Laars LMH User Manual Download Page 5

LAARS Heating Systems

Page 4

SECTION 2.
Operating Instructions

2.1  Filling the Boiler System

1.

Ensure the system is fully connected. Close all
bleeding devices and open make-up water valve.
Allow system to fill slowly.

2.

Move manual lever on 3-way valve actuator to
"open" position, allowing air to purge from boiler
loop. Valve is normally in DHW position until
there is a call for Central Heat via "T-T" contacts.
If make-up water pump is employed, adjust
pressure switch on pumping system to provide a
minimum of 12 psi (81.8 kPa) at the highest point
in the heating loop.

3.

If a water pressure regulator is provided on the
make-up water line, adjust the pressure regulator to
provide at least 12 psi (81.8 kPa) at the highest
point in the heating loop.

4.

Open bleeding devices on all radiation units at the
high points in the piping throughout the system,
unless automatic air bleeders are provided at such
points.

Note that there is an air bleed located on the left
side of Mascot II, on top of the jacket.

5.

Cycle the boiler pump on and off 10 times, 10
seconds on and 10 seconds off to remove all air
from the heat exchanger. Then run system and
appliance pump for a minimum of 30 minutes with
the gas shut off.

6.

Using manual lever located on left side of 3-way
valve actuator, move from "open" position back to
closed position repeatedly. This process forces air
out of the internal DHW loop.

 WARNING

Failure to remove all air from the heat exchanger could
lead to property damage, severe injury or death.

7.

Recheck all air bleeders as described in Step 4.

8.

Start up boiler according to the procedure in this
manual. Operate the entire system, including the
pump, boiler, and radiation units for one (1) hour.

9.

Shut down the entire system and vent all radiation
units and high points in the system piping, as
described in Step 4.

10.

Close make-up water valve and check strainer in
pressure reducing valve for sediment or debris
from the make-up water line. Reopen make-up
water valve.

11.

Check gauge for correct water pressure and also
check water level in the system. If the height
indicated above the boiler insures that water is at
the highest point in the circulating loop, then the
system is ready for operation.

12.

Refer to local codes and the make-up water valve
manufacturer’s instructions as to whether the
make-up water valve should be left open or closed.

13.

After placing the unit in operation, the ignition
system safety shutoff device must be tested.

First, shut off the manual gas valve, and call the
unit for heat. Main gas terminals will be energized,
attempting to light, for four (4) seconds, and then
will de-energize. The unit will go into lockout after
the required number of trial for ignition periods.

Second, turn the power off, press the manual reset
button on the boiler control, or the user display,
open the manual gas valve and allow the unit to
light. While the unit is operating, close the manual
gas valve and ensure that power to the main gas
valve has been cut.

14.

Within three (3) days of start-up, recheck all air
bleeders and the expansion tank as described in
Steps 4 and 8 above.

Important Note:

 The installer is responsible for

identifying to the owner/operator the location of all
emergency shutoff devices.

 WARNING

Do not use this appliance if any part has been under
water. Immediately call a qualified service technician
to inspect the appliance
and to replace any part of the control system and any
gas control that may have been
under water.

2.2  Operating the Burner and Set Up

Initial setup must be checked before the unit is put

in operation. Problems such as failure to start, rough
ignition, strong exhaust odors, etc. can be due to
improper setup. Damage to the boiler resulting from
improper setup is not covered by the limited warranty.

2.2.1  Burner Operation

REQUIRED TOOLS:

 differential pressure gauge

capable of reading negative 0.01 inches W.C. (0.002kPa),
screw drivers, and combustion analyzer.

1.

Using this manual, make sure the installation is
complete and in full compliance with the
instructions and all local codes.

2.

Determine that the appliance and system are filled
with water and all air has been bled from both.
Open all valves.

3.

Observe all warnings on the Operating Instructions
label and turn on gas and electrical power to
appliance.

4.

Mascot II will enter the start sequence. Blower and
pump will energize for pre-purge, then the ignition
sequence starts. After all safety devices are
verified, the gas valve opens. If ignition doesn’t
occur, turn off the Mascot II, check that there is

Summary of Contents for LMH

Page 1: ...t exceed 13 W C 3 2kPa All installations must be made in accordance with 1 American National Standard Z223 1 NFPA54 Latest Edition National Fuel Gas Code or 2 CSA B149 1 Natural Gas and Propane Instal...

Page 2: ...oxide gas in flue gases which could cause serious injury property damage or death Improper installation and or operation will void the warranty AVERTISSEMENT Assurez vous de bien suivres les instructi...

Page 3: ...luded with each Mascot II The PRV should be installed prior to filling the system Refer to Figures 1 and 2 for PRV locations IMPORTANT The inlet gas pressure to the appliance must not exceed 13 W C 3...

Page 4: ...should be filed with the carrier The carrier not the shipper is responsible for shortages and damage to the shipment whether visible or concealed 1 5 Unpacking The Mascot II is shipped in a single cra...

Page 5: ...loop then the system is ready for operation 12 Refer to local codes and the make up water valve manufacturer s instructions as to whether the make up water valve should be left open or closed 13 Afte...

Page 6: ...Slowly make adjustments in 1 16 of a revolution increments until the CO2 is within the range identified see Figure 3 3 Repeat steps 1 and 2 to confirm that the CO2 ranges are within the required rang...

Page 7: ...Page 6 GAS TYPE HIGH FIRE CO2 LOW FIRE CO2 Natural 9 0 0 offset Propane 10 0 Table 2 CO2 Range Figure 3 Adjustment Screws and Settings for CO2 ADJUSTMENT RANGE High Fire CO2 9 0 8 8 Nat 10 0 9 8 LP L...

Page 8: ...doit tre install par un organisme de service conform ment aux instructions du fabricant et tous les codes et les exigences de l autorit comp tente Si les informations contenues dans ces instructions n...

Page 9: ...rvice Advisors 20 Industrial Way Rochester NH 03867 603 335 6300 Fax 603 335 3355 Applications Engineering 1869 Sismet Road Mississauga Ontario Canada L4W 1W8 905 238 0100 Fax 905 366 0130 www Laars c...

Reviews: