1
1 Equipment
Handling
1.1
Storing the TPSD
If the TPSD is to be stored for more than a few days after delivery, it should be stored within its shipping
container. The location chosen for storage should be within an ambient temperature of -40 to 185° F (-40 to
85° C) with a non-condensing relative humidity of 0 to 95%. Storage should not exceed 2 years due to the
limited shelf life of the DC filter capacitors when they are not in service.
1.2
Moving the TPSD
After careful inspection and upon verification that the TPSD is undamaged, identify the enclosure style and
weight of the TPSD unit. Refer to the tables below.
Output
Voltage
Frequency
Ampere Rating
6 ADC
12 ADC
20 ADC
25 ADC
30 ADC
35 ADC
50 ADC
75 ADC
100 ADC
24 VDC
60 Hz
4B Case
4B Case
4 Case
4 Case
4 Case
4 Case
4 Case
4 Case
9 Case
90 lbs
90 lbs
100 lbs
125 lbs
150 lbs
154 lbs
175 lbs
211 lbs
225 lbs
(40.8 kg)
(40.8 kg)
(45.4 kg)
(56.7 kg)
(68 kg)
(69.9 kg)
(79.4 kg)
(95.7 kg)
(102.1 kg)
50 Hz
4 Case
4 Case
4 Case
4 Case
4 Case
4 Case
9 Case
110 lbs
138 lbs
165 lbs
170 lbs
193 lbs
233 lbs
248 lbs
(49.8 kg)
(62.6 kg)
(74.8 kg)
(77.1 kg)
(87.5 kg)
(105.7 kg) (112.5 kg)
48 VDC
60 Hz
4B Case
4B Case
4 Case
4 Case
4 Case
4 Case
4 Case
9 Case
9 Case
90 lbs
110 lbs
150 lbs
150 lbs
155 lbs
180 lbs
205 lbs
295 lbs
321 lbs
(40.8 kg)
(49.9 kg)
(68 kg)
(68 kg)
(70.3 kg)
(81.7 kg)
(93 kg)
(133.8 kg) (145.6 kg)
50 Hz
4 Case
4 Case
4 Case
4 Case
4 Case
9 Case
9 Case
165 lbs
165 lbs
171 lbs
198 lbs
225 lbs
325 lbs
354 lbs
(74.8 kg)
(74.8 kg)
(77.6 kg)
(89.8 kg)
(102.1 kg)
(147.4 kg) (160.6 kg)
130 VDC
60 Hz
4 Case
4 Case
4 Case
4 Case
9 Case
9 Case
9 Case
140 lbs
175 lbs
225 lbs
250 lbs
319 lbs
372 lbs
532 lbs
(63.5 kg)
(79.4 kg)
(102.1 kg)
(113.4 kg) (144.7 kg)
(168.7 kg)
(241.3 kg)
50 Hz
4 Case
4 Case
4 Case
4 Case
9 Case
9 Case
9 Case
154 lbs
193 lbs
233 lbs
275 lbs
352 lbs
410 lbs
586 lbs
(69.9 kg)
(87.5 kg)
(105.7 kg)
(124.7 kg) (159.7 kg)
(186 kg)
(265.8 kg)
Table 1 - Case Type and Weight (Single Phase, 6-100 ADC)