background image

 

 

INSTRUCTIONS OF USE 

14 

 

 

3.  

 

INSTRUCTIONS OF USE 

The manufacturer accepts no liability 

whatsoever for damage caused to parts as 

a result of the improper use of non-

recommended fuels, modifications made 

to the appliance or how it is installed. 

Only use original replacement parts. 

All  local  and  national  regulations, 

including  those  referring  to  national  and 
European  standards,  must  be  observed 
when using the appliance. 

Heat  is  diffused  by  radiation  and 

convection via the front and exterior of the 
appliance. 

3.1.

 

Fuel 

This  appliance  must  not  be  used  as  an 

incinerator. Do not use non-recommended 
fuels. 

 

Use  dry  logs  (max.  16%  humidity), 

cut  at  least  2  years  ago,  clean  of  resin 
and  stored  in  a  sheltered,  ventilated 
place. 

 

Use  hard  woods  with  high  calorie 

values and good ember production. 

 

Large logs should be cut to useable 

lengths  before  being  stored.  The  logs 
should  have  a  maximum  diameter  of 
150mm. 

 

Finely-chopped  wood  produces 

greater  heat  output,  but  also  burns 
more quickly. 

Optimum fuels: 

 

Beech. 

Other fuels: 

 

Oak,  chestnut,  ash,  maple,  birch, 

elm, etc. 

 

Pine  and  eucalyptus  logs  are  low 

density  and  produce  very  long  flames, 
and  may  cause  the  parts  of  the 
appliance  to  wear  out  more  quickly 
than normal. 

 

Resinous wood may mean that the 

appliance  and  the  flue  need  to  be 
cleaned more often. 

Non-permitted fuels: 

 

All types of coal and liquid fuel. 

 

“Green  wood”.  Green  or  damp 

wood  reduces  the  performance  of  the 
appliance  and  leads  to  soot  and  tar 
build-up  on  the  inner  walls  of  the  flue, 
obstructing it. 

 

“Recovered wood”. The  b

urning  of 

treated 

woods 

(railway 

sleepers, 

telegraph  posts,  plywood,  fibreboard, 
pallets,  etc.)  quickly  blocks  the  system 
(soot  and  tar  build-up),  harms  the 
environment  (pollution,  smells)  and 
may lead to deformation of the firebox 
due to overheating. 

 

All  materials  which  are  not  wood 

(plastic, spray cans, etc.). 

Green and reprocessed wood may cause 

chimney fires. 

The  graph  below  shows  how  the 

humidity  of  firewood  affects  its  heat 
output: 

 

Figure No.18 -

 

Relationship between 

firewood humidity and heat output. 

 

 

 

 

Summary of Contents for IV-800

Page 1: ...IV 800 Instruction Book...

Page 2: ...Warning to installers 5 2 2 Room for installation 5 2 2 1 Ventilation of the room 5 2 2 2 Location of the appliance in the room 6 2 3 Installation of the appliance 6 2 3 1 Floor 6 2 3 2 Safety distan...

Page 3: ...4 1 1 Firebox 20 4 1 2 Flue socket 20 4 1 3 Painted sheet steel cast iron parts 20 4 1 4 Firebox glass 20 4 1 5 Electrical system 20 4 1 6 Air intake registers 20 4 2 Maintenance of the chimney flue 2...

Page 4: ...legislation applicable in each country and this instruction book 1 1 General characteristics Unit IV 800 Nominal Heat Output N H O to atmosphere kW 8 5 Efficiency at N H O 78 CO emission at 13 O2 at N...

Page 5: ...dity of the fuel fuel loads fuel load frequencies flue draught and system of installation indicated in this Instruction Book Failure to respect these conditions may lead to problems with the appliance...

Page 6: ...lutely crucial to ensure the suitable renewal of the air in the room in which the appliance is fitted the room must always have at least two permanent grilles or openings to the exterior in order to r...

Page 7: ...the left hand side 400 From the rear 400 From the front 1000 Bear in mind that it may even be necessary to protect non combustible material in order to prevent breakage deformation etc as a result of...

Page 8: ...ow the appliance can be encased properly Figure No 5 Interior diagram of the casing Key to casing diagram 1 Ceiling 2 Flue 3 Incombustible material Inner hood insulation 4 Insulating deflector made of...

Page 9: ...it the necessary inspection accesses trap doors hatches etc so that everything inside the hood that may need maintenance work or replacement can be accessed at any time e g counterweight system hydrau...

Page 10: ...e appliance working at Nominal Heat Output Output kW IV 800 2 5 Note The values shown in the above table were measured at the appliance output point and based on tests performed at nominal heat output...

Page 11: ...n be used to attach it to the apparatus This should be done as follows Loosen without removing the two screws on the upper support of the door with a 10 mm wrench By lifting this piece up the door can...

Page 12: ...al Due to the movement of the ventilators this apparatus may vibrate structures that come into contact with it These vibrations may cause noise To prevent these vibrations from occurring a damping ele...

Page 13: ...imum Each 45 bend is equivalent to a 0 5m reduction in flue length Horizontal flue sections should not be installed because they cut updraught a great deal If the flue draws at more than 20Pa then an...

Page 14: ...acle located within a 10m radius of the chimney outlet by more than 1m Figure No 16 Distances between the chimney crown and objects within a 10m radius The chimney crown must clear any neighbouring bu...

Page 15: ...ly chopped wood produces greater heat output but also burns more quickly Optimum fuels Beech Other fuels Oak chestnut ash maple birch elm etc Pine and eucalyptus logs are low density and produce very...

Page 16: ...rm weather warm days early hours of the afternoon on sunny days may lead to lighting and updraught problems Certain weather conditions such as fog ice humidity entering the flue etc may hinder suffici...

Page 17: ...nutes Always load with the nominal amount see table in section 1 1 For minimum burning e g at night use thicker logs When the firebox is loaded close the door Be careful when placing logs in the fireb...

Page 18: ...e released hatch position In order to fill the complete capacity of the ashpit box shake it back and forth Remove the separator This way there is even greater access to push the ashes from the firebox...

Page 19: ...cooking grille is an element to be used intermittently The grille is not designed to work non stop over the fire Never close the door with the handles inside the firebox These handles should only be u...

Page 20: ...e mains electricity supply in accordance with the conditions described in the relevant section in 1 1 Potentiometer operation By means of its rotating lever the potentiometer controls the flow of hot...

Page 21: ...for longer However the glass may get dirty the longer the appliance is used Special degreasing products designed for the purpose should be used to clean it Clean when the glass is cold and taking car...

Page 22: ...ebox block the connection hole with damp cloths and call the fire brigade 4 3 Important advice Lacunza recommends that only Lacunza authorised replacement parts be used Lacunza accepts no liability fo...

Page 23: ...ips carpentry scraps plywood pallets etc Cold flue Heat up the flue by burning a piece of paper in the firebox Smoke during burning The room is at low pressure In rooms with Controlled Mechanical Vent...

Page 24: ...ndici n IF 800 1 9 5044400000 IV 800 Deflector vermiculita IZQ DCHO 2 10 5044400001 IV 800 Angulo sujeci n deflector 1 11 504420000011 Pieza m vil registro primario IF 800 1 12 504420000012 Pieza m vi...

Page 25: ...DECLARATION OF PERFORMANCE 24 7 DECLARATION OF PERFORMANCE...

Page 26: ...DECLARATION OF PERFORMANCE 25 7...

Page 27: ...CE MARK 26 8 CE MARK...

Page 28: ...LACUNZA KALOR GROUP S A L Pol Ind Ibarrea s n 31800 Alsasua Navarra Spain Tel 00 34 948 56 35 11 Fax 00 34 948 56 35 05 e mail comercial lacunza net Website www lacunza net EDITION 0...

Reviews: