BA_080 Rev 1J8 Pressure transmitter PASCAL CV4
Page 24/24
6.4.10 Overview with menue tree and device functions
Quick Setup
Language…
Select menu language
Pressure unit…
Select unit for measured pressure
Lower range val.…
Setting of the pressure value that should correspond to 4 mA (start of range)
Upper range val.…
Setting of the pressure value that should correspond to 20 mA (end of range)
Damping…
Setting the damping of the output signal
Device ID…
Setting the device ID
Adjustment
Pressure adjust.
Adjustment of the pressure measurement
Zero point…
Set device at ambient pressure to zero (0 bar rel) (only for gauge pressure devices)
Position correct.
Correct zero point error due to installation position (only for gauge pressure devices)
Pos.corr. on/off… Activate/deactivate position correction
Pos.corr. adjust… Correct position error at ambient pressure
Lower adjust….
Offset correction with applied reference pressure
Upper adjust….
Span correction with applied reference pressure
Current adjust.
Adjustment of the current output
Adjust. 4 mA…
Adjustment the output current on 4 mA at the end of measurement chain
Adjust 20 mA…
Adjustment the output current on 20 mA at the end of measurement chain
Display
Language…
Select menu language
Units
Select units for measured values
…
Select units for pressure and temperature
Screen mode
Configuration of the display layout and content
Screen layout…
Define screen structure and layout
1st value…
Content for 1st value in the selected layout
…
Content for further values (up to four)
Decimal point…
Selection of the decimal places of the 1st value by specifying the decimal point
Backlight…
Switch backlight on/off
Measurem./Output
Damping…
Setting the damping of the output signal
Output function…
Setting the output function (linear, inverse)
Lower range val.…
Setting of the pressure value that should correspond to 4 mA (start of range)
Upper range val.…
Setting of the pressure value that should correspond to 20 mA (end of range)
Alarm current…
Selection of the alarm current: High (>21 mA) or low (<3.6 mA)
Minimum current…
Lower limit of the output current (3.8…4.0 mA)
Maximum current…
Upper limit of the output current (20…21 mA)
Diagnosis
Operating hours…
Display of operating hour counter
Min/Max values
Display and reset of min/max-values
Last error…
Display and reset of the last critical error
Simulation
Current sim.…
Setting a fixed current value
Send-preambles…
Setting of the number of send preambles for HART communication
Pressure sim.…
Setting a fixed pressure value
Communication
HART address…
Setting the HART address for device identification in multi-drop mode
Device reset…
Restarting the device (such as after a power outage)
Device data…
Display of device data (same as from measured value display)
Factory reset…
Reset to factory settings
…
Display and reset the different min/max-values
System
Device ID…
Setting the device ID (e.g. to display a free-text in the display)
Current mode…
Setting the current mode (proportional/constant)
HART data…
Display of HART information (HART tag, HART descriptor, etc.)