INSTRUCTIONS FOR THE INSTALLER 

 

 

2.  

 

INSTRUCTIONS FOR THE 

INSTALLER  

2.1.

 

Warning to installers 

All  local  and  national  regulations, 

including all those referring to national and 
European  standards,  must  be  observed 
when installing the appliance. 

Installation  of  the  appliance  must  be 

performed by an authorised installer. 

An  incorrectly  installed  appliance  may 

lead  to  serious  incidents  (fires,  creation  of 
harmful  gases,  deterioration  of  nearby 
fixtures, etc.). 

Lacunza’s  liability  is  limited  to  the 

supply of the material and does not include 
installation of the appliance. 

2.2.

 

Room for installation 

2.2.1.

 

Ventilation of the room 

The  appliance  needs  to  consume 

oxygen  (air)  in  order  to  work  properly. 
Ensure a suitable air supply in the room in 
which the appliance is fitted. This quantity 
of  oxygen  is  additional  to  the  oxygen  that 
we need in order to breathe (air renewal).  

In  order  to  ensure  the  high  quality  of 

the  air you breathe and to avoid potential 
accidents 

resulting 

from 

high 

concentrations  of  the  gases  produced  by 
combustion  (mainly  carbon  dioxide  and 
carbon monoxide), it is absolutely crucial to 
ensure  the  suitable  renewal  of  the  air  in 
the room in which the appliance is fitted. 

the room must always have at least two 

permanent  grilles  or  openings  to  the 
exterior in order to renew the air (one  for 
intake and the other for extraction). 

For  the  installation  of  its  appliances, 

Lacunza recommends an additional section 
for these openings. One of these two grilles 
must  be  situated  high  up  in  the  room  (at 

less  than  30  cm  from  the  ceiling)  and  the 
other  one  low  down  (at  less  than  30  cm 
from  the  floor).  Both  grilles  must  open 
outdoors  in  order  to  renew  the  air  in  the 
room with fresh air. 

The minimum section that each of these 

grilles  must  have  depends  on  the  nominal 
output of the appliance in accordance with 
the following table: 

 

 

 

 

Figure No.2 -

 

Guideline indications for 

ventilation grilles 

The appliance must always be used with 

the door(s) closed.  

In  rooms  equipped  with  Controlled 

Mechanical 

Ventilation, 

the 

system 

extracts  and  renews  the  ambient  air;  in 
such  cases,  the  room  is  at  slightly  low 
pressure and it is necessary to install a non-
closable  outside-air  inlet  with  a  section  of 
at least 90 cm². 

Output of the 

appliance 

(kW)

Minimum 

additional section 

of each of the 

grilles (cm

2

)

P ≤ 10kW

70

10 < P ≤ 15

90

15 < P ≤ 20

120

20 < P ≤ 25

150

25 < P ≤ 30 

180

30 < P ≤ 35 

210

P > 35

240

Summary of Contents for IV-800

Page 1: ...IV 800 Instruction Book...

Page 2: ...Warning to installers 5 2 2 Room for installation 5 2 2 1 Ventilation of the room 5 2 2 2 Location of the appliance in the room 6 2 3 Installation of the appliance 6 2 3 1 Floor 6 2 3 2 Safety distan...

Page 3: ...4 1 1 Firebox 20 4 1 2 Flue socket 20 4 1 3 Painted sheet steel cast iron parts 20 4 1 4 Firebox glass 20 4 1 5 Electrical system 20 4 1 6 Air intake registers 20 4 2 Maintenance of the chimney flue 2...

Page 4: ...legislation applicable in each country and this instruction book 1 1 General characteristics Unit IV 800 Nominal Heat Output N H O to atmosphere kW 8 5 Efficiency at N H O 78 CO emission at 13 O2 at N...

Page 5: ...dity of the fuel fuel loads fuel load frequencies flue draught and system of installation indicated in this Instruction Book Failure to respect these conditions may lead to problems with the appliance...

Page 6: ...lutely crucial to ensure the suitable renewal of the air in the room in which the appliance is fitted the room must always have at least two permanent grilles or openings to the exterior in order to r...

Page 7: ...the left hand side 400 From the rear 400 From the front 1000 Bear in mind that it may even be necessary to protect non combustible material in order to prevent breakage deformation etc as a result of...

Page 8: ...ow the appliance can be encased properly Figure No 5 Interior diagram of the casing Key to casing diagram 1 Ceiling 2 Flue 3 Incombustible material Inner hood insulation 4 Insulating deflector made of...

Page 9: ...it the necessary inspection accesses trap doors hatches etc so that everything inside the hood that may need maintenance work or replacement can be accessed at any time e g counterweight system hydrau...

Page 10: ...e appliance working at Nominal Heat Output Output kW IV 800 2 5 Note The values shown in the above table were measured at the appliance output point and based on tests performed at nominal heat output...

Page 11: ...n be used to attach it to the apparatus This should be done as follows Loosen without removing the two screws on the upper support of the door with a 10 mm wrench By lifting this piece up the door can...

Page 12: ...al Due to the movement of the ventilators this apparatus may vibrate structures that come into contact with it These vibrations may cause noise To prevent these vibrations from occurring a damping ele...

Page 13: ...imum Each 45 bend is equivalent to a 0 5m reduction in flue length Horizontal flue sections should not be installed because they cut updraught a great deal If the flue draws at more than 20Pa then an...

Page 14: ...acle located within a 10m radius of the chimney outlet by more than 1m Figure No 16 Distances between the chimney crown and objects within a 10m radius The chimney crown must clear any neighbouring bu...

Page 15: ...ly chopped wood produces greater heat output but also burns more quickly Optimum fuels Beech Other fuels Oak chestnut ash maple birch elm etc Pine and eucalyptus logs are low density and produce very...

Page 16: ...rm weather warm days early hours of the afternoon on sunny days may lead to lighting and updraught problems Certain weather conditions such as fog ice humidity entering the flue etc may hinder suffici...

Page 17: ...nutes Always load with the nominal amount see table in section 1 1 For minimum burning e g at night use thicker logs When the firebox is loaded close the door Be careful when placing logs in the fireb...

Page 18: ...e released hatch position In order to fill the complete capacity of the ashpit box shake it back and forth Remove the separator This way there is even greater access to push the ashes from the firebox...

Page 19: ...cooking grille is an element to be used intermittently The grille is not designed to work non stop over the fire Never close the door with the handles inside the firebox These handles should only be u...

Page 20: ...e mains electricity supply in accordance with the conditions described in the relevant section in 1 1 Potentiometer operation By means of its rotating lever the potentiometer controls the flow of hot...

Page 21: ...for longer However the glass may get dirty the longer the appliance is used Special degreasing products designed for the purpose should be used to clean it Clean when the glass is cold and taking car...

Page 22: ...ebox block the connection hole with damp cloths and call the fire brigade 4 3 Important advice Lacunza recommends that only Lacunza authorised replacement parts be used Lacunza accepts no liability fo...

Page 23: ...ips carpentry scraps plywood pallets etc Cold flue Heat up the flue by burning a piece of paper in the firebox Smoke during burning The room is at low pressure In rooms with Controlled Mechanical Vent...

Page 24: ...ndici n IF 800 1 9 5044400000 IV 800 Deflector vermiculita IZQ DCHO 2 10 5044400001 IV 800 Angulo sujeci n deflector 1 11 504420000011 Pieza m vil registro primario IF 800 1 12 504420000012 Pieza m vi...

Page 25: ...DECLARATION OF PERFORMANCE 24 7 DECLARATION OF PERFORMANCE...

Page 26: ...DECLARATION OF PERFORMANCE 25 7...

Page 27: ...CE MARK 26 8 CE MARK...

Page 28: ...LACUNZA KALOR GROUP S A L Pol Ind Ibarrea s n 31800 Alsasua Navarra Spain Tel 00 34 948 56 35 11 Fax 00 34 948 56 35 05 e mail comercial lacunza net Website www lacunza net EDITION 0...

Reviews: