SET-1000 12 VDC 

 

 

                                                        D15648_E-2 

Installation and Operating Instructions 

 

Copyright © 2019 Labkotec Oy 

9/14 

We reserve the right for changes without notice 

The  settings  are  changed  using  the  upper  circuit  board’s  switches 
(MODE and DELAY) and potentiometer (SENSITIVITY) and the lower 
circuit board’s jumpers (Sensor selection and Buzzer). The switches are 
displayed in their default setting in the circuit board figure (figure 9). 

 

OPERATING DIRECTION (MODE) 

 

Switch  S1  is  used  to  set  the  operating  direction.  When  the 
switch  is  in  its  low  position,  Alarm  LED  indicator  as  well  as 
buzzer  is  on  and  relays  de-energize  when  the  liquid  level  is 
beneath the trigger level of the sensor (low level mode).  

This  setting  is  also  used,  when  an  alarm  of  an  oil-layer  on 
water is required. 

 

 

When the switch is in its high position the Alarm LED indicator 
as well as buzzer will be on and relays de-energize when the 
liquid  level  is  above  the  sensor

’s  trigger  level  (high  level 

mode). 

 

OPERATIONAL DELAY SETTING (DELAY) 

 

Switch  S2 is used to set the  operational  delay of the  device. 
When the switch is in low position relays operate and buzzer 
is on after 5 seconds after the level reaches trigger level, if the 
level still remains on the same side of the trigger level. 

When the switch is in high position, the delay is 30 seconds. 

Delays  are  operational  in  both  directions  (energizing,  de-
energizing). 

Alarm LED follows the  sensor current value and trigger level 
without delay. Fault LED has a fixed delay of 5 sec. 
 

 

TRIGGER LEVEL SETTING (SENSITIVITY) 

 

Trigger level setting is executed as follows: 

1.  Immerse the sensor

’s sensing element to the 

medium to the desired height 

– see sensor 

instructions, if needed. 

2.  Rotate the potentiometer so, that the Alarm LED is 

on and the relay de-energizes 

– please pay attention 

to the operational delay. 

3.  Check the function by lifting the sensor to the air and 

immersing it back to the medium. 

 

 

 

 

Summary of Contents for SET-1000 12 VDC

Page 1: ...D Tel 358 29 006 260 Fax 358 29 006 1260 24 9 2019 Internet www labkotec fi D15648_E 2 1 14 Copyright 2019 Labkotec Oy We reserve the right for changes without notice SET 1000 12 VDC Level switch for...

Page 2: ...able junction box 5 2 2 Cabling when using cable joint 6 3 OPERATION AND SETTINGS 7 3 1 Operation 7 3 2 Altering settings 8 4 TROUBLE SHOOTING 10 5 REPAIR AND SERVICE 11 6 SAFETY INSTRUCTIONS 11 APPEN...

Page 3: ...er alarms level control and alarms in oil sand and grease separators The LED indicators push buttons and interfaces of the device are described in figure 1 Figure 1 SET 1000 level switch features SET...

Page 4: ...t cover The connectors of the external conductors are isolated by separating plates The plates must not be removed The plate covering the connectors must be installed back after executing cable connec...

Page 5: ...to equipotential ground thru the ground terminal Other components of the system that need to be grounded can also be connected to the same ground terminal The wire used for equipotential grounding mu...

Page 6: ...cable between SET 1000 control unit and the sensor do not exceed the maximum allowed electrical parameters see appendix 1 Technical data IP rating of the cable joint is IP68 Make sure that the cable j...

Page 7: ...t a representative of the manufacturer Normal mode no alarms The level in the tank is below the sensor Mains LED indicator is on Other LED indicators are off Relays 1 and 2 are energized High level al...

Page 8: ...e it is already in alarm status When the Test push button is released The device returns without delay to the preceding status Fault alarm on When pressing the Test push button The device does not rea...

Page 9: ...will be on and relays de energize when the liquid level is above the sensor s trigger level high level mode OPERATIONAL DELAY SETTING DELAY Switch S2 is used to set the operational delay of the device...

Page 10: ...easure the voltage separately between the poles 10 and 11 The voltages should be between 10 3 11 8 V 3 If the voltages are correct measure the sensor current Do as follows 3 1 Disconnect sensor s wire...

Page 11: ...e atmosphere Sensors connected to it may be installed in explosive atmosphere zone 0 1 or 2 In case of installations in explosive atmospheres the national requirements and relevant standards as IEC EN...

Page 12: ...uts Two potential free relay outputs 250 V 5 A 100 VA Operational delay 5 sec or 30 sec Relays de energize at trigger point Operation mode selectable for increasing or decreasing level Electrical safe...

Page 13: ...0 15 mH 0 5 mH 1 0 mH 2 0 mH 5 0 mH Lo Ro 116 5 H IIC and 466 H IIB Table 2 Electrical parameters Maximum length of the sensor cable is determined by the resistance max 75 and other electrical parame...

Page 14: ......

Reviews: