Laars LMC User Manual Download Page 3

User’s Manual - Mascot II Boilers and Water Heaters

Page 3

1. Caring For Your Mascot II

Your Mascot II will require very little 

maintenance. However, as with any fine appliance 

there are certain steps that should be taken to ensure 

continuing optimum performance.

1.1  General Care

Keep the area around the Mascot II clean and 

free from combustible materials, gasoline and other 

flammable liquids and vapors.

The Mascot II must be completely isolated and 

protected from any source of corrosive chemical fumes 

such as trichlorethylene, perchlorethylene, chlorine, 

etc.

Keep bottom and top openings on the boiler free 

for proper ventilation of interior components.

Do not obstruct or block a free flow of air to the 

boiler to ensure proper ventilation.

If desired, clean the jacket surfaces with a damp 

cloth and mild detergent. Do not use flammable 

cleaning materials.

If sidewall vented, keep the vent terminal clear 

of obstructions — do not pile snow against the vent 

terminal. Clean the intake screen often, and then 

develop an appropriate maintenance schedule.

1.2  Annual Inspection of Flue and Vents

Visually inspect the vent pipe once a year. Should 

any deterioration exist, have the affected parts replaced 

by a qualified service person.

1.3  In the Event of a Power Failure

The Mascot II can not be operated during 

an electrical power outage. If there is an extended 

power outage with danger from freezing, then the 

Mascot II (and all other water systems) should be 

drained completely. When draining the boiler, turn 

off main electrical disconnect switch. When placing 

back in service, refer to Section 2 of this Manual for 

instruction. All draining and filling must only be done 

by a qualified service person.

1.4  Full Service Every Three (3) Years

In addition to the annual visual inspections, a 

qualified service agency should conduct a detailed 

inspection of all flue product carrying areas of the 

boiler and its venting system.

2. Filling, Shut Down and Restart

2.1   Filling the Boiler System

1.  Ensure the system is fully connected. Close all 

bleeding devices and open make-up water valve. 

Allow system to fill slowly.

2.  Move manual lever on 3-way valve actuator to 

“open” position, allowing air to purge from boiler 

loop. Valve is normally in DHW position until 

there is a call for Central Heat via “T-T” contacts. 

3.  If a water pressure regulator is provided on the 

make-up water line, adjust the pressure regulator 

to provide at least 12 psi (81.8 kPa) at the highest 

point in the heating loop.

4.  Open bleeding devices on all radiation units at the 

high points in the piping throughout the system, 

unless automatic air bleeders are provided at such 

points.

 

Note that there is an air bleed located on the left 

side of Mascot II, on top of the jacket.

5.  Cycle the boiler pump on and off 10 times, 10 

seconds on and 10 seconds off to remove all air 

from the heat exchanger. Then run system and 

appliance pump for a minimum of 30 minutes with 

the gas shut off.

6.  Using manual lever located on left side of 3-way 

valve actuator, move from “open” position back to 

closed position repeatedly. This process forces air 

out of the internal DHW loop.

 WARNING

Failure to remove all air from the heat exchanger could 

lead to property damage, severe injury or death.

7.  Recheck all air bleeders as described in Step 4.
8.  Shut down the entire system and vent all radiation 

units and high points in the system piping, as 

described in Step 4.

9.  Close make-up water valve and check strainer in 

pressure reducing valve for sediment or debris from 

the make-up water line. Reopen make-up water 

valve.

10.  Check gauge for correct water pressure and then 

the system is ready for operation.

11.  Refer to local codes and the make-up water valve 

manufacturer’s instructions as to whether the 

make-up water valve should be left open or closed.

12.  After placing the unit in operation, the ignition 

system safety shutoff device must be tested. 

Summary of Contents for LMC

Page 1: ...xide gas in flue gases which could cause serious injury property damage or death Improper installation and or operation will void the warranty AVERTISSEMENT Assurez vous de bien suivres les instructio...

Page 2: ...For Your Mascott II 3 2 Filling Shut Down and Restart 3 4 3 Digital Display and Control 5 7 To open the front panels Remove these two phillips screws and fold lower door down The middle panel will th...

Page 3: ...ion of all flue product carrying areas of the boiler and its venting system 2 Filling Shut Down and Restart 2 1 Filling the Boiler System 1 Ensure the system is fully connected Close all bleeding devi...

Page 4: ...ezing All water must be removed from heat exchanger and condensate trap or else damage from freezing may occur This step to be performed by a qualified service person 2 3 To Restart Mascot II If drain...

Page 5: ...rature units LBTHODLOD Outdoor reset enable disable enables menu items LBT Low boiler setpoint during outdoor reset HOD High outdoor temperature setpoint LOD Low outdoor temperature setpoint RMT Add U...

Page 6: ...hen there is a central heat call supplied the system pump relay is active If there is a DHW call supplied while the central heat call is active the system pump turns off This happens because of domest...

Page 7: ...er operation the LL menu should be set to LDR To set the boiler to slave SLA should be selected 3 8 3 Lead Lag Address The Lead Lag address must be set for each boiler connected to the lead lag system...

Page 8: ...mer Service Service Advisors 20 Industrial Way Rochester NH 03867 603 335 6300 Fax 603 335 3355 Applications Engineering 1869 Sismet Road Mississauga Ontario Canada L4W 1W8 905 238 0100 Fax 905 366 01...

Reviews: