Page 28
8.7. System layout 7 (2 collector arrays, 2 storage reservoirs, 2 pumps, 1 three-way valve)
Description of the system layout:
The solar controller compares the temperatures from collector
sensors F1 (TC1) and F2 (TC2) with the temperatures from the
storage reservoir sensors F4 and F6. If one of the measured
temperature differences exceeds one of the switch-on
temperature differences set here (TDE1 or TDE2), the
corresponding storage reservoir is loaded by means of the
respective speed-controlled solar pump R1 or R2 and the three-
way valve R3. The selected first-priority storage reservoir is
loaded for as long as a loading precondition persists for this
storage reservoir. Afterwards, the second-priority storage
reservoir is loaded by means of batch loading.
F1
R1
(F5)
F6
F2
R2
R3
(F3)
F4
The following settings are possible in this system layout:
Level
Display
Function
Factory
setting
Range
Selection
AE
MAX1
Maximum loading temperature
MAX1 for storage reservoir 1.
70 °C
10 °C to 90 °C
AE
MAX2
Maximum loading temperature
MAX2 for storage reservoir 2.
70 °C
10 °C to 90 °C
AE
SPA1
Activation / deactivation of
storage reservoir 1.
YES
YES / no
AE
SPA2
Activation / deactivation of
storage reservoir 2.
YES
YES / no
E3-1 / 1
KON
System layout setting.
1
1 to 7
7
E3-1 / 3
SPV
Number of the first-priority
storage reservoir (see section
9.1
.
Batch loading
).
1
0 to 2
E3-1 / 4
SLZ
Batch loading time (see section
9.1.).
15 min.
1 to 60 min.
E3-1 / 5
SPZ
Batch pause time after batch
loading (see section 9.1.).
2 min.
1 to 60 min.
E3-1 / 6
KAT
Limit for collector’s temperature
increase in the batch pause time
(see section 9.1.).
2
1 to 10 K
E3-1 / 13
SSP1
Upper storage reservoir sensor
F3 present (storage reservoir 1),
see section 5.5.
YES
YES / no
E3-1 / 14
SSP2
Upper storage reservoir sensor
F5 present (storage reservoir 2),
see section 5.5.
YES
YES / no
Configuration of system layouts