BA_080 Rev 1J8 Pressure transmitter PASCAL CV4
Page 20/24
6.4.6
Menue "Diagnosis"
In this menue you can view and configure various diagnostic information. The following
diagnostic functions are available:
Menue entry
Description
Operating hours
Display of operating hour counter
Min/Max values
Displaying and resetting the min/max values
Last error
Display and reset of the last critical error
Table 14: "Diagnosis" menue
6.4.6.1
Min/Max values
The min/max values save the maximum and minimum values until they are reset by the
user. The menue item that shows the min/max value, can also be used to reset it. Some of
the min/max values are also directly accessible from the measured value display in the
device data (see 6.2.1).
OK
Figure 10: Display and resetting of the Min/Max values
6.4.7
Menue "Simulation"
In the "Simulation" menue, you can simulate the pressure as well as the current to test the
subsequent measuring chain.
Menue entry
Description
Current sim.
Setting a fixed current value
Pressure sim.
Setting a fixed pressure value
Table 15: "Simulation" menue
The current simulation influences only the current output. The pressure simulation takes all
settings into consideration, including the damping.