background image

LAARS Heating Systems

Page 26

1.

Touch the other lead of the voltmeter to both
terminals of the manual reset hi-limit switch. The
voltmeter should read 20 to 28VAC at both
terminals.

2.

If no voltage is detected at one terminal, reset the
manual reset hi-limit switch by pressing the reset
button. Check the temperature setting.

3.

If after pressing the reset button there is still no
voltage indicated at one terminal, replace the
manual reset hi-limit switch. An open switch may
indicate excessive water temperatures or
improper setting.

5.2.5 Testing the Flow Switch

The flow switch is a safety device that senses

water flow through the heater. When the switch senses
adequate water flow, it closes, allowing the heater to
fire. If the water flow is too low, the switch remains
open and prevents the heater from firing regardless of
the temperature control setting.

The flow switch is factory mounted and wired.

Never attempt to repair the flow switch. If the flow
switch is found to be defective, replace the flow
switch. To test the flow switch:
1.

Remove cap from flow switch (see Figure 22).

2.

Touch a voltmeter lead to each terminal of the
flow switch.

3.

If the voltmeter reads voltage at each of the
terminals, the switch is good.

4.

If there is no voltage at one terminal, it indicates
an open switch. Replace the flow switch.

5.2.6 Testing the Fusible Link

(flame roll-out switch)

The fusible link is a thermally fusible element

which shuts down the heater if it detects excessive
temperatures inside the heat exchanger compartment.
To test the fusible link (flame roll-out switch):

1.

Remove the electrical wiring from the fuses and
check across each fuse's terminals with a
continuity or ohm meter.

2.

Touch the voltmeter lead to the lower terminal on
the terminal block.

3.

If the voltmeter reads voltage, the safety fuse and
the fusible link are good.

4.

Replace the fuse when an open circuit is detected.
An open fuse indicates overheating in the heat
exchanger compartment.

5.

Check for blockage of the heat exchanger.

5.2.7 Testing the Fuse

To test the fuse:

1.

Clip a lead of the voltmeter to the grounding
terminal.

2.

Touch the other voltmeter lead to terminal
number (1) one on the terminal strip.

3.

If there is no voltage, replace the fuse. A blown
fuse is usually an indication of a short in the
24VAC circuit. It is important that the cause of
the short be found and repaired. Do not jumper or
bypass the fuse.

5.2.8 Testing the Ignition Control

WARNING

The ignition control and igniter operate on 120V
power. Keep this in mind while servicing the heater,
and take care to avoid electrical shock, which can
cause serious injury or loss of life.

The ignition control provides power to the

igniter, energizes the gas valve when there is a call for
heat, and senses when a flame is established. To test
the ignition control for spark ignition:
1.

Clip one lead from the voltmeter to the yellow
wire terminal on the transformer (or to terminal
number (12) twelve on the terminal strip).

2.

Touch the other voltmeter lead to terminal
number (6) six on the terminal strip.

3.

If the voltmeter reads voltage, the temperature
control and the manual reset hi-limit switch are
not keeping the heater from firing.

4.

Make sure the flame sensor is clean and
positioned in place, the terminal connection is
tight, and the lead is at least 3/8 inch (9.5 mm)
from the heater chassis and other metal parts.

NOTE: The ignition control cannot be repaired in the
field. If it does not operate properly, replace it.

5.2.9 Combustion Air Blower

This heater uses a fan-assisted combustion

process. For proper operation of the burners, inspect
the air blower for contamination one week after start-
up and every six (6) months thereafter.
1.

To inspect and service the blower, shut off all
electrical and gas supply to the heater.

2.

Disconnect the air hose from the air blower (see
Figure 39) and from the air inlet elbow.

3.

Remove the screws holding the blower bracket
(see Figure 39) off the inner front panel.

4.

Inspect the blower wheel. Clean the blower
housing and its wheel from any contamination or
debris.

5.

Check the air hose for any blockage or rupture.
Clean any blockage, if ruptured or holes exist,
replace the hose.

6.

Reassemble all parts securely in place.

OUT OF

PRODUCTION

Summary of Contents for VW-PW Series

Page 1: ...e or death Improper installation and or operation will void the warranty WARNING If the information in this manual is not followed exactly a fire or explosion may result causing property damage person...

Page 2: ...s Only 13 2 7 1 General Instructions 13 2 8 Electrical Wiring 14 SECTION 3 Operating Instructions 3 1 Start Up Procedure 15 3 2 Setting the Temperature Controls 15 3 2 1 Remote Water Heater Temperatur...

Page 3: ...er heaters must be installed in accordance with the procedures detailed in this manual or the Laars Heating Systems warranty will be voided The installation must conform to the requirements of the loc...

Page 4: ...t hood to the 6 position Molex plug on the side of the unit see Figure 15 Refer to instruction sheet included with cable 1 2 Warranty Laars Heating Systems Mighty Therm heaters are covered by a limite...

Page 5: ...LO NOx Volume Water Heater Page 5 Figure 2 Figure 3 Figure 4 Figure 5 Figure 6 Figure 7 Figure 8 Figure 9 Figure 10 Figure 11 Figure 13 Figure 14 Figure 15 Drafthood Switch Receptacle Figure 12 OUT O...

Page 6: ...on of a heater is a restricted section of a room not separated from the room by a door or partition and which meets the minimum clearances specified in this manual When the ceiling height exceeds 8 fe...

Page 7: ...tes the most common requirements specify that the space enclosure shall communicate with the outdoors in accordance with method 1 or 2 which follow Where ducts are used they shall be of the same cross...

Page 8: ...be taken by the installer to ensure safe operation In the event that the common vent is Method 2 One permanent opening commencing within 12 30 cm of the top of the enclosure shall be permitted The ope...

Page 9: ...pliances connected to a common vent cannot be assured including prevention of spillage of flue gasses into living spaces common venting should not be applied and appliances should each be vented separ...

Page 10: ...high enough to prevent scaling from hard water yet low enough to avoid erosion by soft water Hardness Grains per Parts Category Gallon per Million Soft 1 through 7 5 17 through 128 Normal 7 6 through...

Page 11: ...Relief Valve Figure 22 Pressure Relief Valve The factory provided pump on the PW heaters is sized to provide proper circulation through the heater and through the heater to tank circulation loop see...

Page 12: ...ailable To Drain Heater Service Valve Pump To Drain Conventional Tank Figure 24 Hot Water Supply with Horizontal Tank Note Heavy line indicates heater to tank circulation loop Hot Water Return from Bu...

Page 13: ...iment trap drip leg ahead of the gas controls see Figure 25 Fit the trap with a threaded cap which can be removed for cleaning valve is directed to an open drain and protected from freezing 2 Install...

Page 14: ...ectrical Code NFPA 70 In Canada use the latest edition of the Canadian Electrical Code CSA C22 2 No 0 Do not rely on the gas or water piping to ground the metal parts of the heater Often plastic pipe...

Page 15: ...trol 10 F 6 C higher The heater s temperature control senses the inlet water temperature to the heater The heater s manual reset high limit and automatic reset high limit if applicable senses heater o...

Page 16: ...is to be performed 5 Turn gas control knob clockwise to OFF 6 Replace heater door A This appliance does not have a pilot light It is equipped with an ignition device which automatically lights the hea...

Page 17: ...eil s il faut proc der l entretien 4 Tournez le bouton de contr l de gaz dans le sens des aiguilles d une montre jusqu la position OFF 5 Replacez le panneau d acc s aux commandes A Cet appareil ne com...

Page 18: ...LAARS Heating Systems Page 18 Figure 29 Mighty Therm LO NOx PW250 OUT OF PRODUCTION...

Page 19: ...Mighty Therm LO NOx Volume Water Heater Page 19 Figure 30 Mighty Therm LO NOx VW250 OUT OF PRODUCTION...

Page 20: ...LAARS Heating Systems Page 20 Figure 31 Mighty Therm LO NOx PW PH 400 OUT OF PRODUCTION...

Page 21: ...Mighty Therm LO NOx Volume Water Heater Page 21 Figure 32 Mighty Therm LO NOx VW HH 400 OUT OF PRODUCTION...

Page 22: ...gas supply fail to shut off turn off the manual gas control valve to the heater refer to troubleshooting section 3 4 Shut Down Procedure Shut down the heater following the instructions in Figures 27 a...

Page 23: ...eft side of the heater 2 Remove the large hex head plug located on the right side of the heater under the in out header see Figure 34 Perform this inspection after 60 days of and after 120 days of ope...

Page 24: ...ive 3 Make sure the gas valve is on and there is gas pressure in the line 4 Check all electrical connections and wiring Finding a loose connection or a charred wire can save a lot of time and money 5...

Page 25: ...tiquetez tous les fils avant de les d brancher Les erreurs de c blage peuvent nuire au bon fonctionnement et tre dangereuses S assurer que l appareil fonctionne ad quatement une fois l entretien termi...

Page 26: ...7 Testing the Fuse To test the fuse 1 Clip a lead of the voltmeter to the grounding terminal 2 Touch the other voltmeter lead to terminal number 1 one on the terminal strip 3 If there is no voltage r...

Page 27: ...Main All R0360400 11 Gas Pipe with Attachment All R0360200 12 Flame Sensor All R0360900 13 Manifold 250 R0365803 400 R0365805 14 Air Inlet Hose All R0360600 ELECTRICAL SYSTEM 15 Fusible Link Assembly...

Page 28: ...affle Retainer All S0083900 Key Model Order No Description No Part No 58 Baffle Heat Exchanger 8 250 10697403 400 10697405 59 End Baffle Heat Exchanger 250 R0365903 400 R0365905 FIREBOX COMPONENTS 60...

Page 29: ...ter Page 29 34 33 30 32 31 26 27 28 23 24 25 29 C See next page for details 64 66 18 B A 62 65 63 54 51 A 3 1 2 B 20 21 61 17 14 Burner Tray See next page for details 4 50 22 C 53 52 46 43 52 51 38 50...

Page 30: ...LAARS Heating Systems Page 30 39 58 57 40 40 44 36 38 41 45 44 45 35 12 16 13 7 10 9 59 59 55 37 41 15 8 6 11 56 OUT OF PRODUCTION...

Page 31: ...Mighty Therm LO NOx Volume Water Heater Page 31 OUT OF PRODUCTION...

Page 32: ...5 529 2000 FAX 805 529 5934 20 Industrial Way Rochester NH 03867 603 335 6300 FAX 603 335 3355 480 S Service Road West Oakville Ontario Canada L6K 2H4 905 844 8233 FAX 905 844 2635 www laars com Litho...

Reviews: