background image

Mighty Therm Hydronic Boiler

Page 13

4.

Flow Switch:

Standard on all models: Models HH and
PH, the switch is mounted in the outlet
“tee” connection. The flow switch shuts
down all burners in case of pump failure.

5.

Low Water Cut Off (Optional):

The low water cut off automatically shuts
off boiler whenever water level drops
below probe. Located at boiler inlet (model
PH) and at return header (model HH).

3B. Initial Start-Up

Lighting:

 Safe lighting and other performance

criteria were met with the gas manifold and control
assembly provided on the boiler when it underwent
tests specified in the ANSI Z21.13 standard.

Before placing the boiler in operation, be certain

that the boiler is filled with water and all air is purged
from the system. Once the boiler is connected to the
gas supply, the automatic safety shutoff devices must
be checked.

1.

Before beginning the tests, make sure the main
manual gas valve, and any other boiler firing
valves are in the “OFF” position.

2.

Make sure the boiler’s power switch is in the
“ON” position. After placing the manual pilot
gas valve in the open position and resetting all
safety devices, (high limit, pressure switch, low-
water cutoff, etc.) pilot(s) can be lit following
the procedure located on the boiler rating plate.

3.

Once the pilot(s) is lit and has been established
for five minutes, the flame failure response time
should be checked as follows:

Systems 9 and 4 

- (Intermittent ignition), natural

gas only: With this system pilots are automatically lit
when the operating controls call for heat. If the pilot
flame fails for any reason, the main valve is shut off
within one second and the pilot spark ignition is
initiated until the pilot flame has been reestablished.
On propane systems, unit locks out for safety. This
sequence should be checked by turning off the manual
pilot gas valve, and, at the same time, monitoring the
audible sparking at the pilot burner and signal
interruption to the main valve.

Caution

Propane gas is heavier than air and sinks to
the ground. Exercise extreme care in lighting
the boiler when so equipped.

System 16 

- (Electronically supervised standing

pilot system): Extinguish the pilot flame by placing
the manual pilot valve in the closed position, and at
the same time, begin recording the time it takes for the
output signal from the electronic ignition control to be

Figure 14. Gas Manual Valves.

interrupted. The signal interruption can be detected
either with a test light or a voltmeter. The response
time should never exceed one second.

4.

With the pilots lit, initial activation of the main
burners can be achieved by slowly opening the
main valve. The result should be a smooth
lighting of the main burners.

Hi-Limit Checkout :

After running the boiler for a long enough

period, bring the water temperature within the range
of the hi-limit and slowly back off the high limit
setting until the boiler shuts off. The main burners
should reignite when the hi-limit is reset and turned
back up to its original setting. The boiler should now
run until it shuts off automatically on operating
aquastat.

3C. To Start Up System:

1.

Start Up Boiler

Be certain system pump is running, then proceed
as follows:

a.

Turn off main electrical switch.

b.

Turn off all manual gas valves and wait
five minutes (see Figure 14).

c.

Set operating control to lowest setting.

d.

Slowly turn manual gas valve to “ON”.

e.

Reset all safety valve switches (manual
reset high limit and low water cut off).

Summary of Contents for Mighty Therm HH 500

Page 1: ...se gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance WHAT TO DO IF YOU SMELL GAS Do not try to light any appliance Do not touch any electrical switch do not...

Page 2: ...Venting 8 2C Installation of Outdoor Boilers 9 2D Gas Supply and Piping 9 2E Electrical Wiring 10 2F Water Piping of System 11 2G Filling Fully Connected System 11 SECTION 3 Operation 3A Controls Gen...

Page 3: ...149 requirement When required by the authority having jurisdiction the installation must conform to American Society of Mechanical Engineers safety codes for controls and safety devices for automatica...

Page 4: ...ult in an excessive water temperature rise and unstable boiler operation If the system water flow is variable it must not be allowed to fall below 30 of full flow The boiler must be equipped with stag...

Page 5: ...the boiler piping system shall be equipped with a flow control valve or other automatic means to prevent gravity circulation of chilled water through the boiler Chilled water in the boiler will create...

Page 6: ...es the general requirements specify that boiler rooms should be provided with two permanent air supply openings communicating directly through the wall to outside air one within 12 inches 305mm of the...

Page 7: ...t be completely isolated and this could cause flue products to accumulate in the room Additional air must be supplied to compensate for such exhaust The information in Table 3 is not applicable in ins...

Page 8: ...id ending heater vents near air conditioning or air supply fans The fans can pick up exhaust flue products from the boiler and return them inside the building creating a possible health hazard A minim...

Page 9: ...zing any portion of the common venting system the common venting system should be resized to approach the minimum size as determined using the appropriate tables in Appendix G in the National Fuel Gas...

Page 10: ...corrosion or stress cracking the piping must be rinsed with water after testing unless it has been determined that the leak test solution is noncorrosive 2E Electrical Wiring Electrical diagrams are i...

Page 11: ...l radiation units at the highest points in the piping throughout the system unless automatic air bleeders are provided at such points 5 Run system circulating pump for a minimum of 30 minutes with the...

Page 12: ...8 seconds and provides 100 safety shutdown 2 Operating Controls a Electrically Operating Controls Single two stage four stage or modulating aquastats are provided in models HH and PH boilers to contro...

Page 13: ...nd the pilot spark ignition is initiated until the pilot flame has been reestablished On propane systems unit locks out for safety This sequence should be checked by turning off the manual pilot gas v...

Page 14: ...rature see Table 5 3 Minimum input rates The low firing rate setting must be equal to or greater than the specified minimum input rating as shown on the appliance rating plate Laars boilers use gas va...

Page 15: ...ccurrence dampen the soot deposits with wet brush or fine water spray before servicing or cleaning the heat exchanger With a wire brush remove soot and loose scale from heat exchanger Clean fallen deb...

Page 16: ...ve terminals Check continuity to actuator coil If open circuit or short is indicated replace coil or operator Possible Cause What To Do A Static pressure in system A Calculate height of water in excee...

Page 17: ...o the system Clean tubes with tube cleaning kit Determine hardness Check for modified flow if necessary 7 WATER DRIPPING IN FIREBOX Possible Cause What To Do 6 SOOT IN FLUEWAYS OR IN TUBES OR NOXIOUS...

Page 18: ...81 10364300 10364300 10364300 10364300 10364300 10364300 10364300 10364300 10364300 Return Header S00642 Bronze 10364301 10364301 10364301 10364301 10364301 10364301 10364301 10364301 10364301 13 Inle...

Page 19: ...ature Control Wells Inlet Outlet Header 1 Firing Mode L K C 2 Dry Wells 2 Firing Mode H A Natural Gas Boilers Heaters 500 thru 850 2 Dry Wells 1010 thru 1430 3 Dry Wells 1670 thru 1825 4 Dry Wells B P...

Page 20: ...e Rear Panel Heat Shield Weldment 10540401 10540402 10540403 10540404 10540405 10540406 10540407 10540408 10540409 33 End Panel Upper Right 10531600 10531600 10531600 10531600 10531600 10531600 105316...

Page 21: ...Mighty Therm Hydronic Boiler Page 21 Figure 20 Tile Assemblies...

Page 22: ...4600 W0034600 W0034600 W0034600 Pilot Burner Honeywell Standing Pilot Propane W0034400 W0034400 W0034400 W0034400 W0034400 W0034400 W0034400 W0034400 W0034400 53 Pilot Burner Johnson IID Pilot Nat W00...

Page 23: ...1400 F0011400 F0011400 75 Plug Sq Hd 1 NPT P0033000 P0033000 P0033000 P0033000 P0033000 P0033000 P0033000 P0033000 P0033000 76 Plug 1 2 NPT P0026900 P0026900 P0026900 P0026900 P0026900 P0026900 P00269...

Page 24: ...0703 10550704 97 Burner Tray I I D Mech Mod 3 4 Sect Manifold Nat 10551201 10551202 10551203 10551204 10551205 98 Burner Tray St Pl Mech Mod SpIt Manifold Pro 10550301 10550302 10550303 10550304 99 Bu...

Page 25: ...Mighty Therm Hydronic Boiler Page 25 Figure 21 Outdoor Parts...

Page 26: ...9903 10659904 10659905 10659906 10659907 10659908 10659909 10 Rear Base Extension 10658501 10658502 10658503 10658504 10658505 10658506 10658507 10658508 10658509 11 Gas Train Interface Plate 20050200...

Page 27: ...6 10661507 10661508 10661509 2 2 2 4 4 4 4 4 4 10 Baffle Heat Exchanger 10667701 10667702 10667703 10667704 10667705 10667706 10667707 10667708 10667709 7 14 14 14 14 28 28 28 14 41 Middle Front Panel...

Page 28: ...ould be ordered separately SECTION 8 Optional Parts Descriptions and Order Numbers H0117400E Standard PH Model Pumps Armstrong 1050 PH Model Part Number Description 500 850 A2000700 1 3 hP with 3 1 2...

Reviews: