LabRepCo LABL-27-HG Manual Download Page 3

2.

 

Operation 

a.

 

Electrical Supply and Connections:  
Plug all standard models into 115 volts A.C. 60 cycle outlet. Low line voltage in often the 
cause of service complaints. Check to see that the line voltage is 110 volts or more with 
the unit running. Other motors or heavy appliances should not be used on the same 
circuit with the cooler. When working on the inside of the cooler disconnect from 
electrical circuit for safety reasons. CAUTION: If an extension cord is necessary, use only 
a three wire grounding type of wire 16AWG or larger; do not exceed 20 ft. in length. The 
use of ungrounded cords or overloaded circuits voids compressor warranty.  
 

b.

 

Temperature Control: See Control instructions for more info. 
Factory setting of temperature control is 4°C. To change temperature hold down set key 
for 3 seconds, press up or down arrow to change set point and press set to finish. 
 

c.

 

Condensate Disposal: 
The evaporator blower housing serves as a pan to collect and direct the condensate to 
the evaporator pan located behind the front grille. Air flow over the pan hastens 
condensate evaporation so that external drain plumbing is not required.  
 

3.

 

Maintenance – Caution: Disconnect Electrical service before accessing mechanical enclosures 
having moving and/or electrical components.  

a.

 

Cleaning Cabinet Exterior:  
Cabinets should be cleaned with a solution of mild soap and water. Do not use caustic 
soap or abrasive cleaners, since these might damage the cabinet finish. If stainless steel 
surface becomes discolored, scrub by rubbing only in the direction of the finish grain. Do 
not use steel wool.  
 

b.

 

Cleaning Interior Surfaces:  
The inside of the cabinet is coated with baked-on vinyl (except stainless steel cooler). To 
clean, use mild soapy water and cloth or sponge.  
 

c.

 

Condenser: 
For efficient operation, it is recommended that the condenser coil and fans be cleaned 
every 3 to 6 months. Remove front grille for access. Vacuum clean front surface of coil 
thoroughly or direct forced air through condenser fins. Failure to clean condenser can 
cause compressor malfunction and will void warranty.  
 

d.

 

Evaporator Fan:  
Evaporator pan should be cleaned periodically to prevent odors and maintain 
evaporating efficiency. The pan contains wicks to assist evaporation and should be 
replaced periodically.  

Summary of Contents for LABL-27-HG

Page 1: ...n includes complete refrigeration System cabinet construction finish IMPORTANT PLEASE RETAIN FOR YOUR RECORDS LABL 27 HG LABL 38 SG LABL 45 SG LABL 49 HG AND LABL 74 HG 101 Witmer Road Suite 700 Horsh...

Page 2: ...ustable to suit requirements See Instruction Sheet ILA 0904 for installing e Door Removal and Adjustment 1 Slide Doors Each door has its own Closing Spring located at the top and is positioned for Pro...

Page 3: ...r flow over the pan hastens condensate evaporation so that external drain plumbing is not required 3 Maintenance Caution Disconnect Electrical service before accessing mechanical enclosures having mov...

Page 4: ......

Page 5: ......

Page 6: ...LL SCALE SHELF SUPPORT FRONT WITH 1 4 TAB FULL SCALE NOTES INSTRUCTIONS 1 PLACE SHELF SUPPORTS WITH 1 4 TABS INTO PILASTER AT DESIRED POSITION NOTE THAT SUPPORTS WITH 1 4 TABS ARE LOCATED AT FRONT ONL...

Page 7: ...hields by using the identification mark on the end of the bulb Properly installed bulbs will have the mark centered between the halves of the lamp holder On units with shields the identification mark...

Page 8: ......

Page 9: ...sy Off Oven Cleaner Apply generous coating Excellent removal fatty acids miikstone Allow to stand for 10 to 15 Satisfactory for use on all where swabbing or rubbing minutes Rinse Repeated finishes is...

Page 10: ...if necessary Check air flow across condenser Unit runs OK but short cycles 1 Overload protector 1 Check wiring diag for correct wiring 2 Cold control 2 Differential set too close 3 Overcharge 3 Reduce...

Reviews: