 35 G20 20 0 20 0 G20 12 0 12 0 G20 1 5 1 5 G20 3 2 73 3 64 G20 3 0 88 1 22 G31 x 11 x 0 79 15 x 0 79...

Page 23: ...11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 35 30 25 20 15 10 5 kW mbar B 0 1 2 3 4 5 6 7 0 500 1 000 1 500 2 000 Q l h H m H 2 O A 3 2 1 kW 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 2...

Page 24: ...cod 3541P520 Rev 00 06 2018 5 6 23 A 32 42 44 72 81 95 114 126 136 138 139 278 81 1kW L N 230V 50 Hz 32 L N T T 278 T 42 4 3 2 1 44 136 ABM01A 95 3 2 1 RED LIGHT BLUE WHITE G N D O U T 5 V 114 126 3 2...

Page 25: ......

Page 26: ......

Page 27: ......

Page 28: ...i VIA n 047 6 BRUCIATORI CALDAIE MURALI E TERRA A GAS GRUPPI TERMICI IN GHISA E IN ACCIAIO GENERATORI DI ARIA CALDA TRATTAMENTO ACQUA CONDIZIONAMENTO...

Reviews: