99
Service Manual - NeoTherm 500
Code Description
L or H
Procedure
178
Safety relay on at safe start check
L
Internal fault.
1. Reset module.
2. If fault repeats, replace module.
184
Invalid blower/ HSI output setting
L
1. Return to configuration mode and recheck selected
parameters, reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.
185
Invalid Delta T limit enable setting
L
1. Return to configuration mode and recheck selected
parameters, reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.
186
Invalid Delta T limit response setting
L
1. Return to configuration mode and recheck selected
parameters, reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.
187
Invalid DHW (Domestic Hot Water) high limit
enable setting
L
1. Return to configuration mode and recheck selected
parameters, reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.
188
Invalid DHW (Domestic Hot Water) high limit
response setting
L
1. Return to configuration mode and recheck selected
parameters, reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.
189
Invalid flame sensor type setting
L
1. Return to configuration mode and recheck selected
parameters, reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.
192
Invalid igniter on during setting
L
1. Return to configuration mode and recheck selected
parameters, reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.
193
Invalid ignite failure delay setting
L
1. Return to configuration mode and recheck selected
parameters, reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.
194
Invalid ignite failure response setting
L
1. Return to configuration mode and recheck selected
parameters, reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.
195
Invalid ignite failure retries setting
L
1. Return to configuration mode and recheck selected
parameters, reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.
Appendix 1 - Error Codes (continued)
App1
cont.