Storing the ITSM
If the ITSM is to be stored for more than a few days after delivery, it should be stored within its shipping
container. The location chosen for storage should be within an ambient temperature of -40 to 185° F (-40 to
85° C) with a non-condensing relative humidity of 0 to 95%.
Mounting the ITSM
When mounting the ITSM, consider the size and weight of the unit. The floor must be able to support the
weight of the unit as well as an additional safety factor. The location chosen for the ITSM should be within an
ambient temperature range of 32 to 122°F (0 to 50°C) with a non-condensing relative humidity no higher than
95%. The ITSM should be mounted in an area free of explosive materials and away from drips and splatter. The
ITSM utilizes convection cooling so a clearance of at least 6in (152mm) of free air must be maintained on the
top, bottom, back and both sides for cooling air. Maintain 36in (914mm) or more of clearance at the front of the
unit in order to allow for operation and maintenance.
Case number
Cable Entry
Mounting
AC input
AC Output
108
Top Right
Top Left
Floor
Floor-Mounting the ITSM
Floor mounting the 108 cases is standard. To floor-mount the ITSM, install four bolts into the floor. Place the
ITSM on the bolts, add appropriate mounting hardware, and tighten securely. The figure below shows the
footprint and the bolt size of each ITSM case style. (All dimensions are in inches)
Case
number
Dim.
A
Dim.
B
Bolt
Size
108
18.288
11
3/8