background image

Mascot FT

Error Code 44

• Check the “Min Fire” fan speed. Should be 

1440 rpm (Plus or Minus 100 rpm)

• Set DIP Switch #7 to the 

ON

position to 

run boiler in 

“Min Fire

” (see attached)

• Press the Status button. Scroll to 

C:Fr

to 

read fan speed. 

(see attached)

• If fan speed is not 1580-1620 (Plus or 

Minus 100 rpm)

• Set 

9:FL

to 

-8 

(see attached)

• Verify “Min Fire” fan speed is 1440 (Plus 

or Minus 100 rpm)

• If not, Increase or decrease 9:FL to 

achieve 1440 

“Min Fire” fan speed

• Set DIP SW #7 to the 

OFF

position

Reviews: