Mascot FT
Error Code 44
• Check the “Min Fire” fan speed. Should be
1440 rpm (Plus or Minus 100 rpm)
• Set DIP Switch #7 to the
ON
position to
run boiler in
“Min Fire
” (see attached)
• Press the Status button. Scroll to
C:Fr
to
read fan speed.
(see attached)
• If fan speed is not 1580-1620 (Plus or
Minus 100 rpm)
• Set
9:FL
to
-8
(see attached)
• Verify “Min Fire” fan speed is 1440 (Plus
or Minus 100 rpm)
• If not, Increase or decrease 9:FL to
achieve 1440
“Min Fire” fan speed
• Set DIP SW #7 to the
OFF
position