Laars LMH User Manual Download Page 6

User’s Manual - Mascot II Boilers and Water Heaters

Page 5

proper gas supply. Wait 5 minutes and start the
unit again.

5.

Turn Mascot II on.

6.

After placing the appliance in operation, the
Burner Safety Shutoff Device must be tested

:

(a)

Close gas shutoff valve with burner operating.

(b)

Flame will go out and blower will continue to
run for the post purge cycle. One or three
additional attempts to light will follow including
pre-purge, ignitor on, valve/flame on and post
purge. Ignition will not occur as the gas is off.
The ignition control will lockout.

(c)

Open gas shutoff valve. Reset the boiler
control by pressing the 

RESET

 button on the

control or on the display. Restart the
appliance. The ignition sequence will start
again and the burner will start. The appliance
will return to its previous mode of operation.

 Caution

Should any odor of gas be detected, or if the gas
burner does not appear to be functioning in a normal
manner, CLOSE MAIN SHUTOFF VALVE. Do not
shut off switch. Contact your heating contractor, gas
company, or factory representative.

2.2.2  Boiler Setup and Adjustment

1.

Measure the CO

2

 in the flue products at high fire.

The Mascot II can be forced to high fire to allow
for easier setup. The CO

2

 readings should be

between the values shown in 

Table 2

. If the CO

2

 is

not within the range shown, adjustments may be
made. To adjust the high fire CO

2

, locate the high fire

adjuster screw according to the appropriate figure.
Slowly make adjustments in 1/16 of a revolution
increments until the CO

2

 is within the range

identified.

2.

Measure the CO

2

/O

2

 in the flue products at low

fire. Mascot II can be forced to low fire to allow
for easier setup. CO

2

 readings should be between

the values shown in 

Table 2

. If the CO

2

 is not

within the range shown, adjustments may be made.
To adjust the low fire CO

2

, locate the low fire

adjuster screw according to the appropriate figure.
Slowly make adjustments in 1/16 of a revolution
increments until the CO

2

 is within the range

identified (see 

Figure 3

).

3.

Repeat steps 1 and 2 to confirm that the CO

2

ranges are within the required ranges. Adjust if
necessary.

4.

If any of the measurements cannot be adjusted
to the specified ranges or the CO levels are
above 150ppm when adjusted please consult the
factory for further information.

   

 WARNING

Improper adjustment may lead to poor combustion
quality, increasing the amount of carbon monoxide
produced. Excessive carbon monoxide levels may
lead to personal injury or death.

2.3  Shutting Down Mascot II

1.

Turn off the main electrical disconnect switch.

2.

Close all manual gas valves.

3.

If freezing is anticipated, drain Mascot II and be
sure to also protect building piping from freezing.
All water must be removed from heat exchanger
and condensate trap or else damage from freezing
may occur.

This step to be performed by a qualified service person.

2.4  To Restart Mascot II

If drained, follow 

Section 2.1

 in this manual for

proper filling and purging.

1.

Turn off the main electrical disconnect switch.

2.

Close all manual gas valves.

3.

WAIT FIVE (5) MINUTES.

4.

Set the aquastat or thermostat to its lowest setting.

5.

Open all manual gas valves.

6.

Reset all safety switches (pressure switch, manual
reset high limit, etc.).

7.

Set the temperature controller to the desired
temperature setting and switch on electrical power.

8.

Burner will go through a prepurge period and
ignitor warm-up period, followed by ignition.

 MENU ITEM

FUNCTION

RANGE

DEFAULT

 Outlet water

Displays the current outlet

55-190°F

120°F

 temperature

water temperature & allows
the setpoint to be adjusted

 Inlet water

Displays the current inlet

 temperature

water temperature

 Delta T

Displays the current

temperature rise across
the heat exchanger

 Stack

Displays the current stack

 temperature

temperature

 Outdoor

Displays the current outdoor

 temperature

air temperature

 Firing Rate

Displays an indicator of the

current firing rate based
upon fan RPM. The actual
firing rate may vary.

Table 1. User Mode Menu Structure.

Summary of Contents for LMH

Page 1: ...t exceed 13 W C 3 2kPa All installations must be made in accordance with 1 American National Standard Z223 1 NFPA54 Latest Edition National Fuel Gas Code or 2 CSA B149 1 Natural Gas and Propane Instal...

Page 2: ...oxide gas in flue gases which could cause serious injury property damage or death Improper installation and or operation will void the warranty AVERTISSEMENT Assurez vous de bien suivres les instructi...

Page 3: ...luded with each Mascot II The PRV should be installed prior to filling the system Refer to Figures 1 and 2 for PRV locations IMPORTANT The inlet gas pressure to the appliance must not exceed 13 W C 3...

Page 4: ...should be filed with the carrier The carrier not the shipper is responsible for shortages and damage to the shipment whether visible or concealed 1 5 Unpacking The Mascot II is shipped in a single cra...

Page 5: ...loop then the system is ready for operation 12 Refer to local codes and the make up water valve manufacturer s instructions as to whether the make up water valve should be left open or closed 13 Afte...

Page 6: ...Slowly make adjustments in 1 16 of a revolution increments until the CO2 is within the range identified see Figure 3 3 Repeat steps 1 and 2 to confirm that the CO2 ranges are within the required rang...

Page 7: ...Page 6 GAS TYPE HIGH FIRE CO2 LOW FIRE CO2 Natural 9 0 0 offset Propane 10 0 Table 2 CO2 Range Figure 3 Adjustment Screws and Settings for CO2 ADJUSTMENT RANGE High Fire CO2 9 0 8 8 Nat 10 0 9 8 LP L...

Page 8: ...doit tre install par un organisme de service conform ment aux instructions du fabricant et tous les codes et les exigences de l autorit comp tente Si les informations contenues dans ces instructions n...

Page 9: ...rvice Advisors 20 Industrial Way Rochester NH 03867 603 335 6300 Fax 603 335 3355 Applications Engineering 1869 Sismet Road Mississauga Ontario Canada L4W 1W8 905 238 0100 Fax 905 366 0130 www Laars c...

Reviews: