Temperature Compensation
–
Allows enable or disable of the Temperature Compensation feature.
•
Select TEMP. COMP. from Configuration Menu
o
Select DISABLE or ENABLE
NOTE:
For internal compensation, enable the setting and place JP4 jumper across pins 1 and 2. For external
compensation, disable the setting and place jumper across 2 and 3 (refer to Figure 10 and 11).
Battery Test
–
Allows the user to select whether the battery test is performed automatically or manually. The
automatic battery test can be performed every day, every 7, 14, 21, 30, or every 60 days.
•
Select BATTERY TEST from configuration menu
o
Select MAN. BAT. TEST or AUTO BAT. TEST with the following selections available:
Everyday:
Battery Test is started automatically everyday
7 Days:
Battery Test is started automatically every 7 days
14 Days:
Battery Test is started automatically every 14 days
21 Days:
Battery Test is started automatically every 21 days
30 Days:
Battery Test is started automatically every 30 days
60 Days:
Battery Test is started automatically every 60 days
Alarm Settings
–
Allows setting the alarm thresholds for the provided alarms and the alarm time delay
•
Select ALARM SETTING from the Configuration Menu.
o
ALARM DELAY
▪
Select the alarm delay in seconds. Delay can be set from 1 second to 255 seconds
o
GROUND DETECTION DELAY
▪
Select the ground detection alarm delay in seconds. Delay can be set from 1 to 255 seconds
o
DC LOW VOLTAGE
▪
Select the desired low voltage alarm point in V/C (volts per cell)
o
DC HIGH VOLTAGE
▪
Select the desired high voltage alarm point in V/C (volts per cell)
o
LOW DC CURRENT
▪
Select the desired low DC current alarm point in amps
NOTE:
The Low DC Current alarm can be disabled if considered a nuisance. To disable the alarm, continuously
press the DOWN button until OFF is displayed.