  BA_049_2019-06_10.00  Resistance thermometer clamp-on technology 

Page 3/6 

3.1.1 

Mounting the clamping element 

There are three options how to connect the device to the process: 

  

 

Figure 1:  mounting options: a) clamping block, b) clamping shoe and c) clamping bracket 

  

3.1.1.1 

Mounting the clamping block 

Required tools: 

Hexagon socket wrench 3 mm (mounting screws) 

Hexagon socket wrench 2 mm (vibration protection) 

  

  Turn  back  the  vibration  protection,  so  that  it 

does not exceed the semi-cycle groove for the 
pipe (see picture to the right). 

  Mount  the  clamping  block  with  the  included 

screws at the intended position on the pipe. Do 
not  exceed  the  allowed  tightening  torque  of  2 
Nm  for  pipe  diameters  up  to  17,2  mm  and  4 
Nm for bigger pipes. 

  Hand-tighten  the  vibration  protection.  Do  not 

tighten the vibration protection screw too hard. 
You  might  damage  the  clamping  block  or  the 
pipe. 

 

Figure 2:  Clamping block from below 

  

3.1.1.2 

Mounting the clamping shoe 

Required tools: 

depends on the used hose clamps 

  

  Mount  the  clamping  shoe  with  two  appropriate  hose  clamps  or  tightening  straps. 

The maximum width for a safe fit is 5 mm. 

  Tighten the clamps so that the clamping shoe cannot be moved by hand applying a 

usual hand force. 

  

Summary of Contents for GA261 Series

Page 1: ... Fax 49 4408 804 100 e mail sales labom com www labom com Page 1 6 Operating Instructions 1 General Information 2 1 1 General Safety Notes 2 1 2 Intended Use 2 1 3 Conformity with EU Regulations 2 1 4 ATEX Approval 2 2 Transportation and Storage 2 3 Installation and Commissioning 2 3 1 Mechanical Installation 2 3 2 Electrical Connection 5 4 Operation 6 4 1 Calibration 6 4 2 Maintenance Service 6 5...

Page 2: ...eclaration of Conformity document no KE_011 at www labom com 1 4 ATEX Approval Devices of the type GA26x1 are certified for use in explosive environments If you purchased a device with ATEX approval please refer to the accompanying docu ment XA_001 for ATEX relevant information 2 Transportation and Storage Store and transport the device only under clean and dry conditions preferably in the origi n...

Page 3: ...see picture to the right Mount the clamping block with the included screws at the intended position on the pipe Do not exceed the allowed tightening torque of 2 Nm for pipe diameters up to 17 2 mm and 4 Nm for bigger pipes Hand tighten the vibration protection Do not tighten the vibration protection screw too hard You might damage the clamping block or the pipe Figure 2 Clamping block from below 3...

Page 4: ...entical for all clamping elements First apply heat conductive paste to the tip of the measuring insert Heat conductive paste is mandatory for this type series for a good measuring accuracy Now insert the measuring insert into the bore in the clamping element You can position the insert in two ways Choose the position that simplifies the later cable routing Finally tighten the connection by turning...

Page 5: ...ile the voltage supply is switched off Circular connector 3 wire 4 wire 3 wire bridged 4 wire Transmitter Type PA2430 Transmitter IO Link Type PA2530 Cable gland 3 wire 4 wire Figure 5 Variants of electrical connection Route the cable so that it does not apply force or torque to the measuring insert For devices with field housing hold the housing with the other hand when you screw or unscrew the f...

Page 6: ...uipped with an integrated temperature transmitter you must not exceed 85 C at the housing Apply new heat conductive paste when you reinstall the measuring insert after the calibra tion This ensures a good and constant thermal coupling between insert and pipe For further details please consult the separate calibration guideline for the Clamp on family TA_008 4 2 Maintenance Service When properly in...

Reviews: