background image

5

3) AUTOMATIC DOOR OPERATION

WARNING!!

Always contact the assistance technician before commissioning the door, to learn how the automation works.

Switch on the power supply by means of the system switch.

The automation electronic control unit beeps shortly to indicate that the automatic door is powered.

The first opening command starts a calibration cycle during which the door opening speed is very low until the end of the motion, to find 

the stop point; after the delay time has elapsed, the door closes back at normal speed.

3.1) NORMAL DOOR OPERATION

• 

When something enters the motion sensors (internal and/or external radar) detection area, the door opens and stays open until the 

sensors detect the presence, then once the pause delay has elapsed the door closes back.

• 

When the manual door opening button is pressed, the door opens and stays open until the command remains active, then once the 

pause delay has elapsed it closes back.

• 

If the closing safety sensor detects a presence, the door immediately reopens, and stays open as long as the sensor remains engaged.

• 

If the opening safety sensor detects a presence, the door slows down and proceeds very slowly until the opening motion is completed.

• 

If during the opening motion the door collides against an obstacle, it stops and closes back.

When it opens again, later, it slows down near the point where it had met the obstacle, to avoid further impact.

• 

If, during the closing motion, the door collides against an obstacle, it stops and opens back.

When it closes again, later, it slows down near the point where it had met the obstacle, to avoid further impact.

3.2) DOOR OPERATION IN NIGHT LOCK MODE

• 

The door cannot be opened by means of the external and internal radars.

• 

The door can only be opened by pressing the OPEN button, or using the Spyco radio‑control, if any.

• 

The safety functions (sensors and behaviour in case of obstruction) are active and operate as described in par. 3.1. related to normal 

operation.

4) PROGRAM SELECTORS

The program selector allows the user to select the operating mode of the door.

Depending on one's preferences, the EV‑MSEL mechanical key selector or the ET‑DSEL digital programmer can be used.

Each program selector is fully described below.

4.1) EV-MSEL MECHANICAL KEY SELECTOR

OPERATING MODE

Insert and turn the key of the selector EV‑MSEL to select the 

desired program.

         

Open door program

The door remains motionless in the position of complete opening.

        

Winter reduced opening program

For reducing the opening space

        

Automatic bidirectional program

The door automatically opens following any opening command.

        

Automatic unidirectional exit only program

To disable entry detection on external Radar input.

        

Night lock program

The door can only be opened through the OPEN input or using the SPYCO remote control, if any.

The key can be taken out of the selector when in any position in order to prevent undesired changes to the work program.

Summary of Contents for ETERNA 150 Series

Page 1: ...USER MANUAL TRANSLATION OF THE ORIGINAL INSTRUCTIONS ETERNA 90 ETERNA 150 PEDESTRIAN AUTOMATIC SLIDING DOOR ETERNA 90 150 EN Rel 2 0 10 2019 CD0709EN MU EN ...

Page 2: ...d maintenance conditions provided for by LABEL The equipment can be used by children of at least 8 years of age and by people with reduced physical sensory or mental skills or by inexperienced people provided they are supervised or after the same have received instructions relating to the safe use of the equipment and to the understanding of the relevant hazards Children should not play with the e...

Page 3: ... 4 1 EV MSEL MECHANICAL KEY SELECTOR 5 4 2 DIGITAL PROGRAM SELECTOR ET DSEL 6 4 2 1 GENERAL PROGRAMMING MENU 8 4 2 2 PASSWORD 9 4 2 3 LANGUAGE 11 4 2 4 SELECTOR OPTIONS 12 4 3 DIGITAL PROGRAM SELECTOR T NFC 13 4 3 1 T NFC SELECTOR USER PASSWORD MANAGEMENT 14 5 OPERATION IN CASE OF POWER SUPPLY FAILURE 15 6 USE OF THE PANIC EXIT BREAKOUT SYSTEM FOR ESCAPE ROUTES 16 7 NOTIFICATION OF ERRORS AND OPER...

Page 4: ...ng Opening safety sensor Key button ETERNA automation 1 2 3 4 5 6 7 2 TECHNICAL SPECIFICATIONS OF THE AUTOMATION ETERNA AUTOMATION MODEL ETERNA 90D 150D 2 leaves ETERNA 90S 150S 1 leaf Power supply 230V 50Hz 10 115V 60 Hz 10 Max power 100 W Frequency of use continuous Pause time Max 30 seconds Operating temperature 15 C to 50 C Protection class IP22 Power supply for external accessories 24 Vdc Dim...

Page 5: ...t had met the obstacle to avoid further impact If during the closing motion the door collides against an obstacle it stops and opens back When it closes again later it slows down near the point where it had met the obstacle to avoid further impact 3 2 DOOR OPERATION IN NIGHT LOCK MODE The door cannot be opened by means of the external and internal radars The door can only be opened by pressing the...

Page 6: ...am To disable entry detection on external Radar input Open door program The door remains motionless in the position of complete opening Manual free door Automatic operation is disabled and the door can be opened manually Automatic bidirectional program The door automatically opens following any opening command Automatic unidirectional entry only program To disable exit detection on internal Radar ...

Page 7: ...s the F2 button once the F2 symbol appears on the display To disable chemist s opening press the F2 button once more the F2 symbol goes off on the display F1 Door opening command Pressing the button F1 will open the door The button F1 may open the door even when the NIGHT LOCK work program is selected if the automation electronic control unit is set accordingly F3 It is only used if the ET DSEL di...

Page 8: ...y unauthorised access to the ET DSEL digital programmer DIAGRAM 1 The paragraphs below explain the procedure to be followed to manage the user password and to select the language SECTION RESERVED FOR TECHNICAL STAFF SECTION RESERVED FOR TECHNICAL STAFF SECTION RESERVED FOR TECHNICAL STAFF PASSWORD MANAGEMENT SECTION SELECTOR OPTION SECTION LANGUAGE SECTION SECTION RESERVED FOR TECHNICAL STAFF NOT ...

Page 9: ...r ET DSEL and changing the work program Using a primary password is optional and must be enabled by system owner The default technical password is A A A A A WARNING When enabling the password be very careful not to forget the access combination SERVICE PASSWORD for user It is a 5 character password that the system owner may provide to persons authorized to use the programmer ET DSEL With the servi...

Page 10: ...e procedure Enter the primary password Enter the new service password selecting a combination of 5 characters from the letters A B C D You are prompted to repeat the new password so enter again the previous combination If the password entered is correct PASSWORD OK is displayed for one second and the system returns to the PASSWORD MANAGEMENT section Press the EXIT button to return to the general p...

Page 11: ...ect PASSWORD ON OFF Press the button OK F1 Enter the primary password Enter the primary password Press the OFF button F1 to disable user password usage To return to the general programming menu press the EXIT button twice Access to the digital programmer ET DSEL as program selector now is free 4 2 3 LANGUAGE To select the language perform the operations listed below 1 Press the button for 5 second...

Page 12: ... others are not displayed Automatic bidirectional program Exit Only Program The buttons in this sub menu are used as follows The button allows to go to the next selection The button F2 allows to return to the previous selection The button F1 sets the function state to OFF The button F3 sets the function state to ON Entry Only Program Open door program Night lock program Manual free door Reduced op...

Page 13: ...other activation command To change a work program press the SET button once to exit the Screen Saver function and thus activate the selector the screen will increase its brightness now press SET again several times until you position on the desired work program If you have activated the program lock with the SLIDE function to exit the Screen Saver slide your finger from left to right on the button...

Page 14: ... the only one that enables to enter the user password area and should therefore be known only by the owner of the store organization in which the door is installed The service password 2 instead is used for employees or third parties that can use it to change the work programs of the door but cannot in any way change or disable both passwords To change the password 1 press the button A after selec...

Page 15: ...c lock operation with mains power supply on 5 OPERATION IN CASE OF POWER SUPPLY FAILURE If the battery module is installed in the automation automatic door operation is guaranteed by an emergency battery Depending on the programming of the automation electronic control unit the door may operate as follows a Automatically open and stay open if the program selector is not set to Night Lock b The doo...

Page 16: ...16 6 USE OF THE PANIC EXIT BREAKOUT SYSTEM FOR ESCAPE ROUTES SEMI FIXED LEAF MOBILE LEAF ENGAGEMENT OF THE MOBILE LEAF LEAVES REPOSITIONING DURING CLOSURE ...

Page 17: ...ervice centre to solve the issue The symbol is displayed The system has detected a machine operation error Contact the service centre to solve the issue Should any malfunction occur the Customer must contact the Support Centre and use the door manually without powering it 8 MAINTENANCE The maintenance plan must be observed to ensure the service life and the safe operation of the automatic door We ...

Page 18: ...ETERNA Made in Italy by S p A Via Ilariuzzi 17 A S Pancrazio P se 43126 PARMA ITALIA Tel 39 05 21 67 52 Fax 39 05 21 67 52 22 infocom labelspa it www labelspa com LABEL service centre ...

Reviews: